HomeMy WebLinkAbout017-100-038 EHDR19-01193 CAMP FIRE SEPTIC REPORTPublic Health Department Camp Fire Septic System
Inspection Report revised 032720
Environmental Health
202 Mira Loma Drive T: 530.552.3880
Oroville, California 95965 F: 530.538.5339
buttecounty.net/publichealth
APN:_____________________________ Owner Telephone:__________________________
Parcel Address: _______________________________________________________________
Property Owner Name: _________________________________________________________
PropertyOwner Mailing Address: __________________________________________________
Prior to inspection, contact Butte County Environmental Health for septic records. If no records
are available, an As-Built of the existing tank and leach lines will be required (Form AS).
Septic Tank Physical Observations
Tank Material: Concrete X Fiberglass □ Poly □ Wood (Not Including Baffle) □
Inlet T: Present: Yes X No□ In Good Condition: Yes □ No □
Outlet T: Present: Yes X No□ In Good Condition: Yes □ No □
Is Effluent In The Tank At Normal Operating Level? Yes □ No X
IfNot, Explain? __________________________________________________________
Baffle/ Sidewalls/ Top Has Visible Cracks/Deterioration: Yes □ No X If So, Explain.___________________________________________________________
Overall Tank Condition: Good □ Fair □ Poor X
General Comments: ______________________________________________________
Drain Field Operational Observations
Perform Hydraulic Test of Effluent Line to Dispersal Field
Introduce water through the outlet. Minimum of 50 gallons of water.
Signs of Effluent Line break or Leach Field failure: Yes □ No X *
Surfacing Water □ Moist Soil □ Backflow into Tank for Over 30 Minutes □
Other □ Explain.
____________________________________________________________________________
Butte County Certified Professional Phone Number: 530-877-3207
Name of Inspector Signature Date
This hydraulic test of the effluent line does not constitute a full hydraulic load test of the
dispersal field. A full hydraulic load test can only be effectively done with more water and when
the system has been in continual use.
017-100-038 530-519-6333
12666 Centerville Road, Chico, CA 95928
Requested by Century 21 Select Chico
c/o Emmett Jacobi @ C21
Low liquid level at half seam.
Low liquid level indicates tank is leaking.
Absorption field tested Excellent.
Mark Muhlbaier February 5, 2025