Loading...
HomeMy WebLinkAboutB24-2812 PUMP SPECS /eFIRE PUMP Submittal a xylem brand Job/Project: I Representative: I ESP-Systemwize:WIZE-EC18E444 Created On:09/06/2024 I Phone: I I Location/Tag: I Email: I I Engineer: I Submitted By: I Date: I I Contractor: I Approved By: I Date: I In-Line Fire Pump Selection Criteria 11 NFPA Limits Pump Model:6x6x9.5F-L Rated Flow 750 US gpm 140%Head of Rated Head 84 psi Nom.Spe e d:3550 rpm Rated Head 60 psi 65%Head at 150%Flow 39 psi Market:Listed Fire Pump Imp.Dia 7.02 in Flow at 150% 1125USgpm Approval/Listing:FM/UL Power Required at Duty 40.2 hp Head at 150% 42.3 psi Rated Efficiency 65.1% Power Regat150% 38.5hp Fluid Water Efficiencyat 150% 72.1% Temperature 85°F Max BHP 41 hp Sp.Gravity 1.000 Closed Valve Head 80.1 psi 140% Head if Rated Head 84PSI so — 7o 6o a v e Ix 50 I I 40 n ` i ` 150%of Raled Capaciy I 4150%=1125US gpri H65%=39psi Rated Capacity I I 20 30 p _ 2 N Z 10 _____________- 0 103 203 303 403 500 600 700 800 800 1000 1100 1200 1300 -6S7 H S p p m Typical Performance Curve is shown.Fire Pumps are tested to ANSI/HI 14.6 acceptance grade 1 U. 'ated Duty Point is guaranteed within the following tolerances:Flow 0%to+10%,Head 0%to+6%. 0 OTHER POINTS ARE GUARANTEED.PLEASE CONSULT FACTORY IF NEEDED. Performance Curve Data Flow(USgpm) Head(psi) Efficiency(%) Power Required(hp) NPSHr(ft) 0 80.1 0 0 9 187 75.9 24.1 38.1 9 375 71.6 40.1 39 9 562 66.5 54.5 39.9 9.01 750 60 65.1 40.2 10.3 1125 42.3 72.1 38.5 16.6 1419 23.5 56.5 34.5 23 xylem Xylerc. 8200 N.A 200 N.Austin Avenue Morton Grove,Illinois 60053 Let's Solve Water Phone:(847}96673700 Fax:(847)965-8379 www.acfirepump.com ac F,�v a Deadama.koi xylem mo,o,b a�se.d„„_