Loading...
HomeMy WebLinkAboutFAI15-0085 029-162-002 Richvale Elem FA 11.1.24 (1) ALARM AND DETECTION REPORT Page 1 of 5 VOLTAG PECIALisTs 530-624-4514 C101C16 License#880862 www.VoltageSpecialists.com Inspection # ALARM & DETECTION EQUIPMENT TEST REPORT Type of Inspection: Annual Date: 11/1/24 site: Richvale Elem School Customer:Biggs USD street: 5236 Church Street contact: John Strattard City/State: Richvale, CA Phone#: 530-868-1281 Fax#: 1. Before Test Notify Proper Authorities: Name Phone # A. Owner or Owner's Rep John Strattard 530-868-1281 B. Fire Department C. Central Station Central Station 1-800-722-0364 D. Central Station Acct# 18-9481 2. Control Panel Status Yes No Note # A. Is the system monitored by Central Station? X On Test Time: 3:30 Return to Service Time: 8:00 B. Is the Power Light on? X C. Does the Panel indicate Normal conditions? X D. Are all indicating Lamp Bulbs in Operator order? X E. Does the Trouble Light operate? X F. Does the Silence Switch Operate? X G. Battery A.H. 18 Date Batteries Installed: 9/1/2020 H. Does the Panel have Non-Operational Zones? X I. Does the Panel have Battery Backup? X J. Do the batteries indicate they are Properly Charged? X Condition of Batteries: 27.41 Note# Battery Voltage with AC Power: Good Battery Voltage without AC Power: 27.39 K. List any trouble conditions on panel before test: Note# Note# Comments: Note# Note# 3. FACP Manufacturer: Silent knight Model# 6820EVS System Type: Addressable Location of Annunciators: Main Office Location of Primary Power Source: Panel# Breaker Comments: Note# Note# FCPS: Manufacturer: Silent knight Model# EVS-50W Panel/Breaker# Location:Equipment RM sah Battery Voltage with A/C Power: 27.31 w/o A/C Power 2726 Date: 9/1/2020 FCPS: Manufacturer: Model# Panel/Breaker# Location: Battery Voltage with A/C Power: w/o A/C Power Date: FCPS: Manufacturer: Model# Panel/Breaker# Location: Battery Voltage with A/C Power: w/o A/C Power Date: Owner/Rep: Phone#: Date: Inspector: Wyatt C. Phone#: 530-362-2609 Date: 11/1/24 Owners Rep Sign: Date:11/1/24 Inspector Sign: ALARM AND DETECTION REPORT Page 2 of 5 Property Site: Richvale Elem School Operational #Tested This Equipment Total# Report Yes N/A Note# 4. Remote Annunciators 5. Zones 6. Manual Stations (Pull) 2 2 X Hardwire Addressable 7. Detectors Photoelectric 25 25 X Ionization Heats/Fixed or R of R 7 7 X Flame Duct(See#15) 8. Horn/Strobe Strobe Only Bell Speakers Horn 9. 10. Automatic Door Release 11. Water Flow switches Did W/F Ring Outside Bell? Did W/F Activate Alarm Panel? 12. Tamper Switches 13. PIV OS &Y 14. 15. Did test of Duct Detectors shut down air handling units? X 16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line) receive signal? X 17. Is system reset for normal conditions? X 18. Is system restored to operational service? X 19. Have Proper Authorities (see#1)been notified system is back in service? X List Proper Authorities:Central station 20. Indicate %of equipment tested this report 25% 50% 75% VJI00% 21. Indicate %of equipment tested YTD 25% 50% 75% 100% Comments for any"no"answers or explanations (Note#): 11/1/24 Owners Rep Sign: Date: Inspector Sign: ALARM AND DETECTION REPORT Richvale Elem School Page 3 of 5 DEVICE Zone or SLC DEVICE # TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL HT Boy's RR Attic X 97 MO1 HT East Mech Mezz X 97 M03 HT Girls RR Attic X 97 M04 HT West Mech Mezz X 97 M05 HT Admin Office Attic X 97 M07 HT Conference Rm Attic X 97 M08 HT Waiting Attic X 97 M09 PS Lobby X 97 M06 PS Gym X 97 M10 PSD Electrical RM X 97 sool PSD NE. Storage RM X 97 S002 PSD Boys RR X 97 S003 PSD Girls RR X 97 S004 PSD Janitorial X 97 S005 PSD Activities East X 97 S006 PSD Activities East X 97 S007 PSD Classroom 3 X 97 S009 PSD Classroom 3 X 97 soil PSD Activities RM X 97 S013 PSD Classroom 4 X 97 S015 PSD Activities RM X 97 S016 PSD Classroom 4 X 97 S017 PSD Classroom 2 X 97 S018 PSD Classroom 2 X 97 S020 PSD Classroom 1 X 97 S022 PSD Classroom 1 X 97 S023 PSD Waiting Area X 97 S024 PSD Office/Activities Vestibule X 97 S025 PSD Reception X 97 S026 PSD Conference RM X 97 S027 PSD Work RM X 97 S028 11/1/24 Owners Rep Sign: Date: Inspector Sign: ALARM AND DETECTION REPORT Richvale Elem School Page 4 of 5 DEVICE Zone or DEVICE TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL # PSD Principals Office X 97 S029 PSD Teacher's Rm X 97 S030 PSD Teachers Rm RR X 97 S031 11/1/24 Owners Rep Sign: Date: Inspector Sign: ALARM AND DETECTION REPORT Richvale Elem School Page 5 of 5 Zone or DEVICE DEVICE SLC # TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL LEGEND PSD—Photoelectric Smoke Detector BD—Beam Detector H—Horn V—Visual ISD—Ionization Smoke Detector PS—Pull Station WPH—Weather Proof Horn TS—Tamper Switch PDD—Photo Duct Smoke Detector RR—Rate of Rise Heat Detector C—Chime WF—Water Flow Switch IDD—Ion Duct Smoke Detector HT—Fixed Temp Heat Detector CV—Chime Visual DH—Door Holder DHS—Door Holder&Smoke Detector FD—Flame Detector S—Speaker OSY—Outside Stem&Yoke Tamper Valve SSD—Signal Station Smoke Detector B—Bell AV—Audible Visual Ply—Post Indicator Valve Cur-Elevator Curtains FRD-Fire Rolldown Door SDC Smoke Detector&Door Holder Combo CO-Carbon Monoxide Detector - - - NOTE # COMMENT ** See Discrepancy Report ** Discrepancies Found? ✓ Yes I I No See Discrepancy Report? ✓ Yes No 11/1/24 Owners Rep Sign: Date: Inspector Sign: