PRIORITY INSPECTION REPORT
BUILDING INFORMATION
SFM FILE NUMBER: 129309-41-04-61-0006-10001 JURISDICTION: Life Safety North
BARRACKS/KITCHEN/OF
BUILDING OWNER: BUILDING NAME: FICE
BUILDING ADDRESS: 7540 ORO ANGOR HIGHWAY, BANGOR, CA 95914
INSPECTION INFORMATION
Inspection Number : 216257 Inspection Type: Annual
Inspection Date : 04/09/2025 Inspection Status : Failed
Inspector: Keith Hard
Inspector Signature:
Inspection Comments: 08 APRIL 2025 ANNUAL INSPECTION. DEFICIENCIES NOTED AND CITED BY
INSPECTION REPORT. OSFM FOLLOW UP INSPECTION IN 30 DAYS.
Total Inspectable Items: 20
Inspectable Items: EGRESS/EXITING, ELECTRICAL HAZARDS, FACILITY ADDRESS, FIRE ALARM
INITIATITING DEVICES, FIRE ALARM NOTIFICATION DEVICES, FIRE DEPARTMENT
ACCESS, FIRE DEPARTMENT CONNECTION (FDC), FIRE HYDRANTS, FIRE PUMP,
UTILITY IDENTIFICATION, WATER HEATER HAZARDS, PORTABLE FIRE
EXTINGUISHERS, DRYER HAZARDS, LABELING, FIRE ALARM CONTROL PANEL
(FACP), FIRE RISER, FIRE SPRINKLERS, HAZARD SIGNAGE, OCCUPANT
SMOKE/CARBON-MONOXIDE DETECTORS, SAFETY DATA SHEET (SDS)
Accompanied By: ARMANDO ALVAREZ Title: CAL FIRE CAPTAIN
Discussed With: ARMANDO ALVAREZ Title: CAL FIRE CAPTAIN
Accompanied By: -r- ,otn,cep- evLoGr-eeg
Signed: 04/14/2025
COMMENTS OR QUESTIONS ABOUT INSPECTION SERVICES
Please contact CAL Fire Life Safety North at (916) 568-3801 for assistance.
Page 1 of 8
�,}O0.NIR pERRTMEN} DEPARTMENT OF FORESTRY AND FIRE PROTECTION
0pCAL}Ems
OFFICE OF THE STATE FIRE MARSHAL
FIRE Fire and Life Safety Division
SINCE 1885
2251 Harvard Street, Suite 130, Sacramento, CA 95815
(916) 568-3801
PRIORITY INSPECTION REPORT
Violation Name: MODIFIED OR DAMAGED
Violation Code: 2022 CFC - 603.2.1
Location: KITCHEN
Violation Comments: Electrical wiring, devices, equipment and appliances that are modified or damaged, and
constitute an electrical shock or fire hazard, shall not be used until repaired or replaced
in accordance with this code and the California Electrical Code.
KITCHEN AREA GFCI ELECTRICAL RECEPTACLE INOPERATIVE AND SHALL BE
REPLACED.
Inspectable Items:
Comments: KITCHEN AREA
COMMENTS OR QUESTIONS ABOUT INSPECTION SERVICES
Please contact CAL Fire Life Safety North at (916) 568-3801 for assistance.
Page 2 of 8
�,}O0.NIR pERRTMEN} DEPARTMENT OF FORESTRY AND FIRE PROTECTION
0pCAL}Ems
OFFICE OF THE STATE FIRE MARSHAL
FIRE Fire and Life Safety Division
SINCE 1885
2251 Harvard Street, Suite 130, Sacramento, CA 95815
(916) 568-3801
PRIORITY INSPECTION REPORT
Violation Name: MODIFIED OR DAMAGED
Violation Code: 2022 CFC - 603.2.1
Location: KITCHEN
Violation Comments: Electrical wiring, devices, equipment and appliances that are modified or damaged, and
constitute an electrical shock or fire hazard, shall not be used until repaired or replaced
in accordance with this code and the California Electrical Code.
KITCHEN AREA GFCI ELECTRICAL RECEPTACLE INOPERATIVE AND SHALL BE
REPLACED.
Inspectable Items:
4--
' 1
atio"-ewe
Comments: KITCHEN AREA GFCI ELECTRICAL RECEPTACLE
COMMENTS OR QUESTIONS ABOUT INSPECTION SERVICES
Please contact CAL Fire Life Safety North at (916) 568-3801 for assistance.
Page 3 of 8
�,}O0.NIR pERRTMEN} DEPARTMENT OF FORESTRY AND FIRE PROTECTION
0pCAL}Ems
OFFICE OF THE STATE FIRE MARSHAL
FIRE Fire and Life Safety Division
SINCE 1885
2251 Harvard Street, Suite 130, Sacramento, CA 95815
(916) 568-3801
PRIORITY INSPECTION REPORT
Violation Name: MODIFIED OR DAMAGED
Violation Code: 2022 CFC - 603.2.1
Location: FIREFIGHTER BATHROOM
Violation Comments: Electrical wiring, devices, equipment and appliances that are modified or damaged, and
constitute an electrical shock or fire hazard, shall not be used until repaired or replaced
in accordance with this code and the California Electrical Code.
