HomeMy WebLinkAbout24-123 Fiske Cabin - 06.23.25-Site Plan w Meadow BufferGeneral
Site
Plans
Structural
A1
A2 - A3
A4
A5
A6
A7
A8
A9
S1
S2.1
S2.2
COVER SHEET
GREEN BUILDING CODES
TITLE 24 REPORTS
WILDLAND URBAN INTERFACE
PROPOSED SITE PLAN
1st & 2nd FLOOR PLAN
ELEVATIONS, SECTION, DEMO
ELECTRICAL PLAN
STRUCTURAL NOTES
STRUCTURAL FOUNDATION PLAN
STRUCT. FLOOR FRAMING PLAN
A.P.N.:060-240-038
ZONING:Residential
SITE AREA:51,668 sf
BLDG USE:R-3
OCC. GROUP:R-3/U
CONST. TYPE:V-B
CLIMATE ZONE:11
BLDG. CODE:CRC/CBC 2022
FIRE SPRINKLERS:NO - NOT PRIMARY RESIDENCE
FLOOD ZONE: NO
WUI ZONE: NO
FISKE FAMILY
ACOUS.........
ADJ...............
A.F.F..............
APPROX.......
ARCH............
ARCH'T.........
ASPH.............
BALC............
BD.................
BED...............
BLDG...........
BM................
B.O................
BOT...............
BTWN............
B.U.R.............
CAB..............
CEM.............
CB.................
CL..................
CLG..............
CLOS............
CLR...............
CTR................
COL...............
COND..........
CONN..........
CONST..........
CONT. ..........
CONTR.........
C.S.................
DBL................
DEPT..............
ACOUSTIC
ADJACENT
ABOVE FINISH FLOOR
APPROXIMATE
ARCHITECTURAL
ARCHITECT
ASPHALT
BALCONY
BOARD
BEDROOM
BUILDING
BEAM
BOTTOM OF ...
BOTTOM
BETWEEN
BUILT UP ROOFING
CABINET
CEMENT
CEILING BREAK
CENTER LINE
CEILING
CLOSET
CLEAR
CENTER
COLUMN
CONDITION
CONNECTION
CONSTRUCTION
CONTINUOUS
CONTRACTOR
CARPET STRIP
BOUBLE
DEPARTMENT
DET.............
D.F. ............
DIA..............
DIM.............
DISP............
D.O. ..........
DN..............
DR.(S).........
DWGS........
DS...............
DSSB...........
DSSD..........
DSPT...........
DSRB..........
DSDK.........
D.W. ..........
DWR...........
EA...............
ELEC..........
ELEV..........
ENCL.........
EQ..............
EQMT.........
ETC.............
EXT..............
F.D. ............
F.E.C. ........
FIN...............
FF.................
FLASH.........
FLOUR........
FLR..............
F.O. ...........
F.O.B. ........
DETAIL
DOUGLAS FIR
DIAMETER
DIMENSION
DISPENSER
DOOR OPENING
DOWN
DOOR (S)
DRAWINGS
DOWNSPOUT
DS to SPLASH BLOCK
DS to STORM DRAIN
DS through PT
DS to ROOF BELOW
DS through DECK
DISHWASHER
DRAWER
EACH
ELECTRICAL
ELEVATION
ENCLOSURE
EQUAL
EQUIPMENT
ETCETERA
EXTERIOR
FLOOR DRAIN
FIRE EXTINGUISHER
FINISH
FINISH FLOOR
FLASHING
FLOURESCENT
FLOOR
FACE OF
FACE OF BEAM
F.O.C. .....
F.O.F. ......
F.O.S. ......
F.O.W. ....
F.P. ..........
FXPNL......
FT.............
FTG..........
FURR.......
GA...........
GALV......
G.B. ........
G.D. ........
GL............
GM..........
GND.......
GR...........
GSM........
GYP. BD..
H.B. .........
HDPE.......
HDWD....
H.M. ........
HORIZ.....
H.C. ........
HR............
HGT..........
INFO........
INSUL.......
INT............
JT.............
FACE OF CONCRETE
FACE OF FINISH
FACE OF STUD
FACE OF WALL
FIRE PROTECTION
FIXED PANEL
FOOT, FEET
FOOTING
FURRING
GAUGE
GALVANIZED
GRAB BAR
GARBAGE DISPOSAL
GLASS
GAS METER
GROUND
GRADE
GALVANIZED SHEET METAL
GYPSUM BOARD
HOSE BIB
HIGH DENSITY POLYETHYLENE
HARDWOOD
HOLLOW METAL
HORIZONTAL
HOLLOW CORE
HOUR
HEIGHT
INFORMATION
INSULATION
INTERIOR
JOINT
KIT................
LAM............
LAV.............
LANDSC....
LT.................
MAT'L.........
MAX...........
M.C. ..........
MECH........
MEMB........
MFR............
MIN............
MIR.............
MISC..........
M.T. ...........
MTD............
MTL.............
MUL............
N.I.C. .........
NO..............
NOM..........
NR...............
N.T.S. .........
OBS.............
O.C. ..........
O.D. ..........
OPNG........
OPP............
O/ .............
P..................
P & S..........
KITCHEN
LAMINATE
LAVATORY
LANDSCAPE
LIGHT
MATERIAL
MAXIMUM
MEDICINE CABINET
MECHANICAL
MEMBRANE
MANUFACTURER
MINIMUM
MIRROR
MISCELLANEOUS
METAL THRESHOLD
MOUNTED
METAL
MULLION
NOT IN CONTRACT
NUMBER
NOMINAL
NOT RATED
NOT TO SCALE
OBSCURE
ON CENTER
OUTSIDE DIAMETER
OPENING
OPPOSITE
OVER
PANTRY
POLE AND SHELF
PT............
P.T. .........
P.T.D.F. ..
PERF.......
PR...........
PROJ......
Q.T. ........
R..............
R.A. ........
RAD........
RCGP.....
REC.........
REF..........
REFR.......
REINF......
REQ.('d).
RESIL.......
REV.........
RM...........
R.O..........
RS............
RWD.......
RWL........
R.T.S. ......
S.C.D. ....
S.F.P.D. ..
S.E.D. .....
S.S.D. .....
S.M.D. ...
S.L.D. .....
S.P.D. .....
S.C. ........
SCHED. ..
POST-TENSIONED
PRESSURE TREATED
P.T. DOUGLAS FIR
PERFORATED
PAIR
PROJECT
QUARRY TILE
RISER
RETURN AIR
RADIUS
RAIN CHAIN to GRAVEL PIT
RECOMMENDATION
REFERENCE
REFRIGERATOR
REINFORCING
REQUIRE(d)
RESILLENT
REVERSE
ROOM
ROUGH OPENING
ROUGH SAWN
REDWOOD
RAINWATER LEADER
RUBBER TOP SET
SEE CIVIL DRAWINGS
SEE FIRE PROTECTION DWG'S
SEE ELECTRICAL DRAWINGS
SEE STRUCTURAL DRAWINGS
SEE MECHANICAL DRAWINGS
SEE LANDSCAPE DRAWINGS
SEE PLUMBING DRAWINGS
SOLID CORE
SCHEDULE
S.D. .........
SECT........
SEP..........
SH............
SHWR......
SHT..........
SHTG.......
SIM..........
SL.............
SPEC.......
SQ...........
STD..........
STL...........
STOR.......
STRUC....
ST. STL. ...
SYM........
T&B..........
T.B. .........
T.C. ........
TEL...........
TEMP.......
T & G......
T.O. ........
T.O.C. ....
T.P.H. ......
TRD.........
TS.............
T.V. .........
T.O.W. ....
TYP. ........
U.O.N. ...
V.T. .........
SOAP DISPENSER
SECTION
SEPARATION
SHELF
SHOWER
SHEET
SHEATHING
SIMILAR
SLIDING
SPECIFICATION
SQUARE
STANDARD
STEEL
STORAGE
STRUNTURAL
STAINLESS STEEL
SYMMETRICAL
TOP & BOTTOM
TOWEL BAR
TIME CLOCK
TELEPHONE
TEMPERED
TONGUE and GROOVE
TOP OF …
TOP of CONCRETE
TOILET PAPER HOLDER
TREAD
TUBE STEEL
TELEVISION
TOP OF WALL
TYPICAL
UNLESS OTHERWISE NOTED
VINYL TILE
V.B. ..........
VERT.........
VEST.........
V.F.C. .....
V.I.F. .......
V.W.C. ...
V.G.D.F. .
W..............
W/............
W.C. .......
WD. ........
W/O........
W.O. .......
W.R. ........
W.P. ........
WT............
W.W.F. ....
&...............
@...............
C...............
Ø.............
P................
VAPOR BARRIER
VERTICAL
VESTIBULE
VINYL FLOOR COVERING
VERIFY in FIELD
VIYL WALL COVERING
VERT. GRAIN DOUGLAS FIR
WIDTH
WITH
WATER CLOSET
WOOD
WITHOUT
WALL OPENING
WATER RESISTANT
WATERPROOF
WEIGHT
WELDED WIRE FABRIC
AND
AT
CENTERLINE
DIAMETER
PROPERTY LINE
ALL WORK SHALL COMPLY WITH APPLICABLE CODES,
AMENDMENTS, RULES, ORDINANCE, LAWS, ORDERS, APPROVALS,
ETC.., THAT ARE REQUIRED BY PUBLIC AUTHORITIES. IN THE EVENT
OF CONFLICT, THE MOST STRINGENT REQUIREMENTS SHALL
GOVERN. REQUIREMENTS INCLUDE, BUT ARE NOT LIMITED TO THE
CURRENT APPLICABLE EDITIONS OR PUBLICATIONS OF THE
FOLLOWING (OR AS OTHERWISE NOTED):
Local City or County Ordinances: Butte County
Governing Building Standards to be the “International Building
Code”, 2021 Edition, as adopted and modified by the State of
California in reference to the 2022 California Building Code.
Governing Residential Standards to be the “International
Residential Code”, 2021 Edition, as adopted and modified by the
State of California in reference to the 2022 California Residential
Code.
Governing Electrical Standards to be the “International Electrical
Code”, 2021 Edition, as adopted and modified by the State of
California in reference to the 2022 California Electrical Code.
Governing Mechanical Standards to be the “International
Mechanical Code”, 2021 Edition, as adopted and modified by the
State of California in reference to the 2022 California Mechanical
Code.
Governing Plumbing Standards to be the “International Plumbing
Code”, 2021 Edition, as adopted and modified by the State of
California in reference to the 2022 California Plumbing Code.
Governing Fire Regulation Standards to be the “International Fire
Code”, 2021 Edition, as adopted and modified by the State of
California in reference to the 2022 California Fire Code.
Governing Energy Standards to be the “California Energy
Standards”, 2022 Edition.
Governing Green Building Standards to be the “California Green
Building Standards” 2022 Edition.
DESIGNER:
Sequoia Engineering
1306 Mangrove Ave
Chico, USA 95926
Office: 530.487.7133
Contact: Chad Ratzlaff, P.E., M. ASCE
STRUCTURAL ENGINEER:
Sequoia Engineering
1306 Mangrove Ave.
Chico, CA 95926
Phone: 530.591.7258
Contact: Chad Ratzlaff, P.E., M. ASCE
TRUSS DESIGN:
Homewood Truss
5321 Eastside Rd
Redding, CA 96001
Phone: 530.243.8121
Contact:
FIRE PROTECTION:
NOT REQUIRED
SOLAR PV CONTRACTOR:
NOT REQUIRED
GENERAL CONTRACTOR:
Billson Construction
15 Commerce Ct., Suite 150
Chico, CA 95928
SITE DATA:
LOT SIZE:
TOTAL SITE COVERAGE:
PERCENT COVERAGE:
BUILDING DATA:
TOTAL CONDITIONED AREA:
(E) PORTION TO BE DEMOLISHED:
(E) PORTION TO REMAIN:
(N) ADDITION:
TOTAL SITE COVERAGE:
51668
1621
~3.0%
2244
326
768
1476
1621
SPECIAL FEATURES
• Insulation below roof deck
• Northwest Energy Efficiency Alliance (NEEA) rated heat pump
water heater; specific brand/model, or equivalent, must be
installed
HERS VERIFICATIONS
• Indoor air quality ventilation
• Kitchen range hood
• Minimum Airflow
• Verified Refrigerant Charge
• Fan Efficacy Watts/CFM
• Verified heat pump rated heating capacity
• Duct leakage testing
• Drain water heat recovery system
SQ.FT.
SQ.FT.
SQ.FT.
SQ.FT.
SQ.FT.
THIS PROJECT INCLUDES THE CONSTRUCTION OF A
RESIDENTIAL ADDITION OF 2 BEDROOM, 1.5 BATH
TOTALING 1476 SQ.FT
S2.3 STRUCT. ROOF FRAMING PLAN
S3.1 STRUCTURAL DETAILS
S3.2
S3.3
STRUCTURAL DETAILS
STRUCTURAL DETAILS
STRUCTURAL DETAILSS3.4
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CACOVER SHEET24-123
SUBMITTAL
CMR
06.05.2025
A1
JUN 05, 2025
PROJECT SITE
CHAPTER 4
RESIDENTIAL MANDATORY MEASURES
DIVISION 4.1 PLANNING AND DESIGN
DIVISION 4.3 WATER EFFICIENCY AND CONSERVATION
4.406 ENHANCED DURABILITY AND REDUCED MAINTENANCE
4.406.1 RODENT PROOFING. Annular spaces around pipes, electric cables, conduits or other openings in
sole/bottom plates at exterior walls shall be protected against the passage of rodents by closing such
openings with cement mortar, concrete masonry or a similar method acceptable to the enforcing
agency.
4.408 CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RECYCLING
4.408.1 CONSTRUCTION WASTE MANAGEMENT. Recycle and/or salvage for reuse a minimum of 65
percent of the non-hazardous construction and demolition waste in accordance with either Section
4.408.2, 4.408.3 or 4.408.4, or meet a more stringent local construction and demolition waste
management ordinance.
Exceptions:
1. Excavated soil and land-clearing debris.
2. Alternate waste reduction methods developed by working with local agencies if diversion or
recycle facilities capable of compliance with this item do not exist or are not located reasonably
close to the jobsite.
3. The enforcing agency may make exceptions to the requirements of this section when isolated
jobsites are located in areas beyond the haul boundaries of the diversion facility.
4.408.2 CONSTRUCTION WASTE MANAGEMENT PLAN. Submit a construction waste management plan
in conformance with Items 1 through 5. The construction waste management plan shall be updated as
necessary and shall be available during construction for examination by the enforcing agency.
1. Identify the construction and demolition waste materials to be diverted from disposal by recycling,
reuse on the project or salvage for future use or sale.
2. Specify if construction and demolition waste materials will be sorted on-site (source separated) or
bulk mixed (single stream).
3. Identify diversion facilities where the construction and demolition waste material collected will be
taken.
4. Identify construction methods employed to reduce the amount of construction and demolition waste
generated.
5. Specify that the amount of construction and demolition waste materials diverted shall be calculated
by weight or volume, but not by both.
4.408.3 WASTE MANAGEMENT COMPANY. Utilize a waste management company, approved by the
enforcing agency, which can provide verifiable documentation that the percentage of construction and
demolition waste material diverted from the landfill complies with Section 4.408.1.
Note: The owner or contractor may make the determination if the construction and demolition waste
materials will be diverted by a waste management company.
4.408.4 WASTE STREAM REDUCTION ALTERNATIVE [LR]. Projects that generate a total combined
weight of construction and demolition waste disposed of in landfills, which do not exceed 3.4
lbs./sq.ft. of the building area shall meet the minimum 65% construction waste reduction requirement in
Section 4.408.1
4.408.4.1 WASTE STREAM REDUCTION ALTERNATIVE. Projects that generate a total combined
weight of construction and demolition waste disposed of in landfills, which do not exceed 2 pounds
per square foot of the building area, shall meet the minimum 65% construction waste reduction
requirement in Section 4.408.1
4.408.5 DOCUMENTATION. Documentation shall be provided to the enforcing agency which demonstrates
compliance with Section 4.408.2, items 1 through 5, Section 4.408.3 or Section 4.408.4..
Notes:
1. Sample forms found in "A Guide to the California Green Building Standards Code
(Residential)" located at www.hcd.ca.gov/CALGreen.html may be used to assist in
documenting compliance with this section.
2. Mixed construction and demolition debris (C & D) processors can be located at the California
Department of Resources Recycling and Recovery (CalRecycle).
4.410 BUILDING MAINTENANCE AND OPERATION
4.410.1 OPERATION AND MAINTENANCE MANUAL. At the time of final inspection, a manual, compact
disc, web-based reference or other media acceptable to the enforcing agency which includes all of the
following shall be placed in the building:
1. Directions to the owner or occupant that the manual shall remain with the building throughout the
life cycle of the structure.
2. Operation and maintenance instructions for the following:
a. Equipment and appliances, including water-saving devices and systems, HVAC systems,
photovoltaic systems, electric vehicle chargers, water-heating systems and other major
appliances and equipment.
b. Roof and yard drainage, including gutters and downspouts.
c. Space conditioning systems, including condensers and air filters.
d. Landscape irrigation systems.
e. Water reuse systems.
3. Information from local utility, water and waste recovery providers on methods to further reduce
resource consumption, including recycle programs and locations.
4. Public transportation and/or carpool options available in the area.
5. Educational material on the positive impacts of an interior relative humidity between 30-60 percent
and what methods an occupant may use to maintain the relative humidity level in that range.
6. Information about water-conserving landscape and irrigation design and controllers which conserve
water.
7. Instructions for maintaining gutters and downspouts and the importance of diverting water at least 5
feet away from the foundation.
8. Information on required routine maintenance measures, including, but not limited to, caulking,
painting, grading around the building, etc.
9. Information about state solar energy and incentive programs available.
10. A copy of all special inspections verifications required by the enforcing agency or this code.
11. Information from the Department of Forestry and Fire Protection on maintenance of defensible
space around residential structures.
