HomeMy WebLinkAboutB25-0164 025-200-118 Avatar Foods Hydrant Flow Test Report - APPROVED , lI
p 1 ) f
I 11,10
( 11
f6111, ,
A
rrttrc
A VA A A A A,
Hydrant Flow Test Report
Test Date: 4/7/25 Test Time: 9:00 am
Water District: Gridley Water
Jurisdiction: Butte County
Site Address: 1900 CA-99 Gridley, CA
Requested by: Foothill Fire Protection Inc.
Purpose of Test: Determine available water supply.
Conducted by: Ricky Fox, R.J.Volpato
Test Hydrant Locations:
#1 Test Hydrant: Hydrant—400' South of 1900 CA-99 parking entrance.
#2 Flow Hydrant: Hydrant at 1900 CA-99 parking entrance
80
70
60
SO
40
30
21 14GPIVI at 20 psi
20
10
0 200 400 600 800 1,000 1,200 1,400 1,600 1,800 2,000 2,200 2,400 2,600
Predicted Flow Rate(GPM)
Hydrant# Outlet Size Pitot Static PSI Residual PSI Flow Observed Flow at 20
(GPM) PSI Residual
(GPM)
1 6050
2 2.5" 30 924 2,114
Note: This test was conducted per NFPA 291. Foothill Fire Protection (FFP) is not the
controlling water district and cannot guarantee the flows above. It shall also be noted
the time that the test was conducted. This test time may not reflect the available flow
while the water system is at its highest demand from the existing services. FFP
assumes no responsibility for loss or damages if this flow test data is used.
Permit #
FIRE
BUTTE COUNTY FIRE DEPARTMENT
11111,71,t •
REVIEWED FOR
CODE COMPLIANCE
Date:04/11/2025 Reviewercboyd