HomeMy WebLinkAboutFAI15-0085 029-162-002 Richvale Elem FA 11.1.24 (1) ALARM AND DETECTION REPORT Page 1 of 5
VOLTAG PECIALisTs
530-624-4514
C101C16 License#880862 www.VoltageSpecialists.com Inspection #
ALARM & DETECTION EQUIPMENT TEST REPORT
Type of Inspection: Annual Date: 11/1/24
site: Richvale Elem School Customer:Biggs USD
street: 5236 Church Street contact: John Strattard
City/State: Richvale, CA Phone#: 530-868-1281
Fax#:
1. Before Test Notify Proper Authorities: Name Phone #
A. Owner or Owner's Rep John Strattard 530-868-1281
B. Fire Department
C. Central Station Central Station 1-800-722-0364
D. Central Station Acct# 18-9481
2. Control Panel Status Yes No Note #
A. Is the system monitored by Central Station? X
On Test Time: 3:30 Return to Service Time: 8:00
B. Is the Power Light on? X
C. Does the Panel indicate Normal conditions? X
D. Are all indicating Lamp Bulbs in Operator order? X
E. Does the Trouble Light operate? X
F. Does the Silence Switch Operate? X
G. Battery A.H. 18 Date Batteries Installed: 9/1/2020
H. Does the Panel have Non-Operational Zones? X
I. Does the Panel have Battery Backup? X
J. Do the batteries indicate they are Properly Charged? X
Condition of Batteries: 27.41 Note#
Battery Voltage with AC Power: Good Battery Voltage without AC Power: 27.39
K. List any trouble conditions on panel before test: Note#
Note#
Comments: Note#
Note#
3. FACP Manufacturer: Silent knight Model# 6820EVS System Type: Addressable
Location of Annunciators: Main Office
Location of Primary Power Source: Panel# Breaker
Comments: Note#
Note#
FCPS: Manufacturer: Silent knight Model# EVS-50W Panel/Breaker# Location:Equipment RM
sah
Battery Voltage with A/C Power: 27.31 w/o A/C Power 2726 Date: 9/1/2020
FCPS: Manufacturer: Model# Panel/Breaker# Location:
Battery Voltage with A/C Power: w/o A/C Power Date:
FCPS: Manufacturer: Model# Panel/Breaker# Location:
Battery Voltage with A/C Power: w/o A/C Power Date:
Owner/Rep: Phone#: Date:
Inspector: Wyatt C. Phone#: 530-362-2609 Date: 11/1/24
Owners Rep Sign: Date:11/1/24 Inspector Sign:
ALARM AND DETECTION REPORT Page 2 of 5
Property Site: Richvale Elem School
Operational
#Tested
This
Equipment Total# Report Yes N/A Note#
4. Remote Annunciators
5. Zones
6. Manual Stations (Pull) 2 2 X
Hardwire
Addressable
7. Detectors
Photoelectric 25 25 X
Ionization
Heats/Fixed or R of R 7 7 X
Flame
Duct(See#15)
8. Horn/Strobe
Strobe Only
Bell
Speakers
Horn
9.
10. Automatic Door Release
11. Water Flow switches
Did W/F Ring Outside Bell?
Did W/F Activate Alarm Panel?
12. Tamper Switches
13. PIV
OS &Y
14.
15. Did test of Duct Detectors shut down air handling units? X
16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line) receive signal? X
17. Is system reset for normal conditions? X
18. Is system restored to operational service? X
19. Have Proper Authorities (see#1)been notified system is back in service? X
List Proper Authorities:Central station
20. Indicate %of equipment tested this report 25% 50% 75% VJI00%
21. Indicate %of equipment tested YTD 25% 50% 75% 100%
Comments for any"no"answers or explanations (Note#):
11/1/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Richvale Elem School Page 3 of 5
DEVICE Zone or SLC DEVICE
#
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
HT Boy's RR Attic X 97 MO1
HT East Mech Mezz X 97 M03
HT Girls RR Attic X 97 M04
HT West Mech Mezz X 97 M05
HT Admin Office Attic X 97 M07
HT Conference Rm Attic X 97 M08
HT Waiting Attic X 97 M09
PS Lobby X 97 M06
PS Gym X 97 M10
PSD Electrical RM X 97 sool
PSD NE. Storage RM X 97 S002
PSD Boys RR X 97 S003
PSD Girls RR X 97 S004
PSD Janitorial X 97 S005
PSD Activities East X 97 S006
PSD Activities East X 97 S007
PSD Classroom 3 X 97 S009
PSD Classroom 3 X 97 soil
PSD Activities RM X 97 S013
PSD Classroom 4 X 97 S015
PSD Activities RM X 97 S016
PSD Classroom 4 X 97 S017
PSD Classroom 2 X 97 S018
PSD Classroom 2 X 97 S020
PSD Classroom 1 X 97 S022
PSD Classroom 1 X 97 S023
PSD Waiting Area X 97 S024
PSD Office/Activities Vestibule X 97 S025
PSD Reception X 97 S026
PSD Conference RM X 97 S027
PSD Work RM X 97 S028
11/1/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Richvale Elem School Page 4 of 5
DEVICE Zone or
DEVICE
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL #
PSD Principals Office X 97 S029
PSD Teacher's Rm X 97 S030
PSD Teachers Rm RR X 97 S031
11/1/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Richvale Elem School Page 5 of 5
Zone or DEVICE
DEVICE SLC #
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
LEGEND
PSD—Photoelectric Smoke Detector BD—Beam Detector H—Horn V—Visual
ISD—Ionization Smoke Detector PS—Pull Station WPH—Weather Proof Horn TS—Tamper Switch
PDD—Photo Duct Smoke Detector RR—Rate of Rise Heat Detector C—Chime WF—Water Flow Switch
IDD—Ion Duct Smoke Detector HT—Fixed Temp Heat Detector CV—Chime Visual DH—Door Holder
DHS—Door Holder&Smoke Detector FD—Flame Detector S—Speaker OSY—Outside Stem&Yoke Tamper Valve
SSD—Signal Station Smoke Detector B—Bell AV—Audible Visual Ply—Post Indicator Valve
Cur-Elevator Curtains FRD-Fire Rolldown Door SDC Smoke Detector&Door Holder Combo
CO-Carbon Monoxide Detector - - -
NOTE # COMMENT
** See Discrepancy Report **
Discrepancies Found? ✓ Yes I I No
See Discrepancy Report? ✓ Yes No
11/1/24