12. Information and/or drawings identifying the location of grab bar reinforcements.
4.410.2 RECYCLING BY OCCUPANTS. Where 5 or more multifamily dwelling units are constructed on a
building site, provide readily accessible area(s) that serves all buildings on the site and are identified for the
depositing, storage and collection of non-hazardous materials for recycling, including (at a minimum) paper,
corrugated cardboard, glass, plastics, organic waster, and metals, or meet a lawfully enacted local recycling
ordinance, if more restrictive.
Exception: Rural jurisdictions that meet and apply for the exemption in Public Resources Code Section
42649.82 (a)(2)(A) et seq. are note required to comply with the organic waste portion of
this section.
DIVISION 4.4 MATERIAL CONSERVATION AND RESOURCE
EFFICIENCY
DIVISION 4.5 ENVIRONMENTAL QUALITY
4.303 INDOOR WATER USE
4.303.1 WATER CONSERVING PLUMBING FIXTURES AND FITTINGS. Plumbing fixtures (water closets and
urinals) and fittings (faucets and showerheads) shall comply with the sections 4.303.1.1, 4.303.1.2, 4.303.1.3,
and 4.303.4.4.
Note: All noncompliant plumbing fixtures in any residential real property shall be replaced with water-conserving
plumbing fixtures. Plumbing fixture replacement is required prior to issuance of a certificate of final
completion, certificate of occupancy, or final permit approval by the local building department. See Civil
Code Section 1101.1, et seq., for the definition of a noncompliant plumbing fixture, types of residential
buildings affected and other important enactment dates.
4.303.1.1 Water Closets. The effective flush volume of all water closets shall not exceed 1.28 gallons per
flush. Tank-type water closets shall be certified to the performance criteria of the U.S. EPA WaterSense
Specification for Tank-type Toilets.
Note: The effective flush volume of dual flush toilets is defined as the composite, average flush volume
of two reduced flushes and one full flush.
4.303.1.2 Urinals. The effective flush volume of wall mounted urinals shall not exceed 0.125 gallons per flush.
The effective flush volume of all other urinals shall not exceed 0.5 gallons per flush.
4.303.1.3 Showerheads.
4.303.1.3.1 Single Showerhead. Showerheads shall have a maximum flow rate of not more than 1.8
gallons per minute at 80 psi. Showerheads shall be certified to the performance criteria of the U.S. EPA
WaterSense Specification for Showerheads.
4.303.1.3.2 Multiple showerheads serving one shower. When a shower is served by more than one
showerhead, the combined flow rate of all the showerheads and/or other shower outlets controlled by
a single valve shall not exceed 1.8 gallons per minute at 80 psi, or the shower shall be designed to only
allow one shower outlet to be in operation at a time.
Note: A hand-held shower shall be considered a showerhead.
4.303.1.4 Faucets.
4.303.1.4.1 Residential Lavatory Faucets. The maximum flow rate of residential lavatory faucets shall
not exceed 1.2 gallons per minute at 60 psi. The minimum flow rate of residential lavatory faucets shall
not be less than 0.8 gallons per minute at 20 psi.
4.303.1.4.2 Lavatory Faucets in Common and Public Use Areas. The maximum flow rate of lavatory
faucets installed in common and public use areas (outside of dwellings or sleeping units) in residential
buildings shall not exceed 0.5 gallons per minute at 60 psi.
4.303.1.4.3 Metering Faucets. Metering faucets when installed in residential buildings shall not deliver
more than 0.2 gallons per cycle.
4.303.1.4.4 Kitchen Faucets. The maximum flow rate of kitchen faucets shall not exceed 1.8 gallons
per minute at 60 psi. Kitchen faucets may temporarily increase the flow above the maximum rate, but not
to exceed 2.2 gallons per minute at 60 psi, and must default to a maximum flow rate of 1.8 gallons per
minute at 60 psi.
Note: Where complying faucets are unavailable, aerators or other means may be used to achieve
reduction.
4.303.1.4.5 Pre-rinse spray valves.
When installed, shall meet the requirements in the California Code of Regulations, Title 20 (Appliance
Efficiency Regulations), Sections 1605.1 (h)(4) Table H-2, Section 1605.3 (h)(4)(A), and Section 1607
(d)(7) and shall be equipped with an integral automatic shutoff.
FOR REFERENCE ONLY: The following table and code section have been reprinted from the California
Code of Regulations, Title 20 (Appliance Efficiency Regulations),Section 1605.1 (h)(4) and Section
1605.3 (h)(4)(A).
Title 20 Section 1605.3 (h)(4)(A): Commercial prerinse spray values manufactured on or after January
1, 2006, shall have a minimum spray force of not less than 4.0 ounces-force (ozf)[113 grams-force(gf)]
4.303.2 Submeters for multifamily buildings and dwelling units in mixed-used residential/commercial
buildings.
Submeters shall be installed to measure water usage of individual rental dwelling units in accordance with the
California Plumbing Code.
4.303.3 Standards for plumbing fixtures and fittings. Plumbing fixtures and fittings shall be installed in
accordance with the California Plumbing Code, and shall meet the applicable standards referenced in Table
1701.1 of the California Plumbing Code.
TABLE - MAXIMUM FIXTURE WATER USE
FIXTURE TYPE FLOW RATE
SHOWER HEADS (RESIDENTIAL)1.8 GMP @ 80 PSI
LAVATORY FAUCETS (RESIDENTIAL)MAX. 1.2 GPM @ 60 PSI MIN. 0.8 GPM @ 20
PSI
LAVATORY FAUCETS IN COMMON & PUBLIC
USE AREAS 0.5 GPM @ 60 PSI
KITCHEN FAUCETS 1.8 GPM @ 60 PSI
METERING FAUCETS 0.2 GAL/CYCLE
WATER CLOSET 1.28 GAL/FLUSH
URINALS 0.125 GAL/FLUSH
4.304 OUTDOOR WATER USE
4.304.1 OUTDOOR POTABLE WATER USE IN LANDSCAPE AREAS. Residential developments shall comply with
a local water efficient landscape ordinance or the current California Department of Water Resources' Model Water
Efficient Landscape Ordinance (MWELO), whichever is more stringent.
NOTES:
1. The Model Water Efficient Landscape Ordinance (MWELO) is located in the California Code Regulations,
Title 23, Chapter 2.7, Division 2. MWELO and supporting documents, including water budget calculator, are
available at: https://www.water.ca.gov/
ABBREVIATION DEFINITIONS:
HCD Department of Housing and Community Development
BSC California Building Standards Commission
DSA-SS Division of the State Architect, Structural Safety
OSHPD Office of Statewide Health Planning and Development
LR Low Rise
HR High Rise
AA Additions and Alterations
N New
NOTE:
THIS TABLE COMPILES THE DATA IN SECTION 4.303.1, AND IS INCLUDED AS A
CONVENIENCE FOR THE USER.
SECTION 4.102 DEFINITIONS
4.102.1 DEFINITIONS
The following terms are defined in Chapter 2 (and are included here for reference)
FRENCH DRAIN. A trench, hole or other depressed area loosely filled with rock, gravel, fragments of brick or similar
pervious material used to collect or channel drainage or runoff water.
WATTLES. Wattles are used to reduce sediment in runoff. Wattles are often constructed of natural plant materials
such as hay, straw or similar material shaped in the form of tubes and placed on a downflow slope. Wattles are also
used for perimeter and inlet controls.
4.106 SITE DEVELOPMENT
4.106.1 GENERAL. Preservation and use of available natural resources shall be accomplished through evaluation
and careful planning to minimize negative effects on the site and adjacent areas. Preservation of slopes,
management of storm water drainage and erosion controls shall comply with this section.
4.106.2 STORM WATER DRAINAGE AND RETENTION DURING CONSTRUCTION. Projects which disturb less
than one acre of soil and are not part of a larger common plan of development which in total disturbs one acre
or more, shall manage storm water drainage during construction. In order to manage storm water drainage
during construction, one or more of the following measures shall be implemented to prevent flooding of adjacent
property, prevent erosion and retain soil runoff on the site.
1. Retention basins of sufficient size shall be utilized to retain storm water on the site.
2. Where storm water is conveyed to a public drainage system, collection point, gutter or similar
disposal method, water shall be filtered by use of a barrier system, wattle or other method approved
by the enforcing agency.
3. Compliance with a lawfully enacted storm water management ordinance.
Note: Refer to the State Water Resources Control Board for projects which disturb one acre or more of soil, or
are part of a larger common plan of development which in total disturbs one acre or more of soil.
(Website: https://www.waterboards.ca.gov/water_issues/programs/stormwater/construction.html)
4.106.3 GRADING AND PAVING. Construction plans shall indicate how the site grading or drainage system will
manage all surface water flows to keep water from entering buildings. Examples of methods to manage surface
water include, but are not limited to, the following:
1. Swales
2. Water collection and disposal systems
3. French drains
4. Water retention gardens
5. Other water measures which keep surface water away from buildings and aid in groundwater
recharge.
Exception: Additions and alterations not altering the drainage path.
4.106.4 Electric vehicle (EV) charging for new construction. New construction shall comply with Sections
4.106.4.1 or 4.106.4.2 to facilitate future installation and use of EV chargers. Electric vehicle supply
equipment (EVSE) shall be installed in accordance with the California Electrical Code, Article 625.
Exceptions:
1. On a case-by-case basis, where the local enforcing agency has determined EV charging and
infrastructure are not feasible based upon one or more of the following conditions:
1.1 Where there is no local utility power supply or the local utility is unable to supply adequate
power.
1.2 Where there is evidence suitable to the local enforcing agency substantiating that additional
local utility infrastructure design requirements, directly related to the implementation of Section
4.106.4, may adversely impact the construction cost of the project.
2. Accessory Dwelling Units (ADU) and Junior Accessory Dwelling Units (JADU) without additional
parking facilities.
4.106.4.1 New one- and two-family dwellings and townhouses with attached private garages. For each
dwelling unit, install a listed raceway to accommodate a dedicated 208/240-volt branch circuit. The raceway
shall not be less than trade size 1 (nominal 1-inch inside diameter). The raceway shall originate at the main
service or subpanel and shall terminate into a listed cabinet, box or other enclosure in close proximity to the
proposed location of an EV charger. Raceways are required to be continuous at enclosed, inaccessible or
concealed areas and spaces. The service panel and/or subpanel shall provide capacity to install a 40-ampere
208/240-volt minimum dedicated branch circuit and space(s) reserved to permit installation of a branch circuit
overcurrent protective device.
Exemption: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is
installed in close proximity to the proposed location of an EV charger at the time of original construction in
accordance with the California Electrical Code.
4.106.4.1.1 Identification. The service panel or subpanel circuit directory shall identify the overcurrent
protective device space(s) reserved for future EV charging as "EV CAPABLE". The raceway termination
location shall be permanently and visibly marked as "EV CAPABLE".
CHAPTER 3
GREEN BUILDING
SECTION 301 GENERAL
301.1 SCOPE. Buildings shall be designed to include the green building measures specified as mandatory in
the application checklists contained in this code. Voluntary green building measures are also included in the
application checklists and may be included in the design and construction of structures covered by this code,
but are not required unless adopted by a city, county, or city and county as specified in Section 101.7.
301.1.1 Additions and alterations. [HCD] The mandatory provisions of Chapter 4 shall be applied to
additions or alterations of existing residential buildings where the addition or alteration increases the
building's conditioned area, volume, or size. The requirements shall apply only to and/or within the
specific area of the addition or alteration.
The mandatory provision of Section 4.106.4.2 may apply to additions or alterations of existing parking
facilities or the addition of new parking facilities serving existing multifamily buildings. See Section
4.106.4.3 for application.
Note: Repairs including, but not limited to, resurfacing, restriping and repairing or maintaining existing
lighting fixtures are not considered alterations for the purpose of this section.
Note: On and after January 1, 2014, residential buildings undergoing permitted alterations, additions, or
improvements shall replace noncompliant plumbing fixtures with water-conserving plumbing fixtures.
Plumbing fixture replacement is required prior to issuance of a certificate of final completion, certificate
of occupancy or final permit approval by the local building department. See Civil Code Section 1101.1,
et seq., for the definition of a noncompliant plumbing fixture, types of residential buildings affected and
other important enactment dates.
301.2 LOW-RISE AND HIGH-RISE RESIDENTIAL BUILDINGS. [HCD] The provisions of
individual sections of CALGreen may apply to either low-rise residential buildings high-rise residential
buildings, or both. Individual sections will be designated by banners to indicate where the section applies
specifically to low-rise only (LR) or high-rise only (HR). When the section applies to both low-rise and
high-rise buildings, no banner will be used.
SECTION 302 MIXED OCCUPANCY BUILDINGS
302.1 MIXED OCCUPANCY BUILDINGS. In mixed occupancy buildings, each portion of a building
shall comply with the specific green building measures applicable to each specific occupancy.
Exceptions:
1. [HCD] Accessory structures and accessory occupancies serving residential buildings shall
comply with Chapter 4 and Appendix A4, as applicable.
2. [HCD] For purposes of CALGreen, live/work units, complying with Section 419 of the California
Building Code, shall not be considered mixed occupancies. Live/Work units shall comply with
Chapter 4 and Appendix A4, as applicable.
4.106.4.2 New multifamily dwellings, hotels and motels and new residential parking facilities.
When parking is provided, parking spaces for new multifamily dwellings, hotels and motels shall meet the
requirements of Sections 4.106.4.2.1 and 4.106.4.2.2. Calculations for spaces shall be rounded up to the nearest
whole number. A parking space served by electric vehicle supply equipment or designed as a future EV charging
space shall count as at least one standard automobile parking space only for the purpose of complying with any
applicable minimum parking space requirements established by a local jurisdiction. See Vehicle Code Section 22511.2
for further details.
4.106.4.2.1Multifamily development projects with less than 20 dwelling units; and hotels and motels with less
than 20 sleeping units or guest rooms.
The number of dwelling units, sleeping units or guest rooms shall be based on all buildings on a project site subject to
this section.
1.EV Capable. Ten (10) percent of the total number of parking spaces on a building site, provided for all types
of parking facilities, shall be electric vehicle charging spaces (EV spaces) capable of supporting future Level 2
EVSE. Electrical load calculations shall demonstrate that the electrical panel service capacity and electrical
system, including any on-site distribution transformer(s), have sufficient capacity to simultaneously charge all
EVs at all required EV spaces at a minimum of 40 amperes.
The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved
for future EV charging purposes as “EV CAPABLE” in accordance with the California Electrical Code.
Exceptions:
1.When EV chargers (Level 2 EVSE) are installed in a number equal to or greater than the required number
of EV capable spaces.
2.When EV chargers (Level 2 EVSE) are installed in a number less than the required number of EV capable
spaces, the number of EV capable spaces required may be reduced by a number equal to the number of
EV chargers installed.
Notes:
a.Construction documents are intended to demonstrate the project’s capability and capacity for facilitating
future EV charging.
b.There is no requirement for EV spaces to be constructed or available until receptacles for EV charging or
EV chargers are installed for use.
2.EV Ready. Twenty-five (25) percent of the total number of parking spaces shall be equipped with low power
Level 2 EV charging receptacles. For multifamily parking facilities, no more than one receptacle is required per
dwelling unit when more than one parking space is provided for use by a single dwelling unit.
Exception: Areas of parking facilities served by parking lifts.
4.106.4.2.2 Multifamily development projects with 20 or more dwelling units, hotels and motels with 20 or more
sleeping units or guest rooms.
The number of dwelling units, sleeping units or guest rooms shall be based on all buildings on a project site subject to
this section.
1.EV Capable. Ten (10) percent of the total number of parking spaces on a building site, provided for all types
of parking facilities, shall be electric vehicle charging spaces (EV spaces) capable of supporting future Level 2
EVSE. Electrical load calculations shall demonstrate that the electrical panel service capacity and electrical
system, including any on-site distribution transformer(s), have sufficient capacity to simultaneously charge all
EVs at all required EV spaces at a minimum of 40 amperes.
The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved
for future EV charging purposes as “EV CAPABLE” in accordance with the California Electrical Code.
Exception: When EV chargers (Level 2 EVSE) are installed in a number greater than five (5) percent of
parking spaces required by Section 4.106.4.2.2, Item 3, the number of EV capable spaces required may be
reduced by a number equal to the number of EV chargers installed over the five (5) percent required.
Notes:
a.Construction documents shall show locations of future EV spaces.
b.There is no requirement for EV spaces to be constructed or available until receptacles for EV charging or
EV chargers are installed for use.
2.EV Ready. Twenty-five (25) percent of the total number of parking spaces shall be equipped with low power
Level 2 EV charging receptacles. For multifamily parking facilities, no more than one receptacle is required per
dwelling unit when more than one parking space is provided for use by a single dwelling unit.
Exception: Areas of parking facilities served by parking lifts.
3.EV Chargers. Five (5) percent of the total number of parking spaces shall be equipped with Level 2 EVSE.
Where common use parking is provided, at least one EV charger shall be located in the common use parking
area and shall be available for use by all residents or guests.
When low power Level 2 EV charging receptacles or Level 2 EVSE are installed beyond the minimum required,
an automatic load management system (ALMS) may be used to reduce the maximum required electrical
capacity to each space served by the ALMS. The electrical system and any on-site distribution transformers
shall have sufficient capacity to deliver at least 3.3 kW simultaneously to each EV charging station (EVCS)
served by the ALMS. The branch circuit shall have a minimum capacity of 40 amperes, and installed EVSE shall
have a capacity of not less than 30 amperes. ALMS shall not be used to reduce the minimum required electrical
capacity to the required EV capable spaces.
4.106.4.2.2.1 Electric vehicle charging stations (EVCS).
Electric vehicle charging stations required by Section 4.106.4.2.2, Item 3, shall comply with Section 4.106.4.2.2.1.
