HomeMy WebLinkAboutFAI15-0099 022-320-001 Biggs Elem FA 11.1.24 ALARM AND DETECTION REPORT Page 1 of 8
VOLTAG PECIALisTs
530-624-4514
C101C16 License#880862 www.VoltageSpecialists.com Inspection #
ALARM & DETECTION EQUIPMENT TEST REPORT
Type of Inspection: Annual Date: 11/1/24
site: Biggs Elementary School Customer: Biggs USD
Street: 300 B Street Contact: John Strattard
City/State: Biggs, California Phone#: 530-868-1281
Fax#:
1. Before Test Notify Proper Authorities: Name Phone #
A. Owner or Owner's Rep John Strattard 530-868-1281
B. Fire Department
C. Central Station Central Station 1-800-722-0364
D. Central Station Acct# 18-9479
2. Control Panel Status Yes No Note #
A. Is the system monitored by Central Station? X
On Test Time: 3:00 Return to Service Time: 9:00
B. Is the Power Light on? X
C. Does the Panel indicate Normal conditions? X
D. Are all indicating Lamp Bulbs in Operator order? X
E. Does the Trouble Light operate? X
F. Does the Silence Switch Operate? X
G. Battery A.H. 18 Date Batteries Installed: 6/19/2020
1-1. Does the Panel have Non-Operational Zones? X
I. Does the Panel have Battery Backup? X
J. Do the batteries indicate they are Properly Charged? X
Condition of Batteries: Good Note#
Battery Voltage with AC Power: 27.43 Battery Voltage without AC Power: 27.40
K. List any trouble conditions on panel before test: Note#
Note#
Comments: Note#
Note#
3. FACP Manufacturer: Silent Knight Model# 6820EVS System Type: Addressable
Location of Annunciators:
Location of Primary Power Source: Panel# Breaker
Comments: Note#
Note#
FCPS: Manufacturer: Silent Knight Model# EVS-100W Panel/Breaker# Location:Gym Storage
8Ah
Battery Voltage with A/C Power: 27.22 w/o A/C Power 27.19 Date: 9/15/2022
FCPS: Manufacturer: Silent Knight Model# 5895XL Panel/Breaker# Location:Gym Storage
18Ah
Battery Voltage with A/C Power: 27.28 w/o A/C Power 27.24 Date: 8/28/2020
FCPS: Manufacturer: Silent Knight Model# EVS-100 Panel/Breaker# Location:Admin.Nurse Office
18Ah 8/28/2020
Battery Voltage with A/C Power: 27.28 w/o A/C Power 27.26 Date:
Owner/Rep: Phone#: Date:
Inspector: Wyatt C. Phone#: 530 362 2609 Date: 11/1/24
Owners Rep Sign: Date:11/1/24 Inspector Sign:
ALARM AND DETECTION REPORT Page 2 of 8
Property Site: Biggs Elementary School
Operational
#Tested
This
Equipment Total# Report Yes N/A Note#
4. Remote Annunciators
5. Zones
6. Manual Stations (Pull) 4 4 X
Hardwire
Addressable
7. Detectors
Photoelectric 62 62 X
Ionization
Heats/Fixed or R of R 38 38 X
Flame
Duct(See#15)
8. Horn/Strobe
Strobe Only
Bell
Speakers
Horn
9.
10. Automatic Door Release
11. Water Flow switches
Did W/F Ring Outside Bell?
Did W/F Activate Alarm Panel?
12. Tamper Switches
13. PIV
OS &Y
14.
15. Did test of Duct Detectors shut down air handling units?
16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line) receive signal?
