Loading...
HomeMy WebLinkAboutFAI22-0003 2024-08-14 CF FA 2024Fire Alarm and Life Safety System Inspection Certificate For McKinley Elementary School 1045 Sycamore Street Gridley, CA 95948 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval. Inspection Date Aug 14, 2024 Building: McKinley Elementary School Company: Hue & Cry, Inc. Contact: Jordan Reeves Contact: CESAR HERNANDEZ Title: Superintendent Title: INSPECTOR Fire Alarm Testing Report Page of 2 12 Executive Summary Hue & Cry, Inc.Download Date: 08/16/2024 Executive Summary Generated by: BuildingReports.com Building Information Building: McKinley Elementary School Contact: Jordan Reeves Address: 1045 Sycamore Street Phone: 1-530-846-4721 Address: Fax: City/State/ZIP Code: Gridley, CA 95948 Mobile: Country: United States of America Email: jreeves@gusd.org Inspection Performed By Company: Hue & Cry, Inc.Inspector: CESAR HERNANDEZ Address: 1751 Bruce Drive Phone: 9166064121 Address: Fax: City/State/ZIP Code: Anderson, California 96007 Mobile: 19166064121 Country: United States of America Email: C.HERNANDEZ@HUEANDCRY.COM System Control Unit Manufacturer: Silent Knight Inspection Date: 08/14/2024 IDC Style: B Model Number: 5820XL Install Date: 01/31/2005 SLC Style: 4 Software Version: 9.08 Version Date: 05/11/2007 NAC Style: Y Location: Rear Electrical Room in Electric Box Current Protection: Breaker Rear Electrical Room in Electric BoxDisconnect Location:Type: Breaker Page of 3 12 Executive Summary Hue & Cry, Inc.Download Date: 08/16/2024 Inspection Summary Category:Total Items Serviced Passed Failed/Other Qty %Qty %Qty %Qty % Auxiliary 1 1.54%1 100.00%1 100.00%0 0.00% Control 8 12.31%8 100.00%8 100.00%0 0.00% Indicating 17 26.15%17 100.00%17 100.00%0 0.00% Initiating 38 58.46%38 100.00%38 100.00%0 0.00% Monitor 1 1.54%1 100.00%1 100.00%0 0.00% Totals 65 100%65 100.00%65 100.00%0 0.00% Certification Company: Hue & Cry, Inc.Building: McKinley Elementary School Inspector: CESAR HERNANDEZ Contact: Jordan Reeves Signed:Signed: Aug 14, 2024 CESAR HERNANDEZ Certifications Certification Type Number C-10 Electrical Licensed Contractor 620587 Page of 4 12 Inspection & Testing Hue & Cry, Inc.Download Date: 08/16/2024 Inspection & Testing Generated by: BuildingReports.com Building: McKinley Elementary School Control Panel: 1 - Silent Knight 5820XL The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or . Items are listed by Category. Each item includes the services performed, and the time & date at which testing Failed/Other occurred. Device Type Location Service Time Date Passed Auxiliary Lighting Control Room 12 Above Tile North End Annual 9:25:11 AM 08/14/2024 Control Annunciator Main Hall East by Custodian Room Annual 9:06:05 AM 08/14/2024 Battery FACP Annual 8:03:08 AM 08/14/2024 Battery FACP Annual 8:04:27 AM 08/14/2024 Battery Room 3 Annual 8:08:50 AM 08/14/2024 Battery Room 3 Annual 8:09:22 AM 08/14/2024 Control Panel Rear Electrical Room in Electric Box Annual 9:06:10 AM 08/14/2024 Disconnect FACP Room near door Annual 9:27:29 AM 08/14/2024 Voice Evacuation Room 3 Annual 9:25:15 AM 08/14/2024 Indicating Horn East Playground Annual 9:38:07 AM 08/14/2024 Horn South Outside Electrical Room Annual 9:37:53 AM 08/14/2024 Horn West Playground Annual 9:38:11 AM 08/14/2024 Horn Room 2 Annual 9:38:14 AM 08/14/2024 Horn/Strobe Main Hall East Annual 9:38:36 AM 08/14/2024 Horn/Strobe Main Hall West Annual 9:38:32 AM 08/14/2024 Horn/Strobe Room 12 Annual 9:38:17 AM 08/14/2024 Horn/Strobe Room 14 Annual 9:38:20 AM 08/14/2024 Horn/Strobe Room 15 Annual 9:38:24 AM 08/14/2024 Horn/Strobe Room 16 ELO2 4.7k resistor 25.7v Annual 9:38:28 AM 08/14/2024 Speaker/Strobe Restroom 1 Annual 9:38:40 AM 08/14/2024 Speaker/Strobe Room 2 Annual 9:39:21 AM 08/14/2024 Speaker/Strobe Room 3 Annual 9:38:46 AM 08/14/2024 Speaker/Strobe Room1 Annual 9:38:49 AM 08/14/2024 Speaker/Strobe Women Restroom Annual 9:38:43 AM 08/14/2024 Speaker/Strobe Work Room Annual 9:39:19 AM 08/14/2024 Strobe Room 3 Bathroom Annual 9:39:27 AM 08/14/2024 Initiating Page of 5 12 Inspection & Testing Hue & Cry, Inc.Download Date: 08/16/2024 Device Type Location Service Time Date Passed Heat Detector Portable restroom above ceiling Annual 9:05:35 AM 08/14/2024 Heat Detector Room 1 Above Tile Annual 9:02:56 AM 08/14/2024 Heat Detector Room 12 Above Tile South End Annual 9:05:25 AM 08/14/2024 Heat Detector Room 14 Above Tile North End Annual 9:04:02 AM 08/14/2024 Heat Detector Room 14 Above Tile South End Annual 9:05:15 AM 08/14/2024 Heat Detector Room 15 Above Tile North End Annual 9:04:06 AM 08/14/2024 Heat Detector Room 15 Above Tile South End Annual 9:05:09 AM 08/14/2024 Heat Detector Room 16 Above Tile North End Annual 9:04:19 AM 08/14/2024 Heat Detector Room 16 Above Tile South End Annual 9:04:53 AM 08/14/2024 Heat Detector Room 2 Above Tile Annual 9:03:00 AM 08/14/2024 Heat Detector Room 3 Above Tile Annual 9:03:04 AM 08/14/2024 Heat Detector Work Room @room1 Annual 9:05:29 AM 08/14/2024 Pull Station Main Hall East by Room 8 Annual 9:07:42 AM 08/14/2024 Pull Station Main Hall West by Room 6 Annual 9:07:39 AM 08/14/2024 Pull Station Room 1 Annual 8:45:05 AM 08/14/2024 Pull Station Room 2 Annual 8:44:54 AM 08/14/2024 Pull Station Room 3 Annual 8:44:51 AM 08/14/2024 Pull Station West Playground Annual 9:06:50 AM 08/14/2024 Pull Station Work Room @room1 Annual 9:06:46 AM 08/14/2024 Smoke Detector Restroom Annual 9:21:19 AM 08/14/2024 Smoke Detector Room 1 Annual 8:45:16 AM 08/14/2024 Smoke Detector Room 1 Annual 8:45:19 AM 08/14/2024 Smoke Detector Room 12 West Annual 9:21:02 AM 08/14/2024 Smoke Detector Room 14 East Annual 9:13:31 AM 08/14/2024 Smoke Detector Room 14 West Annual 9:13:27 AM 08/14/2024 Smoke Detector Room 15 East Annual 9:13:16 AM 08/14/2024 Smoke Detector Room 15 West Annual 9:13:21 AM 08/14/2024 Smoke Detector Room 16 East Annual 9:08:35 AM 08/14/2024 Smoke Detector Room 16 West Annual 9:08:20 AM 08/14/2024 Smoke Detector Room 2 Annual 8:44:38 AM 08/14/2024 Smoke Detector Room 2 Annual 8:44:41 AM 08/14/2024 Smoke Detector Room 3 Annual 8:26:55 AM 08/14/2024 Smoke Detector Room 3 Annual 8:27:00 AM 08/14/2024 Smoke Detector Women Restroom Annual 9:21:06 AM 08/14/2024 Smoke Detector Work Room @room1 Annual 9:22:06 AM 08/14/2024 Smoke Detector Work Room @room1 Annual 9:22:25 AM 08/14/2024 Smoke Detector Room 12 East Annual 9:20:57 AM 08/14/2024 Page of 6 12 Inspection & Testing Hue & Cry, Inc.Download Date: 08/16/2024 Device Type Location Service Time Date Passed Smoke Detector Room 3 restroom Annual 9:21:30 AM 08/14/2024 Monitor Monitor Device Room 3 Annual 9:06:21 AM 08/14/2024 Page of 7 12 Service Summary Hue & Cry, Inc.Download Date: 08/16/2024 Service Summary Generated by: BuildingReports.com Building: McKinley Elementary School The Service Summary section provides an overview of the services performed in this report. Device Type Service Quantity Passed Annunciator Annual 1 Battery Annual 4 Control Panel Annual 1 Disconnect Annual 1 Heat Detector Annual 12 Horn/Strobe Annual 6 Horn Annual 4 Lighting Control Annual 1 Monitor Device Annual 1 Pull Station Annual 7 Smoke Detector Annual 19 Speaker/Strobe Annual 6 Strobe Annual 1 Voice Evacuation Annual 1 Total 65 Grand Total 65 Page of 8 12 Auxiliary Functions Testing Hue & Cry, Inc.Download Date: 08/16/2024 Auxiliary Functions Testing Generated by: BuildingReports.com Building: McKinley Elementary School Control Panel: 1 - Silent Knight 5820XL The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated. Type Location Comment ScanID Simulated Passed Lighting Control Room 12 Above Tile North End Passed 11531210 Smoke Detector Smoke Compartment Restroom Passed 51368394 Smoke Compartment Room 1 Passed 46435456 Smoke Compartment Room 1 Passed 46435455 Smoke Compartment Room 12 West Passed 11531212 Smoke Compartment Room 14 East Passed 11531215 Smoke Compartment Room 14 West Passed 11531217 Smoke Compartment Room 15 East Passed 11531219 Smoke Compartment Room 15 West Passed 11531218 Smoke Compartment Room 16 East Passed 11531224 Smoke Compartment Room 16 West Passed 11531225 Smoke Compartment Room 2 Passed 46435452 Smoke Compartment Room 2 Passed 46435453 Smoke Compartment Women Restroom Passed 51368393 Smoke Compartment Work Room @room1 Passed 51368402 Smoke Compartment Work Room @room1 Passed 51368403 Smoke Compartment Room 12 East Passed 11531211 Smoke Compartment Room 3 restroom Passed 51368401 Page of 9 12 Battery & Power Supply Testing Hue & Cry, Inc.Download Date: 08/16/2024 Battery & Power Supply Testing Generated by: BuildingReports.com Building: McKinley Elementary School Control Panel: 1 - Silent Knight 5820XL The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other. Type Location Rated Ah Rated Volts Pre Test Post Test Min Ah Tested Ah Battery Passed Sealed Lead Acid FACP 7 12 12.65 4.55 7.0 Sealed Lead Acid FACP 7.0 12 12.62 4.55 7.8 Sealed Lead Acid Room 3 8 12 12.85 4.55 4.8 Sealed Lead Acid Room 3 8 12 12.88 4.55 4.6 Page of 10 12 Inventory & Warranty Report Hue & Cry, Inc.Download Date: 08/16/2024 Inventory & Warranty Report Generated by: BuildingReports.com Building: McKinley Elementary School Control Panel: 1 - Silent Knight 5820XL The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference. Device or Type Category % of Inventory Quantity Annunciator Control 1.54%1 Battery Control 6.15%4 Control Panel Control 1.54%1 Disconnect Control 1.54%1 Heat Detector Initiating 18.46%12 Horn Indicating 6.15%4 Horn/Strobe Indicating 9.23%6 Lighting Control Auxiliary 1.54%1 Monitor Device Monitor 1.54%1 Pull Station Initiating 10.77%7 Smoke Detector Initiating 29.23%19 Speaker/Strobe Indicating 9.23%6 Strobe Indicating 1.54%1 Voice Evacuation Control 1.54%1 Type Qty Model #Description Install Date In Service - 3 Years to 5 Years Duracell Battery 2 12-8F2 Sealed Lead Acid 01/04/2021 In Service - 5 Years to 10 Years Power-Sonic Battery 2 PS 1270-F1 Sealed Lead Acid 11/19/2018 Fire-Lite Pull Station 1 BG-12LO/SD500- MIM Dual Action 11/13/2014 In Service - 15 Years to 25 Years Cutler/Hammer Disconnect 1 20amp Breaker 01/31/2005 Silent Knight Annunciator 1 5860 01/31/2005 Control Panel 1 5820XL 01/31/2005 Monitor Device 1 SD500-ARM Relay 01/31/2005 Pull Station 6 SD500-PS Single Action 01/31/2005 Smoke Detector 8 SD505-APS Photoelectric 01/31/2005 Smoke Detector 2 SD505-PHOTO 01/31/2005 Page of 11 12 Inventory & Warranty Report Hue & Cry, Inc.Download Date: 08/16/2024 Smoke Detector 9 SD505-PHOTO Photoelectric 01/31/2005 System Sensor Heat Detector 12 5602 Combination 01/31/2005 Lighting Control 1 5602 01/31/2005 Wheelock Horn 1 01/31/2005 Horn 3 AH-24WP 01/31/2005 Horn/Strobe 6 AS24-MCW 01/31/2005 Speaker/Strobe 6 LSPSTR 01/31/2005 Strobe 1 LSPSTR 01/31/2005 Voice Evacuation 1 SP40S 01/31/2005 Page of 12 12 Zone Address Report Hue & Cry, Inc.Download Date: 08/16/2024 Zone Address Report Generated by: BuildingReports.com Building: McKinley Elementary School Control Panel: 1 - Silent Knight 5820XL The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference. Address Device Type Location Type ScanID Zone/Circuit: 01- 1 Heat Detector Room 12 Above Tile South End Combination 16404062 Zone/Circuit: 02- 1 Lighting Control Room 12 Above Tile North End 11531210 1 Heat Detector Room 14 Above Tile North End Combination 11531214 2 Heat Detector Portable restroom above ceiling Combination 56777923 2 Heat Detector Room 1 Above Tile Combination 56777930 2 Heat Detector Room 14 Above Tile South End Combination 16404061 2 Heat Detector Room 2 Above Tile Combination 56777929 2 Heat Detector Room 3 Above Tile Combination 56777928 2 Heat Detector Work Room @room1 Combination 56777921 Zone/Circuit: 03- 1 Heat Detector Room 15 Above Tile South End Combination 16404060 2 Heat Detector Room 15 Above Tile North End Combination 11531221 3 Heat Detector Room 16 Above Tile North End Combination 11531222 4 Heat Detector Room 16 Above Tile South End Combination 16404059 Zone/Circuit: 05- Smoke Detector Room 12 West Photoelectric 11531212 Zone/Circuit: 06- Smoke Detector Work Room @room1 Photoelectric 51368402 Smoke Detector Work Room @room1 Photoelectric 51368403 Smoke Detector Room 12 East Photoelectric 11531211 Smoke Detector Room 3 restroom Photoelectric 51368401 Zone/Circuit: M33 P015 Pull Station West Playground Dual Action 32021985 07 Smoke Detector Room 14 West Photoelectric 11531217 08 Smoke Detector Room 14 East Photoelectric 11531215 09 Smoke Detector Room 15 East Photoelectric 11531219 10 Smoke Detector Room 15 West Photoelectric 11531218 11 Smoke Detector Room 16 West Photoelectric 11531225 12 Smoke Detector Room 16 East Photoelectric 11531224