FIREFIGHTER BATHROOM GFCI ELECTRICAL RECEPTACLE INOPERATIVE AND
SHALL BE REPLACED.
Inspectable Items:
Ula
--r
Comments: FIREFIGHTER BATHROOM
COMMENTS OR QUESTIONS ABOUT INSPECTION SERVICES
Please contact CAL Fire Life Safety North at (916) 568-3801 for assistance.
Page 4 of 8
�,}O0.NIR pERRTMEN} DEPARTMENT OF FORESTRY AND FIRE PROTECTION
0pCAL}Ems
OFFICE OF THE STATE FIRE MARSHAL
FIRE Fire and Life Safety Division
SINCE 1885
2251 Harvard Street, Suite 130, Sacramento, CA 95815
(916) 568-3801
PRIORITY INSPECTION REPORT
Violation Name: MODIFIED OR DAMAGED
Violation Code: 2022 CFC - 603.2.1
Location: FIREFIGHTER BATHROOM
Violation Comments: Electrical wiring, devices, equipment and appliances that are modified or damaged, and
constitute an electrical shock or fire hazard, shall not be used until repaired or replaced
in accordance with this code and the California Electrical Code.
FIREFIGHTER BATHROOM GFCI ELECTRICAL RECEPTACLE INOPERATIVE AND
SHALL BE REPLACED.
Inspectable Items:
Comments: FIREFIGHTER BATHROOM GFCI ELECTRICAL
RECEPTACLE
COMMENTS OR QUESTIONS ABOUT INSPECTION SERVICES
Please contact CAL Fire Life Safety North at (916) 568-3801 for assistance.
Page 5 of 8
d,lrvrclN} DEPARTMENT OF FORESTRY AND FIRE PROTECTION
0pCAL OFFICE OF THE STATE FIRE MARSHAL
FIRE Fire and Life Safety Division
SINCE 1885
2251 Harvard Street, Suite 130, Sacramento, CA 95815
(916) 568-3801
PRIORITY INSPECTION REPORT
Violation Name: COMBINATION ALARMS
Violation Code: 2022 CFC -915.4.5
Location: KITCHEN/DAY ROOM AREA
Violation Comments: Combination carbon monoxide/smoke alarms shall be an acceptable alternative to
carbon monoxide alarms. Combination carbon monoxide/smoke alarms shall be listed in
accordance with UL 217 and UL 2034.
Combination carbon monoxide/smoke alarms shall comply with Section 915, and all
requirements for listing and approval by the Office of the State Fire Marshal for smoke
alarms.
PROVIDE (1) ONE COMBINATION SMOKE/CARBON-MONOXIDE DETECTOR
FORKITCHEN/DAY ROOM AREA.
Inspectable Items:
Comments: KITCHEN/DAY ROOM AREA
COMMENTS OR QUESTIONS ABOUT INSPECTION SERVICES
Please contact CAL Fire Life Safety North at (916) 568-3801 for assistance.
Page 6 of 8
d,lr.�pERRTMEN} DEPARTMENT OF FORESTRY AND FIRE PROTECTION
`�pECAL�}Ems
OFFICE OF THE STATE FIRE MARSHAL
FIRE Fire and Life Safety Division
SINCE 1885
2251 Harvard Street, Suite 130, Sacramento, CA 95815
(916) 568-3801
PRIORITY INSPECTION REPORT
Violation Name: IDENTIFICATION OF VALVES
Violation Code: 2022 NFPA 13 - 16.9.11.1
Location: EXTERIOR FIRE WATER TANK
Violation Comments: All control, drain, venting, and test connection valves shall be provided with permanently
marked weatherproof metal or rigid plastic identification signs.
PROVIDE APPROPRIATE VALVE IDENTIFICATION AS "NORMALLY OPEN" OR
"NORMALLY CLOSED".
Inspectable Items:
i
Comments: EXTERIOR FIRE WATER TANK
COMMENTS OR QUESTIONS ABOUT INSPECTION SERVICES
Please contact CAL Fire Life Safety North at (916) 568-3801 for assistance.
Page 7 of 8
d,lr.�pERRTMEN} DEPARTMENT OF FORESTRY AND FIRE PROTECTION
`�pECAL�}Ems
OFFICE OF THE STATE FIRE MARSHAL
FIRE Fire and Life Safety Division
SINCE 1885
2251 Harvard Street, Suite 130, Sacramento, CA 95815
(916) 568-3801
PRIORITY INSPECTION REPORT
Violation Name: IDENTIFICATION OF VALVES
Violation Code: 2022 NFPA 13 - 16.9.11.1
Location: EXTERIOR FIRE WATER TANK
Violation Comments: All control, drain, venting, and test connection valves shall be provided with permanently
marked weatherproof metal or rigid plastic identification signs.
PROVIDE APPROPRIATE VALVE IDENTIFICATION AS "NORMALLY OPEN" OR
"NORMALLY CLOSED".
Inspectable Items: 7etiC�
Ar
,,,*„, .,,4 '1"1:1 "-! I
Comments: EXTERIOR FIRE WATER TANK SPRINKLER SUPPLY
VALVE
COMMENTS OR QUESTIONS ABOUT INSPECTION SERVICES
Please contact CAL Fire Life Safety North at (916) 568-3801 for assistance.