Exception: Electric vehicle charging stations serving public accommodations, public housing, motels and hotels
shall not be required to comply with this section. See California Building Code, Chapter 11B, for applicable
requirements.
4.106.4.2.2.1.1 Location.
EVCS shall comply with at least one of the following options:
1.The charging space shall be located adjacent to an accessible parking space meeting the requirements of
the California Building Code, Chapter 11A, to allow use of the EV charger from the accessible parking space.
2.The charging space shall be located on an accessible route, as defined in the California Building Code,
Chapter 2, to the building.
Exception: Electric vehicle charging stations designed and constructed in compliance with the California
Building Code, Chapter 11B, are not required to comply with Section 4.106.4.2.2.1.1 and Section
4.106.4.2.2.1.2, Item 3.
4.106.4.2.2.1.2 Electric vehicle charging stations (EVCS) dimensions.
The charging spaces shall be designed to comply with the following:
1.The minimum length of each EV space shall be 18 feet (5486 mm).
2.The minimum width of each EV space shall be 9 feet (2743 mm).
3.One in every 25 charging spaces, but not less than one, shall also have an 8-foot (2438 mm) wide minimum
aisle. A 5-foot (1524 mm) wide minimum aisle shall be permitted provided the minimum width of the EV space is
12 feet (3658 mm).
a.Surface slope for this EV space and the aisle shall not exceed 1 unit vertical in 48 units horizontal (2.083
percent slope) in any direction.
4.106.4.2.2.1.3 Accessible EV spaces.
In addition to the requirements in Sections 4.106.4.2.2.1.1 and 4.106.4.2.2.1.2, all EVSE, when installed, shall
comply with the accessibility provisions for EV chargers in the California Building Code, Chapter 11B. EV ready
spaces and EVCS in multifamily developments shall comply with California Building Code, Chapter 11A, Section
1109A.
4.106.4.2.3 EV space requirements.
1.Single EV space required. Install a listed raceway capable of accommodating a 208/240-volt dedicated branch
circuit. The raceway shall not be less than trade size 1 (nominal 1-inch inside diameter). The raceway shall
originate at the main service or subpanel and shall terminate into a listed cabinet, box or enclosure in close
proximity to the location or the proposed location of the EV space. Construction documents shall identify the
raceway termination point, receptacle or charger location, as applicable. The service panel and/ or subpanel shall
have a 40-ampere minimum dedicated branch circuit, including branch circuit overcurrent protective device
installed, or space(s) reserved to permit installation of a branch circuit overcurrent protective device.
Exception: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is
installed in close proximity to the location or the proposed location of the EV space, at the time of original
construction in accordance with the California Electrical Code.
2.Multiple EV spaces required. Construction documents shall indicate the raceway termination point and the
location of installed or future EV spaces, receptacles or EV chargers. Construction documents shall also provide
information on amperage of installed or future receptacles or EVSE, raceway method(s), wiring schematics and
electrical load calculations. Plan design shall be based upon a 40-ampere minimum branch circuit. Required
raceways and related components that are planned to be installed underground, enclosed, inaccessible or in
concealed areas and spaces shall be installed at the time of original construction.
SECTION 4.501 GENERAL
4.501.1 Scope
The provisions of this chapter shall outline means of reducing the quality of air contaminants that are odorous,
irritating and/or harmful to the comfort and well being of a building's installers, occupants and neighbors.
SECTION 4.502 DEFINITIONS
5.102.1 DEFINITIONS
The following terms are defined in Chapter 2 (and are included here for reference)
AGRIFIBER PRODUCTS. Agrifiber products include wheatboard, strawboard, panel substrates and door
cores, not including furniture, fixtures and equipment (FF&E) not considered base building elements.
COMPOSITE WOOD PRODUCTS. Composite wood products include hardwood plywood, particleboard and
medium density fiberboard. "Composite wood products" does not include hardboard, structural plywood,
structural panels, structural composite lumber, oriented strand board, glued laminated timber, prefabricated
wood I-joists or finger-jointed lumber, all as specified in California Code of regulations (CCR), title 17, Section
93120.1.
DIRECT-VENT APPLIANCE. A fuel-burning appliance with a sealed combustion system that draws all air for
combustion from the outside atmosphere and discharges all flue gases to the outside atmosphere.
Y N/AYN/AYN/AYN/A RESPON.
PARTY
RESPON.
PARTY
RESPON.
PARTY
RESPON.
PARTY
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE RESIDENTIAL MANDATORY MEASURES (January 2023)
Y = YES
N/A =NOT APPLICABLE
RESPON. PARTY =RESPONSIBLE PARTY (ie: ARCHITECT, ENGINEER,
OWNER, CONTRACTOR, INSPECTOR ETC.)
4.201 GENERAL
4.201.1 SCOPE. For the purposes of mandatory energy efficiency standards in this code, the California Energy
Commission will continue to adopt mandatory standards.
DIVISION 4.2 ENERGY EFFICIENCY
TABLE H-2
STANDARDS FOR COMMERCIAL PRE-RINSE SPRAY
VALUES MANUFACTURED ON OR AFTER JANUARY 28, 2019
PRODUCT CLASS
[spray force in ounce force (ozf)]MAXIMUM FLOW RATE (gpm)
Product Class 1 (≤1.00
Product Class 2 (> 5.0 ozf and ≤1.20
Product Class 3 (> 8.0 ozf)1.28
Exception: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is
installed in close proximity to the location or the proposed location of the EV space at the time of original
construction in accordance with the California Electrical Code.
4.106.4.2.4 Identification.
The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for
future EV charging purposes as “EV CAPABLE” in accordance with the California Electrical Code.
4.106.4.2.5 Electric Vehicle Ready Space Signage.
Electric vehicle ready spaces shall be identified by signage or pavement markings, in compliance with Caltrans
Traffic Operations Policy Directive 13-01 (Zero Emission Vehicle Signs and Pavement Markings) or its
successor(s).
4.106.4.3 Electric vehicle charging for additions and alterations of parking facilities serving existing
multifamily buildings.
When new parking facilities are added, or electrical systems or lighting of existing parking facilities are added or
altered and the work requires a building permit, ten (10) percent of the total number of parking spaces added or
altered shall be electric vehicle charging spaces (EV spaces) capable of supporting future Level 2 EVSE.
Notes:
1.Construction documents are intended to demonstrate the project’s capability and capacity for facilitating future
EV charging.
2.There is no requirement for EV spaces to be constructed or available until EV chargers are installed for use.
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CACAL GREEN24-123
SUBMITTAL
CMR
06.05.2025
A2
JUN 05, 2025
MAXIMUM INCREMENTAL REACTIVITY (MIR). The maximum change in weight of ozone formed by adding a
compound to the "Base Reactive Organic Gas (ROG) Mixture" per weight of compound added, expressed to
hundredths of a gram (g O³/g ROC).
Note: MIR values for individual compounds and hydrocarbon solvents are specified in CCR, Title 17, Sections 94700
and 94701.
MOISTURE CONTENT. The weight of the water in wood expressed in percentage of the weight of the oven-dry wood.
PRODUCT-WEIGHTED MIR (PWMIR). The sum of all weighted-MIR for all ingredients in a product subject to this
article. The PWMIR is the total product reactivity expressed to hundredths of a gram of ozone formed per gram of
product (excluding container and packaging).
Note: PWMIR is calculated according to equations found in CCR, Title 17, Section 94521 (a).
REACTIVE ORGANIC COMPOUND (ROC). Any compound that has the potential, once emitted, to contribute to
ozone formation in the troposphere.
VOC. A volatile organic compound (VOC) broadly defined as a chemical compound based on carbon chains or rings
with vapor pressures greater than 0.1 millimeters of mercury at room temperature. These compounds typically contain
hydrogen and may contain oxygen, nitrogen and other elements. See CCR Title 17, Section 94508(a).
4.503 FIREPLACES
4.503.1 GENERAL. Any installed gas fireplace shall be a direct-vent sealed-combustion type. Any installed
woodstove or pellet stove shall comply with U.S. EPA New Source Performance Standards (NSPS) emission limits as
applicable, and shall have a permanent label indicating they are certified to meet the emission limits. Woodstoves,
pellet stoves and fireplaces shall also comply with applicable local ordinances.
4.504 POLLUTANT CONTROL
4.504.1 COVERING OF DUCT OPENINGS & PROTECTION OF MECHANICAL EQUIPMENT DURING
CONSTRUCTION. At the time of rough installation, during storage on the construction site and until final
startup of the heating, cooling and ventilating equipment, all duct and other related air distribution component
openings shall be covered with tape, plastic, sheet metal or other methods acceptable to the enforcing agency to
reduce the amount of water, dust or debris which may enter the system.
4.504.2 FINISH MATERIAL POLLUTANT CONTROL. Finish materials shall comply with this section.
4.504.2.1 Adhesives, Sealants and Caulks. Adhesives, sealant and caulks used on the project shall meet the
requirements of the following standards unless more stringent local or regional air pollution or air quality
management district rules apply:
1. Adhesives, adhesive bonding primers, adhesive primers, sealants, sealant primers and caulks
shall comply with local or regional air pollution control or air quality management district rules where
applicable or SCAQMD Rule 1168 VOC limits, as shown in Table 4.504.1 or 4.504.2, as applicable.
Such products also shall comply with the Rule 1168 prohibition on the use of certain toxic
compounds (chloroform, ethylene dichloride, methylene chloride, perchloroethylene and
tricloroethylene), except for aerosol products, as specified in Subsection 2 below.
2. Aerosol adhesives, and smaller unit sizes of adhesives, and sealant or caulking compounds (in
units of product, less packaging, which do not weigh more than 1 pound and do not consist of more
than 16 fluid ounces) shall comply with statewide VOC standards and other requirements, including
prohibitions on use of certain toxic compounds, of California Code of Regulations, Title 17,
commencing with section 94507.
4.504.2.2 Paints and Coatings. Architectural paints and coatings shall comply with VOC limits in Table 1 of
the ARB Architectural Suggested Control Measure, as shown in Table 4.504.3, unless more stringent local limits
apply. The VOC content limit for coatings that do not meet the definitions for the specialty coatings categories
listed in Table 4.504.3 shall be determined by classifying the coating as a Flat, Nonflat or Nonflat-High Gloss
coating, based on its gloss, as defined in subsections 4.21, 4.36, and 4.37 of the 2007 California Air Resources
Board, Suggested Control Measure, and the corresponding Flat, Nonflat or Nonflat-High Gloss VOC limit in
Table 4.504.3 shall apply.
4.504.2.3 Aerosol Paints and Coatings. Aerosol paints and coatings shall meet the Product-weighted MIR
Limits for ROC in Section 94522(a)(2) and other requirements, including prohibitions on use of certain toxic
compounds and ozone depleting substances, in Sections 94522(e)(1) and (f)(1) of California Code of
Regulations, Title 17, commencing with Section 94520; and in areas under the jurisdiction of the Bay Area Air
Quality Management District additionally comply with the percent VOC by weight of product limits of Regulation
8, Rule 49.
4.504.2.4 Verification. Verification of compliance with this section shall be provided at the request of the
enforcing agency. Documentation may include, but is not limited to, the following:
1. Manufacturer's product specification.
2. Field verification of on-site product containers.
CHAPTER 7
INSTALLER & SPECIAL INSPECTOR QUALIFICATIONS
702 QUALIFICATIONS
702.1 INSTALLER TRAINING. HVAC system installers shall be trained and certified in the proper
installation of HVAC systems including ducts and equipment by a nationally or regionally recognized training or
certification program. Uncertified persons may perform HVAC installations when under the direct supervision and
responsibility of a person trained and certified to install HVAC systems or contractor licensed to install HVAC systems.
Examples of acceptable HVAC training and certification programs include but are not limited to the following:
1. State certified apprenticeship programs.
2. Public utility training programs.
3. Training programs sponsored by trade, labor or statewide energy consulting or verification organizations.
4. Programs sponsored by manufacturing organizations.
5. Other programs acceptable to the enforcing agency.
702.2 SPECIAL INSPECTION [HCD]. When required by the enforcing agency, the owner or the
responsible entity acting as the owner's agent shall employ one or more special inspectors to provide inspection or
other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence
to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition to
other certifications or qualifications acceptable to the enforcing agency, the following certifications or education may be
considered by the enforcing agency when evaluating the qualifications of a special inspector:
1. Certification by a national or regional green building program or standard publisher.
2. Certification by a statewide energy consulting or verification organization, such as HERS raters, building
performance contractors, and home energy auditors.
3. Successful completion of a third party apprentice training program in the appropriate trade.
4. Other programs acceptable to the enforcing agency.
Notes:
1. Special inspectors shall be independent entities with no financial interest in the materials or the
project they are inspecting for compliance with this code.
2. HERS raters are special inspectors certified by the California Energy Commission (CEC) to rate
homes in California according to the Home Energy Rating System (HERS).
[BSC] When required by the enforcing agency, the owner or the responsible entity acting as the owner's agent shall
employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance with
this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the
particular type of inspection or task to be performed. In addition, the special inspector shall have a certification from a
recognized state, national or international association, as determined by the local agency. The area of certification
shall be closely related to the primary job function, as determined by the local agency.
Note: Special inspectors shall be independent entities with no financial interest in the materials or the
project they are inspecting for compliance with this code.
703 VERIFICATIONS
703.1 DOCUMENTATION. Documentation used to show compliance with this code shall include but is not
limited to, construction documents, plans, specifications, builder or installer certification, inspection reports, or other
methods acceptable to the enforcing agency which demonstrate substantial conformance. When specific
documentation or special inspection is necessary to verify compliance, that method of compliance will be specified in
the appropriate section or identified applicable checklist.
4.505 INTERIOR MOISTURE CONTROL
4.505.1 General. Buildings shall meet or exceed the provisions of the California Building Standards Code.
4.505.2 CONCRETE SLAB FOUNDATIONS. Concrete slab foundations required to have a vapor retarder by
California Building Code, Chapter 19, or concrete slab-on-ground floors required to have a vapor retarder by the
California Residential Code, Chapter 5, shall also comply with this section.
4.505.2.1 Capillary break. A capillary break shall be installed in compliance with at least one of the
following:
1. A 4-inch (101.6 mm) thick base of 1/2 inch (12.7mm) or larger clean aggregate shall be provided with
a vapor barrier in direct contact with concrete and a concrete mix design, which will address bleeding,
shrinkage, and curling, shall be used. For additional information, see American Concrete Institute,
ACI 302.2R-06.
2. Other equivalent methods approved by the enforcing agency.
3. A slab design specified by a licensed design professional.
4.505.3 MOISTURE CONTENT OF BUILDING MATERIALS. Building materials with visible signs of water damage
shall not be installed. Wall and floor framing shall not be enclosed when the framing members exceed 19 percent
moisture content. Moisture content shall be verified in compliance with the following:
1. Moisture content shall be determined with either a probe-type or contact-type moisture meter.Equivalent
moisture verification methods may be approved by the enforcing agency and shall satisfy requirements
found in Section 101.8 of this code.
2. Moisture readings shall be taken at a point 2 feet (610 mm) to 4 feet (1219 mm) from the grade stamped end
of each piece verified.
3. At least three random moisture readings shall be performed on wall and floor framing with documentation
acceptable to the enforcing agency provided at the time of approval to enclose the wall and floor framing.
Insulation products which are visibly wet or have a high moisture content shall be replaced or allowed to dry prior to
enclosure in wall or floor cavities. Wet-applied insulation products shall follow the manufacturers' drying
recommendations prior to enclosure.
4.506 INDOOR AIR QUALITY AND EXHAUST
4.506.1 Bathroom exhaust fans. Each bathroom shall be mechanically ventilated and shall comply with the
following:
1. Fans shall be ENERGY STAR compliant and be ducted to terminate outside the building.
2. Unless functioning as a component of a whole house ventilation system, fans must be controlled by a
humidity control.
a. Humidity controls shall be capable of adjustment between a relative humidity range less than or
equal to 50% to a maximum of 80%. A humidity control may utilize manual or automatic means of
adjustment.
b. A humidity control may be a separate component to the exhaust fan and is not required to be
integral (i.e., built-in)
Notes:
1. For the purposes of this section, a bathroom is a room which contains a bathtub, shower or
tub/shower combination.
2. Lighting integral to bathroom exhaust fans shall comply with the California Energy Code.
4.507 ENVIRONMENTAL COMFORT
4.507.2 HEATING AND AIR-CONDITIONING SYSTEM DESIGN. Heating and air conditioning systems shall be
sized, designed and have their equipment selected using the following methods:
1. The heat loss and heat gain is established according to ANSI/ACCA 2 Manual J - 2011 (Residential
Load Calculation), ASHRAE handbooks or other equivalent design software or methods.
2. Duct systems are sized according to ANSI/ACCA 1 Manual D - 2014 (Residential Duct Systems),
ASHRAE handbooks or other equivalent design software or methods.
3. Select heating and cooling equipment according to ANSI/ACCA 3 Manual S - 2014 (Residential
Equipment Selection), or other equivalent design software or methods.
Exception: Use of alternate design temperatures necessary to ensure the system functions are
acceptable.
TABLE 4.504.1 - ADHESIVE VOC LIMIT1,2
(Less Water and Less Exempt Compounds in Grams per Liter)
ARCHITECTURAL APPLICATIONS VOC LIMIT
INDOOR CARPET ADHESIVES 50
CARPET PAD ADHESIVES 50
OUTDOOR CARPET ADHESIVES 150
WOOD FLOORING ADHESIVES 100
RUBBER FLOOR ADHESIVES 60
SUBFLOOR ADHESIVES 50
CERAMIC TILE ADHESIVES 65
VCT & ASPHALT TILE ADHESIVES 50
DRYWALL & PANEL ADHESIVES 50
COVE BASE ADHESIVES 50
MULTIPURPOSE CONSTRUCTION ADHESIVE 70
STRUCTURAL GLAZING ADHESIVES 100
SINGLE-PLY ROOF MEMBRANE ADHESIVES 250
OTHER ADHESIVES NOT LISTED 50
SPECIALTY APPLICATIONS
PVC WELDING 510
CPVC WELDING 490
ABS WELDING 325
PLASTIC CEMENT WELDING 250
ADHESIVE PRIMER FOR PLASTIC 550
CONTACT ADHESIVE 80
SPECIAL PURPOSE CONTACT ADHESIVE 250
STRUCTURAL WOOD MEMBER ADHESIVE 140
TOP & TRIM ADHESIVE 250
SUBSTRATE SPECIFIC APPLICATIONS
METAL TO METAL 30
PLASTIC FOAMS 50
POROUS MATERIAL (EXCEPT WOOD)50
WOOD 30
FIBERGLASS 80
1. IF AN ADHESIVE IS USED TO BOND DISSIMILAR SUBSTRATES TOGETHER,
THE ADHESIVE WITH THE HIGHEST VOC CONTENT SHALL BE ALLOWED.
2. FOR ADDITIONAL INFORMATION REGARDING METHODS TO MEASURE
THE VOC CONTENT SPECIFIED IN THIS TABLE, SEE SOUTH COAST AIR
QUALITY MANAGEMENT DISTRICT RULE 1168.
TABLE 4.504.2 - SEALANT VOC LIMIT
(Less Water and Less Exempt Compounds in Grams per Liter)
SEALANTS VOC LIMIT
ARCHITECTURAL 250
MARINE DECK 760
NONMEMBRANE ROOF 300
ROADWAY 250
SINGLE-PLY ROOF MEMBRANE 450
OTHER 420
SEALANT PRIMERS
ARCHITECTURAL
NON-POROUS 250
POROUS 775
MODIFIED BITUMINOUS 500
MARINE DECK 760
OTHER 750
TABLE 4.504.5 - FORMALDEHYDE LIMITS1
MAXIMUM FORMALDEHYDE EMISSIONS IN PARTS PER MILLION
PRODUCT CURRENT LIMIT
HARDWOOD PLYWOOD VENEER CORE 0.05
HARDWOOD PLYWOOD COMPOSITE CORE 0.05
PARTICLE BOARD 0.09
MEDIUM DENSITY FIBERBOARD 0.11
THIN MEDIUM DENSITY FIBERBOARD2 0.13
1. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED
BY THE CALIF. AIR RESOURCES BOARD, AIR TOXICS CONTROL
MEASURE FOR COMPOSITE WOOD AS TESTED IN ACCORDANCE
WITH ASTM E 1333. FOR ADDITIONAL INFORMATION, SEE CALIF.
CODE OF REGULATIONS, TITLE 17, SECTIONS 93120 THROUGH
93120.12.
2. THIN MEDIUM DENSITY FIBERBOARD HAS A MAXIMUM
THICKNESS OF 5/16" (8 MM).
TABLE 4.504.3 - VOC CONTENT LIMITS FOR
ARCHITECTURAL COATINGS2,3
GRAMS OF VOC PER LITER OF COATING, LESS WATER & LESS EXEMPT
COMPOUNDS
COATING CATEGORY VOC LIMIT
FLAT COATINGS 50
NON-FLAT COATINGS 100
NONFLAT-HIGH GLOSS COATINGS 150
SPECIALTY COATINGS
ALUMINUM ROOF COATINGS 400
BASEMENT SPECIALTY COATINGS 400
BITUMINOUS ROOF COATINGS 50
BITUMINOUS ROOF PRIMERS 350
BOND BREAKERS 350
CONCRETE CURING COMPOUNDS 350
CONCRETE/MASONRY SEALERS 100
DRIVEWAY SEALERS 50
DRY FOG COATINGS 150
FAUX FINISHING COATINGS 350
FIRE RESISTIVE COATINGS 350
FLOOR COATINGS 100
FORM-RELEASE COMPOUNDS 250
GRAPHIC ARTS COATINGS (SIGN PAINTS)500
HIGH TEMPERATURE COATINGS 420
INDUSTRIAL MAINTENANCE COATINGS 250
LOW SOLIDS COATINGS1 120
MAGNESITE CEMENT COATINGS 450
MASTIC TEXTURE COATINGS 100
METALLIC PIGMENTED COATINGS 500
MULTICOLOR COATINGS 250
PRETREATMENT WASH PRIMERS 420
PRIMERS, SEALERS, & UNDERCOATERS 100
REACTIVE PENETRATING SEALERS 350
RECYCLED COATINGS 250
ROOF COATINGS 50
RUST PREVENTATIVE COATINGS 250
SHELLACS
CLEAR 730
OPAQUE 550
SPECIALTY PRIMERS, SEALERS &
UNDERCOATERS 100
STAINS 250
STONE CONSOLIDANTS 450
SWIMMING POOL COATINGS 340
TRAFFIC MARKING COATINGS 100
TUB & TILE REFINISH COATINGS 420
WATERPROOFING MEMBRANES 250
WOOD COATINGS 275
WOOD PRESERVATIVES 350
ZINC-RICH PRIMERS 340
1. GRAMS OF VOC PER LITER OF COATING, INCLUDING WATER &
EXEMPT COMPOUNDS
2. THE SPECIFIED LIMITS REMAIN IN EFFECT UNLESS REVISED LIMITS
ARE LISTED IN SUBSEQUENT COLUMNS IN THE TABLE.
3. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED BY
THE CALIFORNIA AIR RESOURCES BOARD, ARCHITECTURAL COATINGS
SUGGESTED CONTROL MEASURE, FEB. 1, 2008. MORE INFORMATION IS
AVAILABLE FROM THE AIR RESOURCES BOARD.
DIVISION 4.5 ENVIRONMENTAL QUALITY (continued)
4.504.3 CARPET SYSTEMS. All carpet installed in the building interior shall meet the requirements of the California
Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions
from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for
California Specification 01350)
See California Department of Public Health's website for certification programs and testing labs.
https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx.
4.504.3.1 Carpet cushion. All carpet cushion installed in the building interior shall meet the requirements of the
California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic
Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017
(Emission testing method for California Specification 01350)
See California Department of Public Health's website for certification programs and testing labs.
https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx.
4.504.3.2 Carpet adhesive. All carpet adhesive shall meet the requirements of Table 4.504.1.
4.504.4 RESILIENT FLOORING SYSTEMS. Where resilient flooring is installed , at least 80% of floor area receiving
resilient flooring shall meet the requirements of the California Department of Public Health, "Standard Method for the
Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers,"
Version 1.2, January 2017 (Emission testing method for California Specification 01350)
See California Department of Public Health's website for certification programs and testing labs.
hhtps://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx.
4.504.5 COMPOSITE WOOD PRODUCTS. Hardwood plywood, particleboard and medium density fiberboard
composite wood products used on the interior or exterior of the buildings shall meet the requirements for
formaldehyde as specified in ARB's Air Toxics Control Measure for Composite Wood (17 CCR 93120 et seq.),
by or before the dates specified in those sections, as shown in Table 4.504.5
4.504.5.1 Documentation. Verification of compliance with this section shall be provided as requested
by the enforcing agency. Documentation shall include at least one of the following:
1. Product certifications and specifications.
2. Chain of custody certifications.
3. Product labeled and invoiced as meeting the Composite Wood Products regulation (see
CCR, Title 17, Section 93120, et seq.).
4. Exterior grade products marked as meeting the PS-1 or PS-2 standards of the Engineered
Wood Association, the Australian AS/NZS 2269, European 636 3S standards, and Canadian CSA
0121, CSA 0151, CSA 0153 and CSA 0325 standards.
5. Other methods acceptable to the enforcing agency.
Y N/AYN/AYN/AYN/A RESPON.
PARTY
RESPON.
PARTY
RESPON.
PARTY
RESPON.
PARTY
Y = YES
N/A =NOT APPLICABLE
RESPON. PARTY =RESPONSIBLE PARTY (ie: ARCHITECT, ENGINEER,
OWNER, CONTRACTOR, INSPECTOR ETC.)2022 CALIFORNIA GREEN BUILDING STANDARDS CODE RESIDENTIAL MANDATORY MEASURES (January 2023)REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CACAL GREEN24-123
SUBMITTAL
CMR
06.05.2025
A3
JUN 05, 2025
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CAT2424-123
SUBMITTAL
CMR
06.05.2025
A4
JUN 05, 2025
SECTION R337.1 SCOPE, PURPOSE AND APPLICATION
R337.1.1 SCOPE
SECTION R337 AND ALL SUBSECTIONS APPLY TO BUILDING MATERIALS, SYSTEMS AND OR
ASSEMBLIES USED IN THE EXTERIOR DESIGN AND CONSTRUCTION OF NEW BUILDINGS LOCATED
WITHIN A WILDLAND-URBAN INTERFACE (WUI) FIRE AREA AS DEFINED IN SECTION R337.2.
R337.1.2 PURPOSE
THE PURPOSE OF SECTION R337 IS TO ESTABLISH MINIMUM STANDARDS FOR THE PROTECTION OF
LIFE AND PROPERTY BY INCREASING THE ABILITY OF A BUILDING LOCATED IN ANY FIRE HAZARD
SEVERITY ZONE WITHIN STATE RESPONSIBILITY AREAS OR ANY WILDLAND-URBAN INTERFACE (WUI)
FIRE AREA TO RESIST THE INTRUSION OF FLAME OR BURNING EMBERS PROJECTED BY A VEGETATION
FIRE AND CONTRIBUTES TO A SYSTEMATIC REDUCTION IN CONFLAGRATION LOSSES.
R337.1.3 APPLICATION
NEW BUILDINGS LOCATED IN ANY FIRE HAZARD SEVERITY ZONE OR ANY WILDLAND-URBAN
INTERFACE (WUI) FIRE AREA DESIGNATED BY THE ENFORCING AGENCY CONSTRUCTED AFTER THE
APPLICATION DATE SHALL COMPLY WITH THE PROVISIONS OF THIS SECTION. THIS SHALL INCLUDE
ALL NEW BUILDINGS WITH RESIDENTIAL, COMMERCIAL, EDUCATIONAL, INSTITUTIONAL OR SIMILAR
OCCUPANCY TYPE USE, WHICH SHALL BE REFERRED TO IN THIS SECTION AS "APPLICABLE BUILDING"
(SEE DEFINITION IN SECTION R337.2), AS WELL AS NEW BUILDINGS AND STRUCTURES ACCESSORY TO
THOSE APPLICABLE BUILDINGS (SEE EXCEPTIONS 1 AND 4).
EXCEPTIONS:
1.GROUP U OCCUPANCY ACCESSORY BUILDINGS OF ANY SIZE LOCATED AT LEAST 50 FEET (15 M)
FROM AN APPLICABLE BUILDING ON THE SAME LOT.
2.GROUP U OCCUPANCY AGRICULTURAL BUILDINGS, AS DEFINED IN SECTION 202 OF THE
CALIFORNIA BUILDING CODE, OF ANY SIZE LOCATED AT LEAST 50 FEET (15 M) FROM AN APPLICABLE
BUILDING.
3.GROUP C OCCUPANCY SPECIAL BUILDINGS CONFORMING TO THE LIMITATIONS SPECIFIED IN
SECTION 450.4.1 OF THE CALIFORNIA BUILDING CODE.
4.NEW ACCESSORY BUILDINGS AND MISCELLANEOUS STRUCTURES SPECIFIED IN SECTION
R337.10 SHALL COMPLY ONLY WITH THE REQUIREMENTS OF THAT SECTION.
5.ADDITIONS TO AND REMODELS OF BUILDINGS ORIGINALLY CONSTRUCTED PRIOR TO JULY 1,
2008.
R337.1.3.1 APPLICATION DATE AND WHERE REQUIRED
NEW BUILDINGS FOR WHICH AN APPLICATION FOR A BUILDING PERMIT IS SUBMITTED ON OR AFTER
JULY 1, 2008, LOCATED IN ANY FIRE HAZARD SEVERITY ZONE OR WILDLAND INTERFACE FIRE AREA
SHALL COMPLY WITH ALL SECTIONS OF THIS CHAPTER, INCLUDING ALL OF THE FOLLOWING AREAS:
1.ALL UNINCORPORATED LANDS DESIGNATED BY THE STATE BOARD OF FORESTRY AND FIRE
PROTECTION AS STATE RESPONSIBILITY AR EA (SRA) INCLUDING:
1.MODERATE FIRE HAZARD SEVERITY ZONES
2.HIGH FIRE HAZARD SEVERITY ZONES
3.VERY-HIGH FIRE HAZARD SEVERITY ZONES
2.LAND DESIGNATED AS VERY-HIGH FIRE HAZARD SEVERITY ZONE BY CITIES AND OTHER LOCAL
AGENCIES.
3.LAND DESIGNATED AS WILDLAND INTERFACE FIRE AREA BY CITIES AND OTHER LOCAL
AGENCIES.
EXCEPTIONS:
1.NEW BUILDINGS LOCATED IN ANY FIRE HAZARD SEVERITY ZONE WITHIN STATE RESPONSIBILITY
AREAS, FOR WHICH AN APPLICATION FOR A BUILDING PERMIT IS SUBMITTED ON OR AFTER JANUARY 1,
2008, SHALL COMPLY WITH ALL SECTIONS OF THIS CHAPTER.
2.NEW BUILDINGS LOCATED IN ANY FIRE HAZARD SEVERITY ZONE WITHIN STATE RESPONSIBILITY
AREAS OR ANY WILDLAND INTERFACE FIRE AREA DESIGNATED BY CITIES AND OTHER LOCAL
AGENCIES FOR WHICH AN APPLICATION FOR A BUILDING PERMIT IS SUBMITTED ON OR AFTER
DECEMBER 1, 2005 BUT PRIOR TO JULY 1, 2008, SHALL ONLY COMPLY WITH THE FOLLOWING SECTIONS
OF THIS CHAPTER:
1.SECTION R337.5 - ROOFING
2.SECTION R337.6 - VENTS
R337.1.4 INSPECTION AND CERTIFICATION
BUILDING PERMIT APPLICATIONS AND FINAL COMPLETION APPROVALS FOR BUILDINGS WITHIN THE
SCOPE AND APPLICATION OF THIS CHAPTER SHALL COMPLY WITH THE FOLLOWING:
1.BUILDING PERMIT ISSUANCE. THE LOCAL BUILDING OFFICIAL SHALL, PRIOR TO CONSTRUCTION,
PROVIDE THE OWNER OR APPLICANT A CERTIFICATION THAT THE BUILDING AS PROPOSED TO BE
BUILT COMPLIES WITH ALL APPLICABLE STATE AND LOCAL BUILDING STANDARDS, INCLUDING THOSE
FOR MATERIALS AND CONSTRUCTION METHODS FOR WILDFIRE EXPOSURE AS DESCRIBED IN THIS
CHAPTER. ISSUANCE OF A BUILDING PERMIT BY THE LOCAL BUILDING OFFICIAL FOR THE PROPOSED
BUILDING SHALL BE CONSIDERED AS COMPLYING WITH THIS SECTION.
2.BUILDING PERMIT FINAL. THE LOCAL BUILDING OFFICIAL SHALL, UPON COMPLETION OF
CONSTRUCTION, PROVIDE THE OWNER OR APPLICANT WITH A COPY OF THE FINAL INSPECTION
REPORT THAT DEMONSTRATES THE BUILDING WAS CONSTRUCTED IN COMPLIANCE WITH ALL
APPLICABLE STATE AND LOCAL BUILDING STANDARDS, INCLUDING THOSE FOR MATERIALS AND
CONSTRUCTION METHODS FOR WILDFIRE EXPOSURE AS DESCRIBED IN THIS CHAPTER. ISSUANCE OF
A CERTIFICATE OF OCCUPANCY BY THE LOCAL BUILDING OFFICIAL FOR THE PROPOSED BUILDING
SHALL BE CONSIDERED AS COMPLYING WITH THIS SECTION.
R337.1.5 VEGETATION MANAGEMENT COMPLIANCE
PRIOR TO BUILDING PERMIT FINAL APPROVAL, THE PROPERTY SHALL BE IN COMPLIANCE WITH THE
VEGETATION MANAGEMENT REQUIREMENTS PRESCRIBED IN CALIFORNIA FIRE CODE SECTION 4906
AND 4907, INCLUDING CALIFORNIA PUBLIC RESOURCES CODE 4291 OR CALIFORNIA GOVERNMENT
CODE SECTION 51182. ACCEPTABLE METHODS OF COMPLIANCE INSPECTION AND DOCUMENTATION
SHALL BE DETERMINED BY THE ENFORCING AGENCY AND SHALL BE PERMITTED TO INCLUDE ANY OF
THE FOLLOWING:
1.LOCAL, STATE OR FEDERAL FIRE AUTHORITY OR DESIGNEE AUTHORIZED TO ENFORCE
VEGETATION MANAGEMENT REQUIREMENTS.
2.ENFORCING AGENCY.
3.THIRD PARTY INSPECTION AND CERTIFICATION AUTHORIZED TO ENFORCE VEGETATION
MANAGEMENT REQUIREMENTS.
4.PROPERTY OWNER CERTIFICATION AUTHORIZED BY THE ENFORCING AGENCY.
SECTION R337.2 DEFINITIONS
FOR THE PURPOSES OF SECTION R337, CERTAIN TERMS ARE DEFINED BELOW:
APPLICABLE BUILDING. A BUILDING THAT HAS RESIDENTIAL, COMMERCIAL, EDUCATIONAL,
INSTITUTIONAL OR SIMILAR OCCUPANCY TYPE USE.
DIRECTOR MEANS THE DIRECTOR OF THE CALIFORNIA DEPARTMENT OF FORESTRY AND FIRE
PROTECTION (CAL FIRE).
EXTERIOR COVERING. THE EXPOSED SIDING OR CLADDING MATERIAL APPLIED TO THE EXTERIOR
SIDE OF AN EXTERIOR WALL, ROOF EAVE SOFFIT, FLOOR PROJECTION OR EXPOSED UNDERFLOOR
FRAMING.