17. Is system reset for normal conditions?
18. Is system restored to operational service?
19. Have Proper Authorities (see#1)been notified system is back in service?
List Proper Authorities:
20. Indicate %of equipment tested this report 25% 50% 75% VJI00%
21. Indicate %of equipment tested YTD 25% 50% 75% 100%
Comments for any"no"answers or explanations (Note#):
11/1/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Biggs Elementary School Page 3 of 8
Zone or
DEVICE SLC DEVICE
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL #
HT Classroom 5 HVAC Closet X 97 M02
HT Classroom 8 X 97 M03
HT Classroom 9 X 97 M04
HT Classroom 10 X 97 M05
HT Classroom 8 X 97 M06
HT Classroom 7 X 97 M07
HT Classroom 6 X 97 M08
HT Classroom 14 X 97 M09
HT Classroom 15 X 97 M10
HT Classroom 13 X 97 M11
HT Classroom 16 X 97 M12
HT RM 13-16 Quad Lab/Office X 97 M13
HT RM 13-16 RR X 97 M14
HT Classroom 4 HVAC X 97 M20
HT Classroom 3 HVAC X 97 M21
HT Classroom 2 HVAC X 97 M22
HT Classroom 1 HVAC X 97 M23
HT Classroom 9 HVAC X 97 M24
HT Classroom 10 HVAC X 97 M25
HT RM 1 -4 Boys/Girls RR X 97 M26
HT Shed By RM 14 X 97 S23
HT D Bldg. RR Plumbing Chase X 97 S29
HT Classroom 17 X 01 M10
HT Classroom 18 X 01 M11
HT Classroom 19 X 01 M12
HT Classroom 20 X 01 M13
HT Classroom 21 X 01 M14
HT Classroom 22 X 01 M15
HT Classroom 24 X 01 M16
HT Classroom 23 X 01 M17
HT Classroom 25 X 01 M18
11/1/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Biggs Elementary School Page 4 of 8
Zone or
DEVICE SLC ZONE
CHANNEL
TYPE DEVICE LOCATION PASS FAIL NOTE# #
HT Classroom 26 X 01 M19
HT Kitchen Water Heater Closet X 01 MO1
HT N. Kitchen Breezeway X 01 M02
HT Portable RR Attic X 01 M09
HT Kitchen Freezer Attic X 01 M20
HT Kitchen X 01 S05
HT Kitchen X 01 S06
PS By FACP X 97 MO1
PS MP NE. Exit X 01 M04
PS MP NW. Exit X 01 M07
PS MP S. Exit X 01 M08
BD MP N. X 01 S34
BD MP S. X 01 S35
KH Kitchen Ansul X 01 M03
11/1/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Biggs Elementary School Page 5 of 8
Zone or
DEVICE SLC DEVICE
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL #
PSD Portable Staff RR X 01 soil
PSD Portable Girls RR X 01 S012
PSD Portable Boys RR X 01 S013
PSD Classroom 17 X 01 S014
PSD Classroom 18 X 01 S016
PSD Classroom 19 X 01 S018
PSD Classroom 20 X 01 S020
PSD Classroom 21 X 01 S022
PSD Classroom 22 X 01 S024
PSD Classroom 24 X 01 S026
PSD Classroom 23 X 01 S028
PSD Classroom 25 X 01 S030
PSD Classroom 26 X 01 S032
PSD MP Kitchen Food Storage X 01 S01
PSD Kitchen Food Storage X 01 SO2
PSD Kitchen RR X 01 SO4
PSD MP Peak X 01 S07
PSD MP Peak X 01 S10
PSD Above FACP Main Office X 97 soot
PSD Admin Lobby X 97 S002
PSD Admin Nurses Office X 97 S003
PSD Admin Nurses Office RR X 97 S004
PSD Admin Principles Office X 97 S005
PSD Admin Teacher/Copier RM RR X 97 S006
PSD Admin Teacher/Copier RM RR X 97 S007
PSD Admin Boys RR X 97 S008
PSD Admin Girls RR X 97 S009
PSD Classroom 5 X 97 solo
PSD Classroom 4 X 97 S012
PSD Classroom 3 X 97 S014
PSD Classroom 2 X 97 S016
