Loading...
HomeMy WebLinkAboutB25-0164 025-200-118 Avatar Foods Hydrant Flow Test Report - APPROVED , lI p 1 ) f I 11,10 ( 11 f6111, , A rrttrc A VA A A A A, Hydrant Flow Test Report Test Date: 4/7/25 Test Time: 9:00 am Water District: Gridley Water Jurisdiction: Butte County Site Address: 1900 CA-99 Gridley, CA Requested by: Foothill Fire Protection Inc. Purpose of Test: Determine available water supply. Conducted by: Ricky Fox, R.J.Volpato Test Hydrant Locations: #1 Test Hydrant: Hydrant—400' South of 1900 CA-99 parking entrance. #2 Flow Hydrant: Hydrant at 1900 CA-99 parking entrance 80 70 60 SO 40 30 21 14GPIVI at 20 psi 20 10 0 200 400 600 800 1,000 1,200 1,400 1,600 1,800 2,000 2,200 2,400 2,600 Predicted Flow Rate(GPM) Hydrant# Outlet Size Pitot Static PSI Residual PSI Flow Observed Flow at 20 (GPM) PSI Residual (GPM) 1 6050 2 2.5" 30 924 2,114 Note: This test was conducted per NFPA 291. Foothill Fire Protection (FFP) is not the controlling water district and cannot guarantee the flows above. It shall also be noted the time that the test was conducted. This test time may not reflect the available flow while the water system is at its highest demand from the existing services. FFP assumes no responsibility for loss or damages if this flow test data is used. Permit # FIRE BUTTE COUNTY FIRE DEPARTMENT 11111,71,t • REVIEWED FOR CODE COMPLIANCE Date:04/11/2025 Reviewercboyd