EXTERIOR WALL ASSEMBLY. A SYSTEM OR ASSEMBLY OF EXTERIOR WALL COMPONENTS, INCLUDING
EXTERIOR WALL COVERING MATERIALS, THAT PROVIDES PROTECTION OF THE BUILDING
STRUCTURAL MEMBERS, INCLUDING FRAMING AND SHEATHING MATERIALS, AND CONDITIONED
INTERIOR SPACE, FROM THE DETRIMENTAL EFFECTS OF THE EXTERIOR ENVIRONMENT.
EXTERIOR WALL COVERING. A MATERIAL OR ASSEMBLY OF MATERIALS APPLIED ON THE EXTERIOR
SIDE OF EXTERIOR WALLS FOR THE PURPOSE OF PROVIDING A WEATHER-RESISTING BARRIER,
INSULATION OR FOR AESTHETICS, INCLUDING BUT NOT LIMITED TO, VENEERS, SIDING, EXTERIOR
INSULATION AND FINISH SYSTEMS, ARCHITECTURAL TRIM AND EMBELLISHMENTS SUCH AS CORNICES,
SOFFITS, FACIAS, GUTTERS AND LEADERS.
FIRE PROTECTION PLAN. A DOCUMENT PREPARED FOR A SPECIFIC PROJECT OR DEVELOPMENT
PROPOSED FOR A WILDLAND-URBAN INTERFACE (WUI) FIRE AREA. IT DESCRIBES WAYS TO MINIMIZE
AND MITIGATE POTENTIAL FOR LOSS FROM WILDFIRE EXPOSURE. SEE THE CALIFORNIA FIRE CODE,
CHAPTER 49, FOR REQUIRED ELEMENTS OF A FIRE PROTECTION PLAN.
FIRE HAZARD SEVERITY ZONES. GEOGRAPHICAL AREAS DESIGNATED PURSUANT TO CALIFORNIA
PUBLIC RESOURCES CODES SECTIONS 4201 THROUGH 4204 AND CLASSIFIED AS VERY-HIGH, HIGH OR
MODERATE IN STATE RESPONSIBILITY AREAS OR AS LOCAL RESPONSIBILITY AREAS IN VERY-HIGH
FIRE HAZARD SEVERITY ZONES DESIGNATED PURSUANT TO CALIFORNIA GOVERNMENT CODE
SECTIONS 51175 THROUGH 51189. SEE CALIFORNIA FIRE CODE CHAPTER 49.
THE CALIFORNIA CODE OF REGULATIONS, TITLE 14, SECTION 1280 ENTITLES THE MAPS OF THESE
GEOGRAPHICAL AREAS AS "MAPS OF THE FIRE HAZARD SEVERITY ZONES IN THE STATE
RESPONSIBILITY AREA OF CALIFORNIA."
FIRE-RESISTANT VEGETATION. PLANTS, SHRUBS, TREES AND OTHER VEGETATION WHICH EXHIBIT
PROPERTIES, SUCH AS HIGH MOISTURE CONTENT, LITTLE ACCUMULATION OF DEAD VEGETATION,
AND LOW SAP OR RESIN CONTENT, THAT MAKE THEM LESS LIKELY TO IGNITE OR CONTRIBUTE HEAT
OR SPREAD FLAME IN A FIRE THAN NATIVE VEGETATION TYPICALLY FOUND IN THE REGION.
[NOTE: THE FOLLOWING SOURCES CONTAIN EXAMPLES OF TYPES OF VEGETATION THAT CAN BE
CONSIDERED AS FIRE-RESISTANT VEGETATION. (FIRE-RESISTANT PLANTS FOR HOME LANDSCAPES, A
PACIFIC NORTHWEST EXTENSION PUBLICATION; HOME LANDSCAPING FOR FIRE, UNIVERSITY OF
CALIFORNIA DIVISION OF AGRICULTURE AND NATURAL RESOURCES; SUNSET WESTERN GARDEN
BOOK)]
IGNITION-RESISTANT MATERIAL. A TYPE OF BUILDING MATERIAL THAT COMPLIES WITH THE
REQUIREMENTS IN SECTION R337.4.
LOCAL RESPONSIBILITY AREA (LRA). AREAS OF THE STATE IN WHICH THE FINANCIAL RESPONSIBILITY
OF PREVENTING AND SUPPRESSING FIRES IS THE PRIMARY RESPONSIBILITY OF A CITY, COUNTY, CITY
AND COUNTY, OR DISTRICT.
LOG WALL CONSTRUCTION. A TYPE OF CONSTRUCTION IN WHICH EXTERIOR WALLS ARE
CONSTRUCTED OF SOLID WOOD MEMBERS AND WHERE THE SMALLEST HORIZONTAL DIMENSION OF
EACH SOLID WOOD MEMBER IS AT LEAST 6 INCHES (152 MM).
RAFTER TAIL. THE PORTION OF ROOF RAFTER FRAMING IN A SLOPING ROOF ASSEMBLY THAT
PROJECTS BEYOND AND OVERHANGS AN EXTERIOR WALL.
ROOF EAVE. THE LOWER PORTION OF A SLOPING ROOF ASSEMBLY THAT PROJECTS BEYOND AND
OVERHANGS AN EXTERIOR WALL AT THE LOWER END OF THE RAFTER TAILS. ROOF EAVES MAY BE
EITHER "OPEN" OR "ENCLOSED." OPEN ROOF EAVES HAVE EXPOSED RAFTER TAILS AND AN
UNENCLOSED SPACE ON THE UNDERSIDE OF THE ROOF DECK. ENCLOSED ROOF EAVES HAVE A
BOXED-IN ROOF EAVE SOFFIT WITH A HORIZONTAL UNDERSIDE OR SLOPING RAFTER TAILS WITH AN
EXTERIOR COVERING APPLIED TO THE UNDERSIDE OF THE RAFTER TAILS.
ROOF EAVE SOFFIT. AN ENCLOSED BOXED-IN SOFFIT UNDER A ROOF EAVE WITH EXTERIOR
COVERING MATERIAL APPLIED TO THE SOFFIT FRAMING CREATING A HORIZONTAL SURFACE ON THE
EXPOSED UNDERSIDE.
STATE RESPONSIBILITY AREA (SRA). LANDS THAT ARE CLASSIFIED BY THE BOARD OF FORESTRY
PURSUANT TO PUBLIC RESOURCES CODE SECTION 4125 WHERE THE FINANCIAL RESPONSIBILITY OF
PREVENTING AND SUPPRESSING FOREST FIRES IS PRIMARILY THE RESPONSIBILITY OF THE STATE.
WILDFIRE. ANY UNCONTROLLED FIRE SPREADING THROUGH VEGETATIVE FUELS THAT THREATENS TO
DESTROY LIFE, PROPERTY OR RESOURCES AS DEFINED IN PUBLIC RESOURCES CODE SECTIONS 4103
AND 4104.
WILDFIRE EXPOSURE. ONE OR A COMBINATION OF RADIANT HEAT, CONVECTIVE HEAT, DIRECT FLAME
CONTACT AND BURNING EMBERS BEING PROJECTED BY VEGETATION FIRE TO A STRUCTURE AND ITS
IMMEDIATE ENVIRONMENT.
WILDLAND-URBAN INTERFACE (WUI). A GEOGRAPHICAL AREA IDENTIFIED BY THE STATE AS A "FIRE
HAZARD SEVERITY ZONE" IN ACCORDANCE WITH THE PUBLIC RESOURCES CODE SECTIONS 4201
THROUGH 4204 AND GOVERNMENT CODE SECTIONS 51175 THROUGH 51189, OR OTHER AREAS
DESIGNATED BY THE ENFORCING AGENCY TO BE AT A SIGNIFICANT RISK FROM WILDFIRES.
SECTION R337.3 STANDARDS OF QUALITY
R337.3.1 GENERAL
BUILDING MATERIAL, SYSTEMS, ASSEMBLIES AND METHODS OF CONSTRUCTION USED IN SECTION R337
SHALL BE IN ACCORDANCE WITH SECTION R337.3.
R337.3.2 QUALIFICATION BY TESTING
MATERIAL AND MATERIAL ASSEMBLIES TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
R337.3 SHALL BE ACCEPTED FOR USE WHEN THE RESULTS AND CONDITIONS OF THOSE TESTS ARE MET.
PRODUCT EVALUATION TESTING OF MATERIAL AND MATERIAL ASSEMBLIES SHALL BE APPROVED OR
LISTED BY THE STATE FIRE MARSHAL, OR IDENTIFIED IN A CURRENT REPORT ISSUED BY AN APPROVED
AGENCY.
R337.3.3 APPROVED AGENCY
PRODUCT EVALUATION TESTING SHALL BE PERFORMED BY AN APPROVED AGENCY AS DEFINED IN
SECTION 1702 OF THE CALIFORNIA BUILDING CODE. THE SCOPE OF ACCREDITATION FOR THE APPROVED
AGENCY SHALL INCLUDE BUILDING PRODUCT COMPLIANCE WITH THE CALIFORNIA BUILDING CODE.
R337.3.4 LABELING
MATERIAL AND MATERIAL ASSEMBLIES TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
R337.3 SHALL BEAR AN IDENTIFICATION LABEL SHOWING THE FIRE TEST RESULTS. THAT IDENTIFICATION
LABEL SHALL BE ISSUED BY A TESTING AND/OR INSPECTING AGENCY APPROVED BY THE STATE FIRE
MARSHAL.
1.IDENTIFICATION MARK OF THE APPROVED TESTING AND/OR INSPECTING AGENCY.
2.CONTACT AND IDENTIFICATION INFORMATION OF THE MANUFACTURER.
3.MODEL NUMBER OR IDENTIFICATION OF THE PRODUCT OR MATERIAL.
4.PRE-TEST WEATHERING SPECIFIED IN THIS SECTION.
5.COMPLIANCE STANDARD AS DESCRIBED UNDER SECTION R337.3.7.
R337.3.5 WEATHERING AND SURFACE TREATMENT PROTECTION
R337.3.5.1 GENERAL
MATERIAL AND MATERIAL ASSEMBLIES TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
R337.3 SHALL MAINTAIN THEIR FIRE TEST PERFORMANCE UNDER CONDITIONS OF USE WHEN INSTALLED IN
ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS.
R337.3.5.2 WEATHERING
FIRE-RETARDANT-TREATED WOOD AND FIRE-RETARDANT-TREATED WOOD SHINGLES AND SHAKES SHALL
MEET THE FIRE TEST PERFORMANCE REQUIREMENTS OF THIS SECTION AFTER BEING SUBJECTED TO THE
WEATHERING CONDITIONS CONTAINED IN THE FOLLOWING STANDARDS, AS APPLICABLE TO THE
MATERIALS AND THE CONDITIONS OF USE.
R337.3.5.2.1 FIRE-RETARDANT-TREATED WOOD
FIRERETARDANT-TREATED WOOD SHALL BE TESTED IN ACCORDANCE WITH ASTM D2898 (METHOD A), AND
THE REQUIREMENTS OF SECTION 2303.2 OF THE CALIFORNIA BUILDING CODE.
R337.3.5.2.2 FIRE-RETARDANT-TREATED WOOD SHINGLES AND SHAKES
FIRE-RETARDANT-TREATED WOOD SHINGLES AND SHAKES SHALL BE APPROVED AND LISTED BY THE
STATE FIRE MARSHAL IN ACCORDANCE WITH SECTION 208(C), TITLE 19 CALIFORNIA CODE OF
REGULATIONS.
R337.3.5.3 SURFACE TREATMENT PROTECTION
THE USE OF PAINTS, COATINGS, STAINS OR OTHER SURFACE TREATMENTS ARE NOT AN APPROVED
METHOD OF PROTECTION AS REQUIRED IN THIS SECTION.
R337.3.6 ALTERNATES FOR MATERIALS, DESIGN, TESTS AND METHODS OF CONSTRUCTION
THE ENFORCING AGENCY IS PERMITTED TO MODIFY THE PROVISIONS OF THIS CHAPTER FOR
SITE-SPECIFIC CONDITIONS IN ACCORDANCE WITH SECTION 1.11.2.4. WHEN REQUIRED BY THE ENFORCING
AGENCY FOR THE PURPOSES OF GRANTING MODIFICATIONS, A FIRE PROTECTION PLAN SHALL BE
SUBMITTED IN ACCORDANCE WITH THE CALIFORNIA FIRE CODE, CHAPTER 49.
R337.3.7 STANDARDS OF QUALIT
THE STATE FIRE MARSHAL STANDARDS FOR EXTERIOR WILDFIRE EXPOSURE PROTECTION LISTED BELOW
AND AS REFERENCED IN THIS CHAPTER ARE LOCATED IN THE CALIFORNIA REFERENCED STANDARDS
CODE, PART 12 AND CHAPTER 44 OF THIS CODE.SFM STANDARD 12-7A-1, EXTERIOR WALL SIDING AND
SHEATHING. A FIRE RESISTANCE TEST STANDARD CONSISTING OF A 150 KW INTENSITY DIRECT FLAME
EXPOSURE FOR A 10 MINUTES DURATION. SFM STANDARD 12-7A-2, EXTERIOR WINDOWS. A FIRE
RESISTANCE TEST STANDARD CONSISTING OF A 150 KW INTENSITY DIRECT FLAME EXPOSURE FOR AN
8-MINUTE DURATION. SFM STANDARD 12-7A-3, HORIZONTAL PROJECTION UNDERSIDE A FIRE RESISTANCE
TEST STANDARD CONSISTING OF A 300 KW INTENSITY DIRECT FLAME EXPOSURE FOR A 10 MINUTE
DURATION. SFM STANDARD 12-7A-4, DECKING. A TWO-PART TEST CONSISTING OF A HEAT RELEASE RATE
(PART A) DECK ASSEMBLY COMBUSTION TEST WITH AN UNDER DECK EXPOSURE OF 80 KW INTENSITY
DIRECT FLAME FOR A 3 MINUTE DURATION, AND A (PART B) SUSTAINED DECK ASSEMBLY COMBUSTION
TEST CONSISTING OF A DECK UPPER SURFACE BURNING EMBER EXPOSURE WITH A 12 MPH WIND FOR 40
MINUTES USING A 2.2 LB (1 KG) BURNING "CLASS A" SIZE 12" × 12" × 2.25" (300 MM X 300 MM X 57 MM) ROOF
TEST BRAND.
SFM STANDARD 12-7A-4A, DECKING ALTERNATE METHOD A. A HEAT RELEASE RATE DECK ASSEMBLY
COMBUSTION TEST WITH AN UNDER DECK EXPOSURE OF 80 KW INTENSITY DIRECT FLAME FOR A 3 MINUTE
DURATION. ASTM D2898, STANDARD PRACTICE FOR ACCELERATED WEATHERING OF
FIRE-RETARDANT-TREATED WOOD FOR FIRE TESTING. ASTM D3909/D3909M, STANDARD SPECIFICATION
FOR ASPHALT ROLL ROOFING (GLASS FELT) SURFACED WITH MINERAL GRANULES. ASTM E84, STANDARD
TEST METHOD FOR SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS. ASTM E119,
STANDARD TEST METHODS FOR FIRE TESTS OF BUILDING CONSTRUCTION AND MATERIALS. ASTM
E2632/E2632M, STANDARD TEST METHOD FOR EVALUATING THE UNDER-DECK FIRE TEST RESPONSE OF
DECK MATERIALS. ASTM E2707, STANDARD TEST METHOD FOR DETERMINING FIRE PENETRATION OF
EXTERIOR WALL ASSEMBLIES USING A DIRECT FLAME IMPINGEMENT EXPOSURE. ASTM E2726/E2726M,
STANDARD TEST METHOD FOR EVALUATING THE FIRE-TEST-RESPONSE OF DECK STRUCTURES TO
BURNING BRANDS. ASTM E2768 STANDARD TEST METHOD FOR EXTENDED DURATION SURFACE BURNING
CHARACTERISTICS OF BUILDING MATERIALS (30-MINUTE TUNNEL TEST). ASTM E2886/E2886M, STANDARD
TEST METHOD FOR EVALUATING THE ABILITY OF EXTERIOR VENTS TO RESIST THE ENTRY OF EMBERS AND
DIRECT FLAME IMPINGEMENT. ASTM E2957, STANDARD TEST METHOD FOR RESISTANCE TO WILDFIRE
PENETRATION OF EAVES, SOFFITS AND OTHER PROJECTIONS. NFPA 257, STANDARD ON FIRE TEST FOR
WINDOW AND GLASS BLOCK ASSEMBLIES. UL 263, STANDARD FOR FIRE TESTS OF BUILDING
CONSTRUCTION AND MATERIALS. UL 723, STANDARD FOR TEST FOR SURFACE BURNING
CHARACTERISTICS OF BUILDING MATERIALS
SECTION R337.4 IGNITION-RESISTANT CONSTRUCTION
R337.4.1 GENERAL
THE MATERIALS PRESCRIBED HEREIN FOR IGNITION RESISTANCE SHALL CONFORM TO THE
REQUIREMENTS OF SECTION R337.
R337.4.2 IGNITION-RESISTANT MATERIALS
IGNITION-RESISTANT MATERIALS SHALL COMPLY WITH ONE OF THE FOLLOWING:
1.THE REQUIREMENTS IN SECTION R337.4.3 OR
2.ONE OF THE ALTERNATIVE METHODS IN SECTION R337.4.4.
R337.4.3 CONDITIONS OF ACCEPTANCE FOR IGNITION-RESISTANT MATERIALS
THE MATERIAL SHALL COMPLY WITH THE CONDITIONS OF ACCEPTANCE IN ITEMS 1 AND 2 BELOW OR WITH
THE CONDITIONS OF ACCEPTANCE OF ASTM E2768.
1.THE MATERIAL SHALL EXHIBIT A LISTED FLAME SPREAD INDEX NOT EXCEEDING 25 WHEN TESTED IN
ACCORDANCE WITH ASTM E84 OR UL 723.
2.ADDITIONALLY, THE ASTM E84 OR UL 723 TEST SHALL BE CONTINUED FOR AN ADDITIONAL 20-MINUTE
PERIOD, AND THE MATERIAL SHALL EXHIBIT A FLAME FRONT THAT DOES NOT PROGRESS MORE THAN 1012FEET (3200 MM) BEYOND THE CENTERLINE OF THE BURNER AT ANY TIME DURING THE TEST PERIOD.
R337.4.3.1 FIRE TESTING OF WOOD STRUCTURAL PANELS
WOOD STRUCTURAL PANELS SHALL BE TESTED WITH A RIPPED OR CUT LONGITUDINAL GAP OF 18 INCH (3.2
MM).
R337.4.4 ALTERNATIVE METHODS FOR DETERMINING IGNITIONRESISTANT MATERIAL
ANY ONE OF THE FOLLOWING SHALL BE ACCEPTED AS MEETING THE DEFINITION OF IGNITION-RESISTANT
MATERIAL:
1.NONCOMBUSTIBLE MATERIAL. MATERIAL THAT COMPLIES WITH THE DEFINITION FOR
NONCOMBUSTIBLE MATERIALS IN SECTION R202.
2.FIRE-RETARDANT-TREATED WOOD. FIRE-RETARDANT-TREATED WOOD IDENTIFIED FOR EXTERIOR
USE THAT COMPLIES WITH THE REQUIREMENTS OF SECTION 2303.2 OF THE CALIFORNIA BUILDING CODE.
3.FIRE-RETARDANT-TREATED WOOD SHINGLES AND SHAKES. FIRE-RETARDANT-TREATED WOOD
SHINGLES AND SHAKES, AS DEFINED IN SECTION 1505.6 OF THE CALIFORNIA BUILDING CODE AND LISTED
BY STATE FIRE MARSHAL FOR USE AS "CLASS B" ROOF COVERING, SHALL BE ACCEPTED AS AN
IGNITION-RESISTANT WALL COVERING MATERIAL WHEN INSTALLED OVER SOLID SHEATHING.
SECTION R337.5 ROOFING
R337.5.1 GENERAL
ROOFS SHALL COMPLY WITH THE REQUIREMENTS OF SECTIONS R337 AND R902. ROOFS SHALL HAVE A
ROOFING ASSEMBLY INSTALLED IN ACCORDANCE WITH ITS LISTING AND THE MANUFACTURER'S
INSTALLATION INSTRUCTIONS. ROOF ASSEMBLIES IN THE FIRE HAZARD SEVERITY ZONES SHALL BE CLASS
A RATING WHEN TESTED IN ACCORDANCE WITH ASTM E108 OR UL790.
R337.5.2 ROOF COVERINGS
WHERE THE ROOFING PROFILE HAS AN AIRSPACE UNDER THE ROOF COVERING, INSTALLED OVER A
COMBUSTIBLE DECK, A 72 LB. (32.7KG) CAP SHEET COMPLYING WITH ASTM D3909 STANDARD
SPECIFICATION FOR "ASPHALT ROLLED ROOFING (GLASS FELT) SURFACED WITH MINERAL GRANULES,"
SHALL BE INSTALLED OVER THE ROOF DECK. BIRD STOPS SHALL BE USED AT THE EAVES WHEN THE
PROFILE FITS, TO PREVENT DEBRIS AT THE EAVE. HIP AND RIDGE CAPS SHALL BE MUDDED IN TO PREVENT
INTRUSION OF FIRE OR EMBERS.
EXCEPTION: CAP SHEET IS NOT REQUIRED WHEN NO LESS THAN 1 INCH OF MINERAL WOOL BOARD OR
OTHER NONCOMBUSTIBLE MATERIAL IS LOCATED BETWEEN THE ROOFING MATERIAL AND WOOD FRAMING
OR DECK.
ALTERNATELY, A CLASS A FIRE RATED ROOF UNDERLAYMENT, TESTED IN ACCORDANCE WITH ASTM E108,
SHALL BE PERMITTED TO BE USED. IF THE SHEATHING CONSISTS OF EXTERIOR FIRERETARDANT-TREATED
WOOD, THE UNDERLAYMENT SHALL NOT BE REQUIRED TO COMPLY WITH A CLASS A CLASSIFICATION. BIRD
STOPS SHALL BE USED AT THE EAVES WHEN THE PROFILE FITS, TO PREVENT DEBRIS AT THE EAVE. HIP
AND RIDGE CAPS SHALL BE MUDDED IN TO PREVENT INTRUSION OF FIRE OR EMBERS.
R337.5.3 ROOF VALLEYS
WHERE VALLEY FLASHING IS INSTALLED, THE FLASHING SHALL BE NOT LESS THAN 0.019-INCH (0.48 MM)
NO. 26 GAGE GALVANIZED SHEET CORROSIONRESISTANT METAL INSTALLED OVER NOT LESS THAN ONE
LAYER OF MINIMUM 72-POUND (32.4 KG) MINERAL-SURFACED NONPERFORATED CAP SHEET COMPLYING
WITH ASTM D3909, AT LEAST 36-INCH-WIDE (914 MM) RUNNING THE FULL LENGTH OF THE VALLEY.
R337.5.4 ROOF GUTTERS
ROOF GUTTERS SHALL BE PROVIDED WITH THE MEANS TO PREVENT THE ACCUMULATION OF LEAVES AND
DEBRIS IN THE GUTTER.
SECTION R337.6 VENTS
R337.6.1 GENERAL
WHERE PROVIDED, VENTILATION OPENINGS FOR ENCLOSED ATTICS, GABLE ENDS, RIDGE ENDS, UNDER
EAVES AND CORNICES, ENCLOSED EAVE SOFFIT SPACES, ENCLOSED RAFTER SPACES FORMED WHERE
CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF RAFTERS, UNDERFLOOR VENTILATION,
FOUNDATIONS AND CRAWL SPACES, OR ANY OTHER OPENING INTENDED TO PERMIT VENTILATION, EITHER
IN A HORIZONTAL OR VERTICAL PLANE, SHALL BE IN ACCORDANCE WITH SECTION 1202 OF THE
CALIFORNIA BUILDING CODE AND SECTIONS R337.6.1 THROUGH R337.6.2 TO RESIST BUILDING IGNITION
FROM THE INTRUSION OF BURNING EMBERS AND FLAME THROUGH THE VENTILATION OPENINGS.
R337.6.2 REQUIREMENTS
VENTILATION OPENINGS SHALL BE FULLY COVERED WITH WILDFIRE FLAME AND EMBER RESISTANT VENTS
APPROVED AND LISTED BY THE CALIFORNIA STATE FIRE MARSHAL, OR WUI VENTS TESTED TO ASTM E2886
AND LISTED, BY COMPLYING WITH ALL OF THE FOLLOWING REQUIREMENTS:
1.THERE SHALL BE NO FLAMING IGNITION OF THE COTTON MATERIAL DURING THE EMBER INTRUSION
TEST.
2.THERE SHALL BE NO FLAMING IGNITION DURING THE INTEGRITY TEST PORTION OF THE FLAME
INTRUSION TEST.
3.THE MAXIMUM TEMPERATURE OF THE UNEXPOSED SIDE OF THE VENT SHALL NOT EXCEED 662°F
(350°C).
R337.6.2.1 OFF RIDGE AND RIDGE VENTS
VENTS THAT ARE INSTALLED ON A SLOPED ROOF, SUCH AS DORMER VENTS, SHALL COMPLY WITH ALL THE
FOLLOWING:
1.VENTS SHALL BE COVERED WITH A MESH WHERE THE DIMENSIONS OF THE MESH THEREIN SHALL BE
A MINIMUM OF 116 INCH (1.6 MM) AND SHALL NOT EXCEED 18 INCH (3.2 MM) IN DIAMETER.
2.THE MESH MATERIAL SHALL BE NONCOMBUSTIBLE.
3.THE MESH MATERIAL SHALL BE CORROSION RESISTANT.
SECTION R337.7 EXTERIOR COVERING
R337.7.1 SCOPE
THE PROVISIONS OF THIS SECTION SHALL GOVERN THE MATERIALS AND CONSTRUCTION METHODS USED
TO RESIST BUILDING IGNITION AND/OR SAFEGUARD AGAINST THE INTRUSION OF FLAMES RESULTING
FROM SMALL EMBER AND SHORT-TERM DIRECT FLAME CONTACT EXPOSURE.
R337.7.2 GENERAL
THE FOLLOWING EXTERIOR COVERING MATERIALS AND/OR ASSEMBLIES SHALL COMPLY WITH THIS
SECTION:
1.EXTERIOR WALL COVERINGS.
2.EXTERIOR WALL ASSEMBLIES.
3.EXTERIOR EXPOSED UNDERSIDE OF ROOF EAVE OVERHANGS.
4.EXTERIOR EXPOSED UNDERSIDE OF ROOF EAVE SOFFITS.
5.EXPOSED UNDERSIDE OF EXTERIOR PORCH CEILINGS.
6.EXTERIOR EXPOSED UNDERSIDE OF FLOOR PROJECTIONS.
7.EXTERIOR UNDERFLOOR AREAS.
EXCEPTIONS TO SECTION R337.7.2:
1.EXTERIOR WALL ARCHITECTURAL TRIM, EMBELLISHMENTS, FASCIAS AND GUTTERS.
2.ROOF OR WALL TOP CORNICE PROJECTIONS AND SIMILAR ASSEMBLIES.
3.DECK WALKING SURFACES SHALL COMPLY WITH SECTION R337.9 ONLY.
R337.7.3 EXTERIOR WALL COVERINGS
THE EXTERIOR WALL COVERING SHALL COMPLY WITH ONE OR MORE OF THE FOLLOWING REQUIREMENTS,
EXCEPT AS PERMITTED FOR EXTERIOR WALL ASSEMBLIES COMPLYING WITH SECTION R337.7.4:
1.NONCOMBUSTIBLE MATERIAL.
2.IGNITION-RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION R337.4.2.
3.FIRE-RETARDANT-TREATED WOOD. THE FIRE-RETARDANT-TREATED WOOD SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 OF THE CALIFORNIA BUILDING
CODE.
R337.7.3.1 EXTENT OF EXTERIOR WALL COVERING
EXTERIOR WALL COVERINGS SHALL EXTEND FROM THE TOP OF THE FOUNDATION TO THE ROOF, AND
TERMINATE AT 2 INCH (50.8 MM) NOMINAL SOLID WOOD BLOCKING BETWEEN RAFTERS AT ALL ROOF
OVERHANGS, OR IN THE CASE OF ENCLOSED EAVES, TERMINATE AT THE ENCLOSURE.
R337.7.4 EXTERIOR WALL ASSEMBLIES
EXTERIOR WALL ASSEMBLIES OF BUILDINGS OR STRUCTURES SHALL BE CONSTRUCTED USING ONE OR
MORE OF THE FOLLOWING METHODS, UNLESS THEY ARE COVERED BY AN EXTERIOR WALL COVERING
COMPLYING WITH SECTION R337.7.3:
1.ASSEMBLY OF SAWN LUMBER OR GLUE-LAMINATED WOOD WITH THE SMALLEST MINIMUM NOMINAL
DIMENSION OF 4 INCHES (102 MM). SAWN OR GLUE-LAMINATED PLANKS SPLINED, TONGUE-AND-GROVE, OR
SET CLOSE TOGETHER AND WELL SPIKED.
2.LOG WALL CONSTRUCTION ASSEMBLY.
3.ASSEMBLY THAT HAS BEEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES FOR A
10-MINUTE DIRECT FLAME CONTACT EXPOSURE TEST SET FORTH IN ASTM E2707 WITH THE CONDITIONS
OF ACCEPTANCE SHOWN IN SECTION R337.7.4.1.
4.ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN ACCORDANCE WITH THE TEST
PROCEDURES FOR A 10-MINUTE DIRECT FLAME CONTACT EXPOSURE TEST SET FORTH IN SFM STANDARD
12-7A-1.
5.ASSEMBLY SUITABLE FOR EXTERIOR FIRE EXPOSURE WITH A 1-HOUR FIRE-RESISTANCE RATING,
RATED FROM THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263.
6.ASSEMBLY SUITABLE FOR EXTERIOR FIRE EXPOSURE CONTAINING ONE LAYER OF 58-INCH (16 MM)
TYPE X GYPSUM SHEATHING APPLIED BEHIND THE EXTERIOR WALL COVERING OR CLADDING ON THE
EXTERIOR SIDE OF THE FRAMING.
7.ASSEMBLY SUITABLE FOR EXTERIOR FIRE EXPOSURE CONTAINING ANY OF THE GYPSUM PANEL AND
SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN MANUAL AS
COMPLYING WITH A 1-HOUR FIRE-RESISTANCE RATING, AS TESTED IN ACCORDANCE WITH ASTM E119 OR
UL 263.
R337.7.4.1 CONDITIONS OF ACCEPTANCE WHEN TESTED IN ACCORDANCE WITH ASTM E2707
THE ASTM E2707 TEST SHALL BE CONDUCTED ON A MINIMUM OF THREE TEST SPECIMENS, AND THE
CONDITIONS OF ACCEPTANCE IN ITEMS 1 AND 2 BELOW SHALL BE MET. IF ANY ONE OF THE THREE TESTS
DO NOT MEET THE CONDITIONS OF ACCEPTANCE, THREE ADDITIONAL TESTS SHALL BE RUN. ALL THE
ADDITIONAL TESTS SHALL MEET THE CONDITIONS OF ACCEPTANCE.
1.ABSENCE OF FLAME PENETRATION THROUGH THE WALL ASSEMBLY AT ANY TIME.
2.ABSENCE OF EVIDENCE OF GLOWING COMBUSTION ON THE INTERIOR SURFACE OF THE ASSEMBLY
AT THE END OF THE 70-MINUTE TEST.
R337.7.5 OPEN ROOF EAVES
THE EXPOSED ROOF DECK ON THE UNDERSIDE OF UNENCLOSED ROOF EAVES SHALL CONSIST OF ONE OR
MORE OF THE FOLLOWING:
1.NONCOMBUSTIBLE MATERIAL.
2.IGNITION-RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 704A.2.
3.FIRE-RETARDANT-TREATED WOOD. THE FIRE-RETARDANTTREATED WOOD SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 OF THE CALIFORNIA BUILDING
CODE.
4.MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON
THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263.
5.ONE LAYER OF 58-INCH (16 MM) TYPE X GYPSUM SHEATHING APPLIED BEHIND AN EXTERIOR
COVERING ON THE UNDERSIDE OF THE ROOF DECK.
6.THE EXTERIOR PORTION OF A 1-HOUR FIRE-RESISTANCE-RATED EXTERIOR ASSEMBLY, AS TESTED IN
ACCORDANCE WITH ASTM E119 OR UL 263, APPLIED TO THE UNDERSIDE OF THE ROOF DECK DESIGNED
FOR EXTERIOR FIRE EXPOSURE, INCLUDING ASSEMBLIES USING THE GYPSUM PANEL AND SHEATHING
PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN MANUAL.
EXCEPTION TO SECTION R337.7.5: THE FOLLOWING MATERIALS DO NOT REQUIRE PROTECTION:
FASCIA AND OTHER ARCHITECTURAL TRIM BOARDS.
R337.7.6 ENCLOSED ROOF EAVES AND ROOF EAVE SOFFITS
THE EXPOSED UNDERSIDE OF ENCLOSED ROOF EAVES HAVING EITHER A BOXED-IN ROOF EAVE SOFFIT
WITH A HORIZONTAL UNDERSIDE, OR SLOPING RAFTER TAILS WITH AN EXTERIOR COVERING APPLIED TO
THE UNDERSIDE OF THE RAFTER TAILS, SHALL BE PROTECTED BY ONE OR MORE OF THE FOLLOWING:
1.NONCOMBUSTIBLE MATERIAL.
2.IGNITION-RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION R337.4.2.
3.FIRE-RETARDANT-TREATED WOOD. THE FIRE-RETARDANT-TREATED WOOD SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 OF THE CALIFORNIA BUILDING
CODE.
4.MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRERESISTANCE-RATED CONSTRUCTION ON
THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263.
5.ONE LAYER OF 58-INCH (16 MM) TYPE X GYPSUM SHEATHING APPLIED BEHIND THE EXTERIOR
COVERING OR CLADDING ON THE UNDERSIDE OF THE RAFTER TAILS OR SOFFIT.
6.THE EXTERIOR PORTION OF A 1-HOUR FIRE RESISTIVE EXTERIOR ASSEMBLY APPLIED TO THE
UNDERSIDE OF THE RAFTER TAILS OR SOFFIT, INCLUDING ASSEMBLIES USING THE GYPSUM PANEL AND
SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN MANUAL.
7.BOXED-IN ROOF EAVE SOFFIT ASSEMBLIES WITH A HORIZONTAL UNDERSIDE THAT MEET THE
PERFORMANCE CRITERIA IN SECTION R337.7.11 WHEN TESTED IN ACCORDANCE WITH THE TEST
PROCEDURES SET FORTH IN ASTM E2957.
8.BOXED-IN ROOF EAVE SOFFIT ASSEMBLIES WITH A HORIZONTAL UNDERSIDE THAT MEET THE
PERFORMANCE CRITERIA IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN SFM STANDARD
12-7A-3.
EXCEPTION TO SECTION R337.7.6: THE FOLLOWING MATERIALS DO NOT REQUIRE PROTECTION:
FASCIA AND OTHER ARCHITECTURAL TRIM BOARDS.
R337.7.7 EXTERIOR PORCH CEILINGS
THE EXPOSED UNDERSIDE OF EXTERIOR PORCH CEILINGS SHALL BE PROTECTED BY ONE OR MORE OF
THE FOLLOWING:
1.NONCOMBUSTIBLE MATERIAL.
2.IGNITION-RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION R337.4.2.
3.FIRE-RETARDANT-TREATED WOOD. THE FIRE-RETARDANT-TREATED WOOD SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 OF THE CALIFORNIA BUILDING
CODE.
4.MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON
THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263.
5.ONE LAYER OF 58-INCH (16 MM) TYPE X GYPSUM SHEATHING APPLIED BEHIND THE EXTERIOR
COVERING ON THE UNDERSIDE OF THE CEILING.
6.THE EXTERIOR PORTION OF A 1-HOUR FIRE-RESISTANCE-RATED EXTERIOR ASSEMBLY, AS TESTED IN
ACCORDANCE WITH ASTM E119, APPLIED TO THE UNDERSIDE OF THE CEILING ASSEMBLY, INCLUDING
ASSEMBLIES USING THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM
ASSOCIATION FIRE RESISTANCE DESIGN MANUAL
7.PORCH CEILING ASSEMBLIES WITH A HORIZONTAL UNDERSIDE THAT MEET THE PERFORMANCE
CRITERIA IN SECTION R337.7.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH
IN ASTM E2957.
8.PORCH CEILING ASSEMBLIES WITH A HORIZONTAL UNDERSIDE THAT MEET THE PERFORMANCE
CRITERIA IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN SFM STANDARD 12-7A-3.
EXCEPTION TO SECTION R337.7.7: ARCHITECTURAL TRIM BOARDS DO NOT REQUIRE PROTECTION.
R337.7.8 FLOOR PROJECTIONS
THE EXPOSED UNDERSIDE OF A CANTILEVERED FLOOR PROJECTION WHERE A FLOOR ASSEMBLY
EXTENDS OVER AN EXTERIOR WALL SHALL BE PROTECTED BY ONE OR MORE OF THE FOLLOWING:
1.NONCOMBUSTIBLE MATERIAL.
2.IGNITION-RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION R337.4.2.
3.FIRE-RETARDANT-TREATED WOOD. THE FIRE-RETARDANT-TREATED WOOD SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 OF THE CALIFORNIA BUILDING
CODE.
4.MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRERESISTANCE-RATED CONSTRUCTION ON
THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263.
5.ONE LAYER OF 58-INCH (16 MM) TYPE X GYPSUM SHEATHING APPLIED BEHIND AN EXTERIOR
COVERING ON THE UNDERSIDE OF THE FLOOR PROJECTION.
6.THE EXTERIOR PORTION OF A 1-HOUR FIRE-RESISTANCERATED EXTERIOR ASSEMBLY, AS TESTED IN
ACCORDANCE WITH ASTM E119 OR UL 263, APPLIED TO THE UNDERSIDE OF THE FLOOR PROJECTION,
INCLUDING ASSEMBLIES USING THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM
ASSOCIATION FIRE RESISTANCE DESIGN MANUAL.
7.THE UNDERSIDE OF A FLOOR ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN SECTION
R337.7.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN ASTM E2957.
8.THE UNDERSIDE OF A FLOOR ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN
ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN SFM STANDARD 12-7A-3.
EXCEPTION TO SECTION R337.7.8: ARCHITECTURAL TRIM BOARDS DO NOT REQUIRE PROTECTION.
R337.7.9 UNDERFLOOR PROTECTION
THE UNDERFLOOR AREA OF ELEVATED OR OVERHANGING BUILDINGS SHALL BE ENCLOSED TO GRADE IN
ACCORDANCE WITH THE REQUIREMENTS OF THIS CHAPTER OR THE UNDERSIDE OF THE EXPOSED
UNDERFLOOR SHALL BE PROTECTED BY ONE OR MORE OF THE FOLLOWING:
1.NONCOMBUSTIBLE MATERIAL.
2.IGNITION-RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION R337.4.2.
3.FIRE-RETARDANT-TREATED WOOD. THE FIRE-RETARDANTTREATED WOOD SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 OF THE CALIFORNIA BUILDING
CODE.
4.MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRERESISTANCE-RATED CONSTRUCTION ON
THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263.
5.ONE LAYER OF 58-INCH (16 MM) TYPE X GYPSUM SHEATHING APPLIED BEHIND AN EXTERIOR
COVERING ON THE UNDERSIDE OF THE FLOOR PROJECTION.
6.THE EXTERIOR PORTION OF A 1-HOUR FIRE-RESISTANCERATED EXTERIOR ASSEMBLY, AS TESTED IN
ACCORDANCE WITH ASTM E119 OR UL 263, APPLIED TO THE UNDERSIDE OF THE FLOOR, INCLUDING
ASSEMBLIES USING THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM
ASSOCIATION FIRE RESISTANCE DESIGN MANUAL.
7.THE UNDERSIDE OF A FLOOR ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN SECTION
R337.7.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN ASTM E2957.
8.THE UNDERSIDE OF A FLOOR ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN
ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN SFM STANDARD 12-7A-3.
EXCEPTION TO SECTION R337.7.9: STRUCTURAL COLUMNS AND BEAMS DO NOT REQUIRE PROTECTION
WHEN THEY ARE CONSTRUCTED WITH SAWN LUMBER OR GLUE LAMINATED WOOD WITH THE SMALLEST
MINIMUM NOMINAL DIMENSION OF 4 INCHES (102 MM). SAWN OR GLUE-LAMINATED PLANKS SHALL BE
SPLINED, TONGUE-AND-GROVE, OR SET CLOSE TOGETHER AND WELL SPIKED.
R337.7.10 UNDERSIDE OF APPENDAGES
WHEN REQUIRED BY THE ENFORCING AGENCY THE UNDERSIDE OF OVERHANGING APPENDAGES SHALL BE
ENCLOSED TO GRADE IN ACCORDANCE WITH THE REQUIREMENTS OF THIS CHAPTER OR THE UNDERSIDE
OF THE EXPOSED UNDERFLOOR SHALL BE PROTECTED BY ONE OR MORE OF THE FOLLOWING:
1.NONCOMBUSTIBLE MATERIAL.
2.IGNITION-RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION R337.7.2.
3.FIRE-RETARDANT-TREATED WOOD. THE FIRE-RETARDANT-TREATED WOOD SHALL BE LABELED FOR
EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 OF THE CALIFORNIA BUILDING
CODE.
4.MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON
THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263.
5.ONE LAYER OF 58-INCH (16 MM) TYPE X GYPSUM SHEATHING APPLIED BEHIND AN EXTERIOR
COVERING ON THE UNDERSIDE OF THE APPENDAGE PROJECTION.
6.THE EXTERIOR PORTION OF A 1-HOUR FIRE-RESISTANCERATED EXTERIOR ASSEMBLY, AS TESTED IN
ACCORDANCE WITH ASTM E119 OR UL 263, APPLIED TO THE UNDERSIDE OF THE APPENDAGE, INCLUDING
ASSEMBLIES USING THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM
ASSOCIATION FIRE RESISTANCE DESIGN MANUAL.
7.THE UNDERSIDE OF AN APPENDAGE ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN
SECTION R337.7.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN ASTM
E2957.
8.THE UNDERSIDE OF AN APPENDAGE ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN
ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN SFM STANDARD 12-7A-3.
EXCEPTION TO SECTION R337.7.10: STRUCTURAL COLUMNS AND BEAMS DO NOT REQUIRE PROTECTION
WHEN THEY ARE CONSTRUCTED WITH SAWN LUMBER OR GLUE-LAMINATED WOOD WITH THE SMALLEST
MINIMUM NOMINAL DIMENSION OF 4 INCHES (102 MM). SAWN OR GLUE-LAMINATED PLANKS SHALL BE
SPLINED, TONGUE-AND-GROVE, OR SET CLOSE TOGETHER AND WELL SPIKED.
R337.7.11 CONDITIONS OF ACCEPTANCE WHEN TESTED IN ACCORDANCE WITH ASTM E2957
THE TEST SHALL BE CONDUCTED ON A MINIMUM OF THREE TEST SPECIMENS AND THE CONDITIONS OF
ACCEPTANCE IN 1 THROUGH 3 BELOW SHALL BE MET. IF ANY ONE OF THE THREE TESTS DOES NOT MEET
THE CONDITIONS OF ACCEPTANCE, THREE ADDITIONAL TESTS SHALL BE RUN. ALL OF THE ADDITIONAL
TESTS SHALL MEET THE CONDITIONS OF ACCEPTANCE.
1.ABSENCE OF FLAME PENETRATION OF THE EAVES OR HORIZONTAL PROJECTION ASSEMBLY AT ANY
TIME.
2.ABSENCE OF STRUCTURAL FAILURE OF THE EAVES OR HORIZONTAL PROJECTION SUBASSEMBLY AT
ANY TIME.
3.ABSENCE OF SUSTAINED COMBUSTION OF ANY KIND AT THE CONCLUSION OF THE 40-MINUTE TEST.
SECTION R337.8 EXTERIOR WINDOWS, SKYLIGHTS AND DOORS
R337.8.1 GENERAL
R337.8.2 EXTERIOR GLAZING
THE FOLLOWING EXTERIOR GLAZING MATERIALS AND/OR ASSEMBLIES SHALL COMPLY WITH THIS SECTION:
1.EXTERIOR WINDOWS.
2.EXTERIOR GLAZED DOORS.
3.GLAZED OPENINGS WITHIN EXTERIOR DOORS.
4.GLAZED OPENINGS WITHIN EXTERIOR GARAGE DOORS.
5.EXTERIOR STRUCTURAL GLASS VENEER.
6.SKYLIGHTS.
7.VENTS.
R337.8.2.1 EXTERIOR WINDOWS, SKYLIGHTS AND EXTERIOR GLAZED DOOR ASSEMBLY REQUIREMENTS
EXTERIOR WINDOWS, SKYLIGHTS AND EXTERIOR GLAZED DOOR ASSEMBLIES SHALL COMPLY WITH ONE
OF THE FOLLOWING REQUIREMENTS:
1.BE CONSTRUCTED OF MULTIPANE GLAZING WITH A MINIMUM OF ONE TEMPERED PANE MEETING THE
REQUIREMENTS OF SECTION R308 SAFETY GLAZING, OR
2.BE CONSTRUCTED OF GLASS BLOCK UNITS, OR
3.HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 20 MINUTES WHEN TESTED ACCORDING TO
NFPA 257, OR
4.BE TESTED TO MEET THE PERFORMANCE REQUIREMENTS OF SFM STANDARD 12-7A-2.
R337.8.2.2 OPERABLE SKYLIGHTS
OPERABLE SKYLIGHTS SHALL BE PROTECTED BY A NONCOMBUSTIBLE MESH SCREEN WHERE THE
DIMENSIONS OF THE OPENINGS IN THE SCREEN SHALL NOT EXCEED 18 INCH (3.2 MM).
R337.8.2.3 STRUCTURAL GLASS VENEER
THE WALL ASSEMBLY BEHIND STRUCTURAL GLASS VENEER SHALL COMPLY WITH SECTION R337.7.3
EXTERIOR WALLS.
R337.8.3 EXTERIOR DOORS
EXTERIOR DOORS SHALL COMPLY WITH ONE OF THE FOLLOWING:
1.THE EXTERIOR SURFACE OR CLADDING SHALL BE OF NONCOMBUSTIBLE MATERIAL, OR
2.THE EXTERIOR SURFACE OR CLADDING SHALL BE OF IGNITIONRESISTANT MATERIAL, OR
3.THE EXTERIOR DOOR SHALL BE CONSTRUCTED OF SOLID CORE WOOD THAT COMPLIES WITH THE
FOLLOWING REQUIREMENTS:
1.STILES AND RAILS SHALL NOT BE LESS THAN 138 INCHES THICK
2.PANELS SHALL NOT BE LESS THAN 114 INCHES THICK, EXCEPT FOR THE EXTERIOR PERIMETER OF
THE PANEL THAT SHALL BE PERMITTED TO TAPER TO A TONGUE NOT LESS THAN 38 INCH THICK.
4.THE EXTERIOR DOOR ASSEMBLY SHALL HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 20
MINUTES WHEN TESTED ACCORDING TO NFPA 252.
5.THE EXTERIOR SURFACE OR CLADDING SHALL BE TESTED TO MEET THE PERFORMANCE
REQUIREMENTS OF SECTION R337.7.3.1 WHEN TESTED IN ACCORDANCE WITH ASTM E2707.
6.THE EXTERIOR SURFACE OR CLADDING SHALL BE TESTED TO MEET THE PERFORMANCE
REQUIREMENTS OF SFM STANDARD 12-7A-1.
R337.8.3.1 EXTERIOR DOOR GLAZING
GLAZING IN EXTERIOR DOORS SHALL COMPLY WITH SECTION R337.8.2.1.
R337.8.4 GARAGE DOOR PERIMETER GAP
EXTERIOR GARAGE DOORS SHALL RESIST THE INTRUSION OF EMBERS FROM ENTERING BY PREVENTING
GAPS BETWEEN DOORS AND DOOR OPENINGS, AT THE BOTTOM, SIDES AND TOPS OF DOORS, FROM
EXCEEDING 18 INCH (3.2 MM). GAPS BETWEEN DOORS AND DOOR OPENINGS SHALL BE CONTROLLED BY
ONE OF THE FOLLOWING METHODS:
1.WEATHER STRIPPING PRODUCTS MADE OF MATERIALS THAT: (A) HAVE BEEN TESTED FOR TENSILE
STRENGTH IN ACCORDANCE WITH ASTM D638 (STANDARD TEST METHOD FOR TENSILE PROPERTIES OF
PLASTICS) AFTER EXPOSURE TO ASTM G155 (STANDARD PRACTICE FOR OPERATING XENON ARC LIGHT
APPARATUS FOR EXPOSURE OF NONMETALLIC MATERIALS) FOR A PERIOD OF 2,000 HOURS, WHERE THE
MAXIMUM ALLOWABLE DIFFERENCE IN TENSILE STRENGTH VALUES BETWEEN EXPOSED AND
NONEXPOSED SAMPLES DOES NOT EXCEED 10 PERCENT AND (B) EXHIBIT A V-2 OR BETTER FLAMMABILITY
RATING WHEN TESTED TO UL 94, STANDARD FOR TESTS FOR FLAMMABILITY OF PLASTIC MATERIALS FOR
PARTS IN DEVICES AND APPLIANCES.
2.DOOR OVERLAPS ONTO JAMBS AND HEADERS.
3.GARAGE DOOR JAMBS AND HEADERS COVERED WITH METAL FLASHING.
SECTION R337.9 DECKING
R337.9.1 GENERAL
THE WALKING SURFACE MATERIAL OF DECKS, PORCHES, BALCONIES AND STAIRS SHALL COMPLY WITH
THE REQUIREMENTS OF THIS SECTION.
R337.9.1.1 FLASHING
A MINIMUM OF A 6-INCH (150 MM) METAL FLASHING, APPLIED VERTICALLY ON THE EXTERIOR OF THE WALL,
SHALL BE INSTALLED AT ALL DECK-TO-WALL INTERSECTIONS.
R337.9.2 WHERE REQUIRED
THE WALKING SURFACE MATERIAL OF DECKS, PORCHES, BALCONIES AND STAIRS SHALL COMPLY WITH
THE REQUIREMENTS OF THIS SECTION WHEN ANY PORTION OF SUCH SURFACE IS WITHIN 10 FEET (3048
MM) OF THE BUILDING.
R337.9.3 DECKING SURFACES
THE WALKING SURFACE MATERIAL OF DECKS, PORCHES, BALCONIES AND STAIRS SHALL BE
CONSTRUCTED WITH ONE OF THE FOLLOWING MATERIALS:
1.MATERIAL THAT COMPLIES WITH THE PERFORMANCE REQUIREMENTS OF SECTION R337.9.4 WHEN
TESTED IN ACCORDANCE WITH BOTH ASTM E2632 AND ASTM E2726.
2.IGNITION-RESISTANT MATERIAL THAT COMPLIES WITH THE PERFORMANCE REQUIREMENTS OF
SECTION R337.9.4.
3.MATERIAL THAT COMPLIES WITH THE PERFORMANCE REQUIREMENTS OF BOTH SFM STANDARD
12-7A-4 AND SECTION R337.4.3.
4.EXTERIOR FIRE-RETARDANT-TREATED WOOD.
5.NONCOMBUSTIBLE MATERIAL.
6.ANY MATERIAL THAT COMPLIES WITH THE PERFORMANCE REQUIREMENTS OF SFM STANDARD
12-7A-4A WHEN ATTACHED EXTERIOR WALL COVERING IS ALSO COMPOSED OF NONCOMBUSTIBLE OR
IGNITION-RESISTANT MATERIAL.
EXCEPTION: WALL MATERIAL SHALL BE PERMITTED TO BE OF ANY MATERIAL THAT OTHERWISE COMPLIES
WITH THIS CHAPTER WHEN THE DECKING SURFACE MATERIAL COMPLIES WITH THE PERFORMANCE
REQUIREMENTS ASTM E84 WITH A CLASS B FLAME SPREAD INDEX.
7.ANY MATERIAL THAT COMPLIES WITH THE PERFORMANCE REQUIREMENTS OF SECTION R337.9.5
WHEN TESTED IN ACCORDANCE WITH ASTM E2632 AND WHEN ATTACHED EXTERIOR WALL COVERING IS
ALSO COMPOSED OF ONLY NONCOMBUSTIBLE OR IGNITION-RESISTANT MATERIALS.
EXCEPTION: WALL MATERIAL SHALL BE PERMITTED TO BE OF ANY MATERIAL THAT OTHERWISE COMPLIES
WITH THIS CHAPTER WHEN THE DECKING SURFACE MATERIAL COMPLIES WITH THE PERFORMANCE
REQUIREMENTS ASTM E84 WITH A CLASS B FLAME SPREAD INDEX.
R337.9.4 REQUIREMENTS FOR TYPE OF MATERIAL IN SECTION R337.9.3, ITEM 1
THE MATERIAL SHALL BE TESTED IN ACCORDANCE WITH BOTH ASTM E2632 AND ASTM E2726 AND SHALL
COMPLY WITH THE CONDITIONS OF ACCEPTANCE IN SECTIONS R337.9.4.1 AND R337.9.4.2. THE MATERIAL
SHALL ALSO BE TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723 AND COMPLY WITH THE
PERFORMANCE REQUIREMENTS OF SECTION R337.4.3.
R337.9.4.1 CONDITIONS OF ACCEPTANCE FOR ASTM E2632
THE ASTM E2632 TEST SHALL BE CONDUCTED ON A MINIMUM OF THREE TEST SPECIMENS AND THE
CONDITIONS OF ACCEPTANCE IN ITEMS 1 THROUGH 3 BELOW SHALL BE MET. IF ANY ONE OF THE THREE
TESTS DOES NOT MEET THE CONDITIONS OF ACCEPTANCE, THREE ADDITIONAL TESTS SHALL BE RUN. ALL
OF THE ADDITIONAL TESTS SHALL MEET THE CONDITIONS OF ACCEPTANCE.
1.PEAK HEAT RELEASE RATE OF LESS THAN OR EQUAL TO 25 KW/FT2 (269 KW/M2 ).
2.ABSENCE OF SUSTAINED FLAMING OR GLOWING COMBUSTION OF ANY KIND AT THE CONCLUSION OF
THE 40-MINUTE OBSERVATION PERIOD.
3.ABSENCE OF FALLING PARTICLES THAT ARE STILL BURNING WHEN REACHING THE BURNER OR
FLOOR.
R337.9.4.2 CONDITIONS OF ACCEPTANCE FOR ASTM E2726
THE ASTM E2726 TEST SHALL BE CONDUCTED, USING A "CLASS A" SIZE ROOF TEST BRAND, ON A MINIMUM
OF THREE TEST SPECIMENS AND THE CONDITIONS OF ACCEPTANCE IN ITEMS 1 AND 2 BELOW SHALL BE
MET. IF ANY ONE OF THE THREE TEST SPECIMENS DOES NOT MEET THE CONDITIONS OF ACCEPTANCE,
THREE ADDITIONAL TESTS SHALL BE RUN. ALL OF THE ADDITIONAL TESTS SHALL MEET THE CONDITIONS
OF ACCEPTANCE.
1.ABSENCE OF SUSTAINED FLAMING OR GLOWING COMBUSTION OF ANY KIND AT THE CONCLUSION OF
THE 40-MINUTE OBSERVATION PERIOD.
2.ABSENCE OF FALLING PARTICLES THAT ARE STILL BURNING WHEN REACHING THE BURNER OR
FLOOR.
R337.9.5 REQUIREMENTS FOR TYPE OF MATERIAL IN SECTION R337.9.3, ITEM 7
THE MATERIAL SHALL BE TESTED IN ACCORDANCE WITH ASTM E2632 AND SHALL COMPLY WITH THE
FOLLOWING CONDITION OF ACCEPTANCE. THE ASTM E2632 TEST SHALL BE CONDUCTED ON A MINIMUM OF
THREE TEST SPECIMENS AND THE PEAK HEAT RELEASE RATE SHALL BE LESS THAN OR EQUAL TO 25
KW/FT2 (269 KW/M2 ). IF ANY ONE OF THE THREE TESTS DOES NOT MEET THE CONDITIONS OF ACCEPTANCE,
THREE ADDITIONAL TESTS SHALL BE RUN. ALL THE ADDITIONAL TESTS SHALL MEET THE CONDITION OF
ACCEPTANCE.
SECTION R337.10 ACCESSORY BUILDINGS AND MISCELLANEOUS STRUCTURES
R337.10.1 GENERAL
GROUP U OCCUPANCY ACCESSORY BUILDINGS AND MISCELLANEOUS STRUCTURES THAT HAVE THE
POTENTIAL TO POSE A SIGNIFICANT EXTERIOR FIRE EXPOSURE HAZARD DURING WILDFIRES SHALL BE
CONSTRUCTED TO CONFORM TO THE IGNITIONRESISTANCE REQUIREMENTS OF THIS SECTION.
R337.10.2 APPLICABILITY
UNLESS OTHERWISE ADDRESSED BY THE EXCEPTIONS OF SECTION R337.1.3, THE PROVISIONS OF THIS
SECTION SHALL APPLY TO BUILDINGS ACCESSORY TO AN APPLICABLE BUILDING ON THE SAME LOT. THIS
SECTION SHALL ALSO APPLY TO ATTACHED AND DETACHED MISCELLANEOUS STRUCTURES THAT
REQUIRE A BUILDING PERMIT, INCLUDING BUT NOT LIMITED TO; TRELLISES, ARBORS, PATIO COVERS,
GAZEBOS AND SIMILAR STRUCTURES.
EXCEPTIONS:
1.DECKS SHALL COMPLY WITH THE REQUIREMENTS OF SECTION R337.9.
2.AWNINGS AND CANOPIES SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 3105 OF THE
CALIFORNIA BUILDING CODE.
3.EXTERIOR WALL ARCHITECTURAL TRIM, EMBELLISHMENTS AND FASCIA.
R337.10.3 WHERE REQUIRED
MISCELLANEOUS STRUCTURES THAT REQUIRE A PERMIT, AND ACCESSORY BUILDINGS OF ANY SIZE, WHEN
SEPARATED FROM AN APPLICABLE BUILDING ON THE SAME LOT BY A DISTANCE OF LESS THAN 3 FEET (914
MM), SHALL COMPLY WITH SECTION R337.10.3.1. ACCESSORY BUILDINGS THAT ARE GREATER THAN 120
SQUARE FEET (11 M2 ), WHEN SEPARATED FROM AN APPLICABLE BUILDING ON THE SAME LOT BY A
DISTANCE OF 3 FEET (914 MM) OR MORE BUT LESS THAN 50 FEET (15 M) SHALL COMPLY WITH SECTION
R337.10.3.2.
WHEN REQUIRED BY THE ENFORCING AGENCY, MISCELLANEOUS STRUCTURES THAT REQUIRE A PERMIT,
AND ACCESSORY BUILDINGS THAT ARE 120 SQUARE FEET (11 M2 ) OR LESS, WHEN SEPARATED FROM AN
APPLICABLE BUILDING ON THE SAME LOT BY A DISTANCE OF 3 FEET (914 MM) OR MORE BUT LESS THAN 50
FEET (15 M), SHALL COMPLY WITH EITHER SECTION R337.10.3.4 OR SECTION R337.10.3.3, RESPECTIVELY.
NO REQUIREMENTS SHALL APPLY TO ACCESSORY BUILDINGS OR MISCELLANEOUS STRUCTURES WHEN
LOCATED 50 FEET (15 M) OR MORE FROM AN APPLICABLE BUILDING ON THE SAME LOT.
R337.10.3.1 STRUCTURES AND ACCESSORY BUILDINGS WITHIN 3 FEET (914 MM)
MISCELLANEOUS STRUCTURES THAT REQUIRE A PERMIT, AND ACCESSORY BUILDINGS ATTACHED TO OR
SEPARATED FROM AN APPLICABLE BUILDING ON THE SAME LOT BY A DISTANCE OF LESS THAN 3 FEET (914
MM) SHALL BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS OR OF IGNITIONRESISTANT MATERIALS
AS DESCRIBED IN SECTION R337.4.2.
R337.10.3.2 ACCESSORY BUILDINGS GREATER THAN 120 SQUARE FEET (11 M2), LOCATED 3 FEET (914 MM)
OR MORE BUT LESS THAN 50 FEET (15 M)
ACCESSORY BUILDINGS THAT ARE GREATER THAN 120 SQUARE FEET (11 M2 ) IN SIZE AND SEPARATED
FROM AN APPLICABLE BUILDING ON THE SAME LOT BY A DISTANCE OF 3 FEET (914 MM) OR MORE BUT LESS
THAN 50 FEET (15 M) SHALL BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS OR OF
IGNITIONRESISTANT MATERIALS AS DESCRIBED IN SECTION R337.4.2.
R337.10.3.3 ACCESSORY BUILDINGS 120 SQUARE FEET (11 M2) OR LESS, LOCATED 3 FEET (914 MM) OR
MORE BUT LESS THAN 50 FEET (15 M)
WHEN REQUIRED BY THE ENFORCING AGENCY, ACCESSORY BUILDINGS 120 SQUARE FEET (11 M2 ) OR LESS
AND SEPARATED FROM AN APPLICABLE BUILDING ON THE SAME LOT BY A DISTANCE OF 3 FEET (914 MM)
OR MORE BUT LESS THAN 50 FEET (15 M) SHALL BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS OR
OF IGNITION-RESISTANT MATERIALS AS DESCRIBED IN SECTION R337.4.2.
R337.10.3.4 MISCELLANEOUS STRUCTURES LOCATED 3 FEETR (914 MM) OR MORE BUT LESS THAN 50 FEET
(15 M)
WHEN REQUIRED BY THE ENFORCING AGENCY, MISCELLANEOUS STRUCTURES THAT REQUIRE A PERMIT
AND ARE SEPARATED FROM AN APPLICABLE BUILDING ON THE SAME LOT BY A DISTANCE OF 3 FEET (914
MM) OR MORE BUT LESS THAN 50 FEET (15 M) SHALL BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS
OR OF IGNITION-RESISTANT MATERIALS AS DESCRIBED IN SECTION R337.4.3.
R337.10.4 ROOF CONSTRUCTION
ROOFS OF ACCESSORY BUILDINGS REQUIRED TO BE CONSTRUCTED ENTIRELY OF NONCOMBUSTIBLE
MATERIALS OR OF IGNITION-RESISTANT MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF
SECTION 337 AND CHAPTER 9. ROOFS SHALL HAVE A ROOFING ASSEMBLY INSTALLED IN ACCORDANCE
WITH ITS LISTING AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. ROOF ASSEMBLIES IN FIRE
HAZARD SEVERITY ZONES SHALL COMPLY WITH A CLASS A RATING WHEN TESTED IN ACCORDANCE WITH
ASTM E108 OR UL 790.
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CAWUI MEASURES24-123
SUBMITTAL
CMR
06.05.2025
A5
JUN 05, 2025
A. SITE ADDRESS:
1.BUILDINGS SHALL HAVE APPROVED ADDRESS NUMBERS, BUILDING
NUMBERS OR APPROVED BUILDING IDENTIFICATION PLACED IN A POSITION
THAT IS PLAINLY LEGIBLE AND VISIBLE FROM THE STREET OR ROAD
FRONTING THE PROPERTY. THESE NUMBERS SHALL CONTRAST WITH THEIR
BACKGROUND.
2.ADDRESS NUMBERS SHALL BE ARABIC NUMBERS OR ALPHABETICAL LETTERS.
NUMBERS SHALL BE A MINIMUM OF 4" WITH A MINIMUM STROKE WIDTH OF
1/2".
3.WHERE ACCESS IS BY MEANS OF A PRIVATE ROAD AND THE BUILDING
ADDRESS CANNOT BE VIEWED FROM THE PUBLIC WAY, A MONUMENT,
POLE OR OTHER SIGN OR MEANS SHALL BE USED TO IDENTIFY THE
STRUCTURE.
B. CONSTRUCTION WASTE MANAGEMENT:
1.CONSTRUCTION WASTE MANAGEMENT: RECYCLE AND/OR SALVAGE A
MINIMUM OF 65% OF THE NON-HAZARDOUS CONSTRUCTION &
DEMOLITION WASTE. CGBC 4.408.1.
2.CONSTRUCTION WASTE MANAGEMENT PLAN: SUBMIT A CONSTRUCTION
WASTE MANAGEMENT PLAN. THE CONSTRUCTION WASTE MANAGEMENT
PLAN SHALL BE UPDATED AS NECESSARY & SHALL BE AVAILABLE DURING
CONSTRUCTION FOR EXAMINATION BY THE ENFORCING AGENCY. CGBC
4.408.2
3.WASTE MANAGEMENT COMPANY: UTILIZE A WASTE MANAGEMENT
COMPANY, APPROVED BY THE ENFORCING AGENCY, WHICH CAN
PROVIDE VERIFIABLE DOCUMENTATION THAT THE PERCENTAGE OF
CONSTRUCTION & DEMOLITION WASTE MATERIAL DIVERTED FROM THE
LANDFILL COMPLIES WITH SECTION 4.408.3.
4.NOTE: THE OWNER OR CONTRACTOR MAY MAKE THE DETERMINATION IF
THE CONSTRUCTION & DEMOLITION WASTE MATERIALS WILL BE DIVERTED
BY A WASTE MANAGEMENT COMPANY.
5.WASTE STREAM REDUCTION ALTERNATIVE: PROJECTS THAT GENERATE A
TOTAL COMBINED WEIGHT OF CONSTRUCTION & DEMOLITION WASTE
DISPOSED OF IN LANDFILLS, WHICH DO NOT EXCEED 3.4 LBS./SQ. FT. OF
THE BUILDING AREA SHALL MEET THE MINIMUM 65 PERCENT
CONSTRUCTION WASTE REDUCTION REQUIREMENT IN SECTION 4.408.1.
6.DOCUMENTATION: DOCUMENTATION SHALL BE PROVIDED TO THE
ENFORCING AGENCY WHICH DEMONSTRATES COMPLIANCE WITH CGBC
4.408.2.
C. GREEN PLANNING & DESIGN:
1.DURING CONSTRUCTION, ONE OR MORE OF THE FOLLOWING MEASURES
SHALL BE IMPLEMENTED TO PREVENT FLOODING OF THE ADJACENT
PROPERTY, PREVENT EROSION & RETAIN SOIL RUNOFF ON THE SITE:
a.RETENTION BASINS OF SUFFICIENT SIZE SHALL BE UTILIZED TO RETAIN
STORM WATER ON SITE.
b.WHERE STORM WATER IS CONVEYED TO A PUBLIC DRAINAGE SYSTEM,
COLLECTING POINT, GUTTER OR SIMILAR DISPOSAL METHOD, WATER
SHALL BE FILTERED BY USE OF A BARRIER SYSTEM WATTLE OR OTHER
METHOD APPROVED BY THE ENFORCING AGENCY.
c.COMPLIANCE WITH A LAWFUL ENACTED STORM WATER MANAGEMENT
ORDINANCE. METHODS TO MANAGE SURFACE WATER INCLUDE:
SWALES, WATER COLLECTION &DISPOSAL SYSTEMS, FRENCH DRAINS,
WATER RETENTION GARDENS & OTHER WATER MEASURES WHICH KEEP
SURFACE WATER AWAY FROM BUILDINGS & AID IN GROUNDWATER
RECHARGE.
E. EROSION CONTROL:
1. NO SOIL DISRUPTION SHALL OCCUR PRIOR TO OBTAINING A BUILDING
PERMIT OR GRADING PERMIT.
2.THE CONTRACTOR SHALL BE RESPONSIBLE FOR EROSION CONTROL.
3.EROSION CONTROL MEASURES SHALL BE IN PLACE AT ALL TIMES.
4. SOILS TRACKED INTO THE STREET FROM THE WORKSITE SHALL BE CLEANED
UP AT THE END OF EACH WORKDAY.
5. INACTIVE SOIL STOCKPILES SHALL BE COVERED. ACTIVE SOIL STOCKPILES
SHALL BE COVERED PRIOR TO A FORECASTED RAIN EVENT.
6. THE EROSION CONTROL PLAN SHALL BE RE-EVALUATED AND ADJUSTED
ACCORDINGLY AFTER A RAIN EVENT.
7. EROSION CONTROL MEASURES SHALL BE CONTINUOUSLY MAINTAINED.
F. GRADING:
1. THE LOT SHALL BE GRADED TO DRAIN SURFACES AWAY FROM (N)
FOUNDATION WALLS. THE GRADING SHALL FALL A MIN. OF 6INCHES WITHIN
THE FIRST 10 FEET. CRC R401.3
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CAPROPOSED SITE PLAN24-123
SUBMITTAL
CMR
06.05.2025
A6
JUN 05, 2025
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CA1st & 2nd FLOOR PLAN24-123
SUBMITTAL
CMR
06.05.2025
A7
JUN 05, 2025
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CAELEVATIONS, SECTIONDEMOLITION PLAN24-123
SUBMITTAL
CMR
06.05.2025
A8
JUN 05, 2025
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CAELECTRICAL PLAN24-123
SUBMITTAL
CMR
06.05.2025
A9
JUN 05, 2025
S3
S
SD3
SD
J SSSSSSSSSSSSSSSSSSSSSSSSSSS
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CASTRUCTURAL NOTES24-123
SUBMITTAL
CMR
06.05.2025
S1
JUN 05, 2025
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CASTRUCTURAL PLANS24-123
SUBMITTAL
CMR
06.05.2025
S2.1
JUN 05, 2025
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CASTRUCTURAL PLANS24-123
SUBMITTAL
CMR
06.05.2025
S2.2
JUN 05, 2025
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CASTRUCTURAL PLANS24-123
SUBMITTAL
CMR
06.05.2025
S2.3
JUN 05, 2025
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CASTRUCTURAL DETAILS24-123
SUBMITTAL
CMR
06.05.2025
S3.1
JUN 05, 2025
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CASTRUCTURAL DETAILS24-123
SUBMITTAL
CMR
06.05.2025
S3.2
JUN 05, 2025
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CASTRUCTURAL DETAILS24-123
SUBMITTAL
CMR
06.05.2025
S3.3
JUN 05, 2025
REV DATE BY
HAD
CM.RATZ
L
AFFL
EXP. 6-30-27
064399
LIVIC AINROFILACFOETA
TS SEFOR
ERD
NEP
I
ERET
ISGGE
NANOIS
REDRAWING NUMBER
Phase:
Project #:
Ckd. By:
Date:FISKE CABIN7792 HUMBOLDT RDBUTTE MEADOWS, CASTRUCTURAL DETAILS24-123
SUBMITTAL
CMR
06.05.2025
S3.4
JUN 05, 2025