11/1/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Biggs Elementary School Page 6 of 8
Zone or
DEVICE SLC DEVICE
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL #
PSD Classroom 1 X 97 S018
PSD Classroom 1 Work RM X 97 S020
PSD Classroom 1 RR Alcove X 97 S021
PSD Classroom 1 RR X 97 S022
PSD D Bldg. Office Elec. Closet X 97 S024
PSD D Bldg. Office X 97 S025
PSD D Bldg. Storage Closet X 97 S026
PSD D Bldg. Janitors Closet X 97 S027
PSD D Bldg. Girls RR X 97 S028
PSD D Bldg. Boys RR X 97 S030
PSD Classroom 8 X 97 S031
PSD Classroom 9 X 97 S033
PSD Classroom 10 X 97 S035
PSD Library RM 7 X 97 S037
PSD Library RM 7 X 97 S038
PSD Library RM 6 Conference X 97 S039
PSD Library RM 6 Conference X 97 S040
PSD Classroom 13-16 Janitor Closet X 97 S041
PSD Classroom 13-16 Staff RR X 97 S042
PSD Classroom 13-16 Quad Lab X 97 S043
PSD Classroom 13-16 Staff RR X 97 S044
PSD Classroom 13 X 97 S045
PSD Classroom 14 X 97 S048
PSD Classroom 13-16 Girls RR X 97 S049
PSD Classroom 13-16 Boys RR X 97 S050
PSD Classroom 15 X 97 S051
PSD Classroom 16 X 97 S054
PSD Classroom 13-16 Quad Lab X 97 S057
PSD Library 7 HVAC Closet X 97 S060
PSD Library 6 HVAC Closet X 97 S061
PSD F Bldg. Vestibule Staff RR X 97 S062
11/1/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Biggs Elementary School Page 7 of 8
Zone or
DEVICE SLC DEVICE
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL #
CO Classroom 5 X 97 S11
CO Classroom 4 X 97 S13
CO Classroom 3 X 97 S15
CO Classroom 2 X 97 S17
CO Classroom 1 X 97 S19
CO Classroom 8 X 97 S32
CO Classroom 9 X 97 S34
CO Classroom 10 X 97 S36
CO Classroom 13 X 97 S46
CO Classroom 14 X 97 S47
CO Classroom 14 X 97 S52
CO Classroom 16 X 97 S53
CO Classroom 13-16 Office X 97 S55
CO Classroom 13-16 Quad Lab X 97 S56
CO MP Peak X 01 S08
CO MP Peak X 01 S09
CO Classroom 17 X 01 S15
CO Classroom 18 X 01 S17
CO Classroom 19 X 01 S19
CO Classroom 20 X 01 S21
CO Classroom 21 X 01 S23
CO Classroom 22 X 01 S25
CO Classroom 24 X 01 S27
CO Classroom 23 X 01 S29
CO Classroom 25 X 01 S31
CO Classroom 26 X 01 S33
11/1/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Biggs Elementary School Page 8 of 8
Zone or
DEVICE sLC DEVICE
CHANNEL #
TYPE DEVICE LOCATION PASS FAIL NOTE#
LEGEND
PSD—Photoelectric Smoke Detector BD—Beam Detector H—Horn V—Visual
ISD—Ionization Smoke Detector PS—Pull Station WPH—Weather Proof Horn TS—Tamper Switch
PDD—Photo Duct Smoke Detector RR—Rate of Rise Heat Detector C—Chime WF—Water Flow Switch
IDD—Ion Duct Smoke Detector HT—Fixed Temp Heat Detector CV—Chime Visual DH—Door Holder
DHS—Door Holder&Smoke Detector FD—Flame Detector S—Speaker OSY—Outside Stem&Yoke Tamper Valve
SSD—Signal Station Smoke Detector B—Bell AV—Audible Visual PIV—Post Indicator Valve
Cur-Elevator Curtains FRD-Fire Rolldown Door SDC Smoke Detector&Door Holder Combo
CO-Carbon Monoxide Detector - - -
NOTE # COMMENT
Discrepancies Found? I 1 Yes 1,1 No
See Discrepancy Report? n Yes ✓ No
11/1/24
Owners Rep Sign: Date: Inspector Sign: