HomeMy WebLinkAboutFAI19-0037 2024-08-15 CF FA 2024Fire Alarm and Life Safety System
Inspection Certificate
For
Sycamore Middle School
1125 Sycamore Street
Gridley, CA 95948
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages
of this report provide performance measurements, listed ranges of acceptable results, and complete
documentation of the inspection. Whenever discrepancies exist between acceptable performance
standards and actual test results, notes and/or recommended solutions have been proposed or provided
for immediate review and approval.
Annual Inspection
Inspection Date
Aug 15, 2024
Building: Sycamore Middle School Company: Hue & Cry, Inc.
Contact: Jordan Reeves Contact: Nick Kuykendall
Title: Superintendent Title: INSPECTOR/TECHNICIAN
Fire Alarm Testing Report
Page of 2 14
Executive Summary
Hue & Cry, Inc.Download Date: 08/16/2024
Executive Summary
Generated by: BuildingReports.com
Building Information
Building: Sycamore Middle School Contact: Jordan Reeves
Address: 1125 Sycamore Street Phone: 1-530-846-34721
Address: Fax:
City/State/ZIP Code: Gridley, CA 95948 Mobile:
Country: United States of America Email: jreeves@gusd.org
Inspection Performed By
Company: Hue & Cry, Inc.Inspector: Nick Kuykendall
Address: 1751 Bruce Drive Phone: 800-800-alarm
Address: Fax:
City/State/ZIP Code: Anderson, California 96007 Mobile:
Country: United States of America Email: n.kuykendall@hueandcry.com
System Control Unit
Manufacturer: Honeywell Inspection Date: 08/14/2024 IDC Style: B
Model Number: 6820EVS Install Date: 10/17/1995 SLC Style:
Software Version: Version Date: 10/17/1995 NAC Style: Y
Location: Office Current Protection: Breaker
OfficeDisconnect Location:Type: Breaker
Page of 3 14
Executive Summary
Hue & Cry, Inc.Download Date: 08/16/2024
Inspection Summary
Category:Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Control 16 16.49%16 100.00%8 50.00%8 50.00%
Indicating 54 55.67%54 100.00%53 98.15%1 1.85%
Initiating 27 27.84%27 100.00%27 100.00%0 0.00%
Totals 97 100%97 100.00%88 90.72%9 9.28%
Certification
Company: Hue & Cry, Inc.Building: Sycamore Middle School
Inspector: Nick Kuykendall Contact: Jordan Reeves
Signed: Aug 14, 2024 Signed:
Nick Kuykendall Certifications
Certification Type Number
C-10 Electrical Licensed Contractor 620587
Page of 4 14
Discrepancy Report
Hue & Cry, Inc.Download Date: 08/16/2024
Discrepancy Report
Generated by: BuildingReports.com
Building: Sycamore Middle School Control Panel: 1 - Honeywell 6820EVS
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where
appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part
of a manufacturer’s replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
Control
Battery
1 61625370 Extender Panel Date Expired 1 NFPA72 Table
14.4.3.2 (9)c(1)
1 61625371 Extender Panel Date Expired 1 NFPA72 Table
14.4.3.2 (9)c(1)
1 61625375 FACP Failed Test 1 NFPA72 Table
14.4.3.2 (9)c(1)
1 61625376 FACP Failed Test 1 NFPA72 Table
14.4.3.2 (9)c(1)
1 61625365 Portable 21 EVS Power Supply (L) Date Expired 1 NFPA72 Table
14.4.3.2 (9)c(1)
1 61625366 Portable 21 EVS Power Supply (R) Date Expired 1 NFPA72 Table
14.4.3.2 (9)c(1)
1 61625363 Portable 21 Power Supply (L) Date Expired 1 NFPA72 Table
14.4.3.2 (9)c(1)
1 61625364 Portable 21 Power Supply (R) Date Expired 1 NFPA72 Table
14.4.3.2 (9)c(1)
Indicating
Horn
2 11531557 Library Failed Operation 1 NFPA72 14.2.2.2.2
Code References
NFPA72 Table 14.4.3.2 (9)c
(1)
Batteries shall be replaced in accordance with the recommendations of the alarm equipment
manufacturer or when the recharged battery voltage or current falls below the manufacturer's
recommendations
NFPA72 14.2.2.2.2 System deficiencies shall be corrected.
Page of 5 14
Proposed Solutions Report
Hue & Cry, Inc.Download Date: 08/16/2024
Proposed Solutions Report
Generated by: BuildingReports.com
Building: Sycamore Middle School Control Panel: 1 - Honeywell 6820EVS
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check
mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time
and Materials basis.
ScanID Location Solution Model #Cost Fix
Control
Battery
61625370 Extender Panel Replace Battery DURA12 T/M
61625371 Extender Panel Replace Battery DURA12-8F2 T/M
61625375 FACP Replace Battery DURA12-8F2 T/M
61625376 FACP Replace Battery DURA12-8F2 T/M
61625365 Portable 21 EVS Power Supply (L)Replace Battery DURA12-8F2 T/M
61625366 Portable 21 EVS Power Supply (R)Replace Battery DURA12 T/M
61625363 Portable 21 Power Supply (L)Replace Battery DURA12-8F2 T/M
61625364 Portable 21 Power Supply (R)Replace Battery DURA12-8F2 T/M
Indicating
Horn
11531557 Library Investigate 2901-9838 T/M
PO #: (none)T/M
Page of 6 14
Notes & Recommendations
Hue & Cry, Inc.Download Date: 08/16/2024
Notes & Recommendations
Generated by: BuildingReports.com
Building: Sycamore Middle School
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the
building inspection. Notes are grouped by Category.
General Note
All batteries expired and need to be replaced
(8) 12v8ah batteries (12v7ah should work as well)
Horn in library did not go off while testing audibles
Page of 7 14
Inspection & Testing
Hue & Cry, Inc.Download Date: 08/16/2024
Inspection & Testing
Generated by: BuildingReports.com
Building: Sycamore Middle School Control Panel: 1 - Honeywell 6820EVS
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
. Items are listed by Category. Each item includes the services performed, and the time & date at which testing Failed/Other
occurred.
Device Type Location Service Time Date
Passed
Control
Communication Line
Office Annual 12:22:05 PM 08/14/2024
Communication Line
Office Annual 12:22:13 PM 08/14/2024
Control Panel Office Annual 11:18:14 AM 08/14/2024
Disconnect Nurses Office Circuit Breaker #13 Annual 7:40:26 AM 08/15/2024
Disconnect Portable 21 Breaker 13 Annual 7:40:30 AM 08/15/2024
Indicating
Horn Counselors Office Annual 11:43:20 AM 08/14/2024
Horn Gym East Annual 11:43:46 AM 08/14/2024
Horn Hall by Room 15 Annual 11:43:27 AM 08/14/2024
Horn Main Hall by Rooms 2-3 Annual 11:43:06 AM 08/14/2024
Horn Nurses Office Annual 11:43:10 AM 08/14/2024
Horn Office Conference Room Annual 11:43:23 AM 08/14/2024
Horn Offices for Counselors Annual 11:43:13 AM 08/14/2024
Horn Outside by Room 22 Annual 11:43:33 AM 08/14/2024
Horn Outside by Room 23 Annual 11:43:36 AM 08/14/2024
Horn Outside by Rooms 19 Annual 11:43:43 AM 08/14/2024
Horn Outside by Rooms 21 Annual 11:43:40 AM 08/14/2024
Horn Staff Lounge Annual 11:43:30 AM 08/14/2024
Horn Office Annual 11:43:17 AM 08/14/2024
Horn/Strobe Band Room Annual 11:47:05 AM 08/14/2024
Horn/Strobe Boys R/R Outside Main Bldg Annual 11:47:02 AM 08/14/2024
Horn/Strobe Boys R/R by Media Room Annual 11:44:51 AM 08/14/2024
Horn/Strobe Girls R/R by Media Room Annual 11:44:54 AM 08/14/2024
Horn/Strobe Hall by Girls R/R by Main Bldg Annual 11:44:09 AM 08/14/2024
Horn/Strobe Main Hall West near Storage Annual 11:46:19 AM 08/14/2024
Horn/Strobe Main Hall by Rooms 5-6 Annual 11:43:59 AM 08/14/2024
Horn/Strobe Office Lobby Annual 11:44:02 AM 08/14/2024
Page of 8 14
Inspection & Testing
Hue & Cry, Inc.Download Date: 08/16/2024
Device Type Location Service Time Date
Passed
Horn/Strobe Outside Main Bldg West Annual 11:44:05 AM 08/14/2024
Horn/Strobe Storage by Rooms 15-16 Annual 11:44:45 AM 08/14/2024
Horn/Strobe Portables 17 Annual 11:47:09 AM 08/14/2024
Horn/Strobe Portables 17 Annual 11:47:12 AM 08/14/2024
Horn/Strobe Portables 18 Annual 11:46:24 AM 08/14/2024
Horn/Strobe Portables 18 Annual 11:46:56 AM 08/14/2024
Horn/Strobe Portables 19 Annual 11:46:31 AM 08/14/2024
Horn/Strobe Portables 19 Annual 11:46:37 AM 08/14/2024
Horn/Strobe Portables 20 Annual 11:46:40 AM 08/14/2024
Horn/Strobe Portables 20 Annual 11:46:44 AM 08/14/2024
Horn/Strobe Portables 21 Annual 11:46:47 AM 08/14/2024
Horn/Strobe Portables 21 Annual 11:46:51 AM 08/14/2024
Horn/Strobe Room 1 Annual 11:45:04 AM 08/14/2024
Horn/Strobe Room 10 Annual 11:46:07 AM 08/14/2024
Horn/Strobe Room 11 Annual 11:45:54 AM 08/14/2024
Horn/Strobe Room 12 Annual 11:45:43 AM 08/14/2024
Horn/Strobe Room 13 Annual 11:45:14 AM 08/14/2024
Horn/Strobe Room 14 Annual 11:45:11 AM 08/14/2024
Horn/Strobe Room 15 Annual 11:44:48 AM 08/14/2024
Horn/Strobe Room 16 Annual 11:44:42 AM 08/14/2024
Horn/Strobe Room 2 Annual 11:45:39 AM 08/14/2024
Horn/Strobe Room 23 Annual 11:43:53 AM 08/14/2024
Horn/Strobe Room 23 Restroom Annual 11:43:50 AM 08/14/2024
Horn/Strobe Room 3 Annual 11:45:48 AM 08/14/2024
Horn/Strobe Room 4 Annual 11:45:51 AM 08/14/2024
Horn/Strobe Room 5 Annual 11:45:57 AM 08/14/2024
Horn/Strobe Room 6 Annual 11:46:00 AM 08/14/2024
Horn/Strobe Room 7 Annual 11:46:14 AM 08/14/2024
Horn/Strobe Room 8 Annual 11:43:56 AM 08/14/2024
Horn/Strobe Room 9 Annual 11:46:10 AM 08/14/2024
Strobe Counselors R/R Annual 12:20:29 PM 08/14/2024
Strobe Nurses R/R Annual 12:20:26 PM 08/14/2024
Initiating
Heat Detector Portable 17 Annual 12:17:57 PM 08/14/2024
Heat Detector Portable 18 Annual 12:17:44 PM 08/14/2024
Heat Detector Portable 19 Annual 12:17:47 PM 08/14/2024
Heat Detector Portable 20 Annual 12:17:51 PM 08/14/2024
Page of 9 14
Inspection & Testing
Hue & Cry, Inc.Download Date: 08/16/2024
Device Type Location Service Time Date
Passed
Heat Detector Portable 21 Annual 12:17:54 PM 08/14/2024
Pull Station Band Room Annual 12:20:34 PM 08/14/2024
Pull Station Gym East Annual 12:04:28 PM 08/14/2024
Pull Station Gym North Annual 12:05:24 PM 08/14/2024
Pull Station Gym West Exit Annual 12:03:19 PM 08/14/2024
Pull Station Hall by Room 15 Annual 12:07:55 PM 08/14/2024
Pull Station Main Hall between rooms 5-6 Annual 11:56:24 AM 08/14/2024
Pull Station Cafeteria Annual 12:07:51 PM 08/14/2024
Pull Station Kitchen Annual 12:09:05 PM 08/14/2024
Pull Station Main hall betwen rooms 2-3 Annual 11:57:36 AM 08/14/2024
Pull Station Room 22 Annual 12:00:14 PM 08/14/2024
Pull Station Room 23 Annual 12:00:51 PM 08/14/2024
Smoke Detector Office Above FACP Annual 11:50:56 AM 08/14/2024
Smoke Detector Portable 17 Annual 12:20:00 PM 08/14/2024
Smoke Detector Portable 17 Annual 12:20:03 PM 08/14/2024
Smoke Detector Portable 18 Annual 12:18:11 PM 08/14/2024
Smoke Detector Portable 18 Annual 12:19:57 PM 08/14/2024
Smoke Detector Portable 19 Annual 12:19:21 PM 08/14/2024
Smoke Detector Portable 19 Annual 12:19:24 PM 08/14/2024
Smoke Detector Portable 20 Annual 12:19:31 PM 08/14/2024
Smoke Detector Portable 20 Annual 12:19:34 PM 08/14/2024
Smoke Detector Portable 21 Annual 12:19:49 PM 08/14/2024
Smoke Detector Portable 21 Annual 12:19:53 PM 08/14/2024
Device Type Location Service Time Date
Failed/Other
Control
1 Battery Extender Panel Annual 11:28:46 AM 08/14/2024
1 Battery Extender Panel Annual 11:29:14 AM 08/14/2024
1 Battery FACP Annual 11:25:36 AM 08/14/2024
1 Battery FACP Annual 11:26:51 AM 08/14/2024
1 Battery Portable 21 EVS Power Supply (L) Annual 12:13:53 PM 08/14/2024
1 Battery Portable 21 EVS Power Supply (R) Annual 12:14:25 PM 08/14/2024
1 Battery Portable 21 Power Supply (L) Annual 12:13:25 PM 08/14/2024
1 Battery Portable 21 Power Supply (R) Annual 12:12:46 PM 08/14/2024
Indicating
2 Horn Library Annual 11:42:43 AM 08/14/2024
Page of 10 14
Inspection & Testing
Hue & Cry, Inc.Download Date: 08/16/2024
Building: Sycamore Middle School Control Panel: 2
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
. Items are listed by Category. Each item includes the services performed, and the time & date at which testing Failed/Other
occurred.
Device Type Location Service Time Date
Passed
Control
Power Supply Office Annual 11:18:55 AM 08/14/2024
Power Supply Portable 21 Annual 12:12:25 PM 08/14/2024
Power Supply Portable 21 Annual 12:18:05 PM 08/14/2024
Page of 11 14
Service Summary
Hue & Cry, Inc.Download Date: 08/16/2024
Service Summary
Generated by: BuildingReports.com
Building: Sycamore Middle School
The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Failed/Other
Battery Annual 8
Horn Annual 1
Total 9
Passed
Communication Line Annual 2
Control Panel Annual 1
Disconnect Annual 2
Heat Detector Annual 5
Horn/Strobe Annual 38
Horn Annual 13
Power Supply Annual 3
Pull Station Annual 11
Smoke Detector Annual 11
Strobe Annual 2
Total 88
Grand Total 97
Page of 12 14
Battery & Power Supply Testing
Hue & Cry, Inc.Download Date: 08/16/2024
Battery & Power Supply Testing
Generated by: BuildingReports.com
Building: Sycamore Middle School Control Panel: 1 - Honeywell 6820EVS
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used
to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location
Rated
Ah
Rated
Volts Pre Test
Post
Test Min Ah Tested Ah
Battery
Failed/Other
Sealed Lead Acid Extender Panel 7 12 12.91 4.55 7.2
Sealed Lead Acid Extender Panel 7 12 12.91 4.55 6.8
Sealed Lead Acid FACP 8 12 12.91 4.55 2.1
Sealed Lead Acid FACP 8 12 12.91 4.55 4.2
Sealed Lead Acid Portable 21 EVS Power Supply
(L)
7 12
Sealed Lead Acid Portable 21 EVS Power Supply
(R)
7 12
Sealed Lead Acid Portable 21 Power Supply (L) 7 12
Sealed Lead Acid Portable 21 Power Supply (R) 7 12
Page of 13 14
Inventory & Warranty Report
Hue & Cry, Inc.Download Date: 08/16/2024
Inventory & Warranty Report
Generated by: BuildingReports.com
Building: Sycamore Middle School Control Panel: 1 - Honeywell 6820EVS
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A
complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last
year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity
Battery Control 8.25%8
Communication Line Control 2.06%2
Control Panel Control 1.03%1
Disconnect Control 2.06%2
Heat Detector Initiating 5.15%5
Horn Indicating 14.43%14
Horn/Strobe Indicating 39.18%38
Power Supply Control 3.09%3
Pull Station Initiating 11.34%11
Smoke Detector Initiating 11.34%11
Strobe Indicating 2.06%2
Type Qty Model #Description Install Date
In Service - 3 Years to 5 Years
Duracell
Battery 1 DURA12-8F2 Sealed Lead Acid 01/21/2020
Battery 1 DURA12-8F2 Sealed Lead Acid 09/24/2019
Battery 1 DURA12 Sealed Lead Acid 08/22/2019
Battery 3 DURA12-8F2 Sealed Lead Acid 08/22/2019
In Service - 5 Years to 10 Years
Duracell
Battery 1 DURA12 Sealed Lead Acid 01/21/2019
Battery 1 DURA12-8F2 Sealed Lead Acid 01/21/2019
Fire-Lite
Heat Detector 5 H365 Rate-of-Rise 10/22/2014
Honeywell
Smoke Detector 11 SK-PHOTO Photoelectric 10/22/2014
In Service - 15 Years to 25 Years
Gentex
Horn 5 MHR 10/06/2003
Horn/Strobe 2 GXS-4-15/75WR 10/06/2003
Silent Knight
Horn/Strobe 1 10/06/2003
Pull Station 4 PS-SATK Single Action 10/06/2003
SimplexGrinnell
Page of 14 14
Inventory & Warranty Report
Hue & Cry, Inc.Download Date: 08/16/2024
Horn 6 2901-9838 10/06/2003
Horn 2 4901-9817 10/06/2003
Horn 1 GX90-4 10/06/2003
Horn/Strobe 23 2901-9838 10/06/2003
Pull Station 7 596B Single Action 10/06/2003
Strobe 2 unknown 10/06/2003
Squre D
Disconnect 2 20amp Breaker 10/06/2003
System sensor
Horn/Strobe 10 SPScRl 10/06/2003
Wheelock
Horn/Strobe 1 10/06/2003
Horn/Strobe 1 MT12/24 10/06/2003
In Service - 25 Years or Older
Honeywell
Control Panel 1 6820EVS Addressable 10/17/1995
Phone line 1
Communication Line 1 846-2370 10/17/1995
Phone line 2
Communication Line 1 846-1275 10/17/1995
Building: Sycamore Middle School Control Panel: 2
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A
complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last
year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Model #Description Install Date
In Service - 25 Years or Older
Honeywell
Power Supply 2 5496 05/20/1975
Power Supply 1 EVS-50W 05/20/1975