HomeMy WebLinkAboutFAI20-0026 010-180-035 CF FA 2024 Wilson Elementary Fire Alarm and Life Safety System
Inspection Certificate
For
Wilson Elementary School
429 Magnolia Street
Gridley, CA 95948
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages
of this report provide performance measurements, listed ranges of acceptable results, and complete
documentation of the inspection. Whenever discrepancies exist between acceptable performance
standards and actual test results, notes and/or recommended solutions have been proposed or provided
for immediate review and approval.
Annual Inspection
Inspection Date
Aug 15, 2024
Building:Wilson Elementary School Company: Hue&Cry,Inc.
Contact:Jordan Reeves Contact:Nick Kuykendall
Title: Superintendent Title: INSPECTOR/TECHNICIAN
Fire Alarm Testing Report
Executive Summary
Generated by:BuildingReports.com
Building Information
Building: Wilson Elementary School Contact: Jordan Reeves
Address: 429 Magnolia Street Phone: 1-530-846-4721
Address: Fax:
City/State/ZIP Code: Gridley, CA 95948 Mobile:
Country: United States of America Email:jreeves@gusd.org
Inspection Performed By
Company: Hue&Cry, Inc. Inspector: Nick Kuykendall
Address: 1751 Bruce Drive Phone: 800-800-alarm
Address: Fax:
City/State/ZIP Code:Anderson, California 96007 Mobile:
Country: United States of America Email: n.kuykendall@hueandcry.com
System Control Unit
Manufacturer: Honeywell Inspection Date: 08/15/2024 IDC Style:
Model Number: 6820 EVS Install Date: 01/30/2005 SLC Style:
Software Version: Version Date: 11/20/2018 NAC Style:
Location: Custodian Room Current Protection: Breaker
Disconnect Location: Custodian Room Type: Breaker
Hue&Cry,Inc. Page 2 of 16 Download Date:08/16/2024
Executive Summary
Inspection Summary
Total Items Serviced Passed Failed/Other
Category:
Qty % Qty % Qty % Qty %
Control 15 14.85% 15 100.00% 14 93.33% 1 6.67%
Indicating 41 40.59% 41 100.00% 40 97.56% 1 2.44%
Initiating 45 44.55% 45 100.00% 45 100.00% 0 0.00%
Totals 101 100% 101 100.00% 99 98.02% 2 1.98%
Certification
Company: Hue&Cry, Inc. Building:Wilson Elementary School
Inspector: Nick Kuykendall Contact: Jordan Reeves
Signed: Aug 15, 2024 Signed:
Nick Kuykendall Certifications
Certification Type Number
C-10 Electrical Licensed Contractor 620587
Hue&Cry,Inc. Page 3 of 16 Download Date:08/16/2024
Executive Summary
Discrepancy Report
Generated by:BuildingReports.com
Building: Wilson Elementary School ontro1 Panel: 1
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where
appropriate, code references are listed for your convenience.Any item that was inspected that is subject to a recall or part
of a manufacturer's replacement/upgrade program is included.
evice Type Manufacture ModelNumbe' Date Qty
Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScaniD Location Problem Address Reference
Control
Battery
1 44834484 FACP (L) Failed Test 1 NFPA72 Table
14.4.3.2 (9)c(1)
Indicating
Horn/Strobe
1 11531289 Cafe North EOL 3.9k 27v Damaged/Worn 1 NFPA72 14.2.2.2.2
Code References
NFPA72 Table 14.4.3.2(9)cBatteries shall be replaced in accordance with the recommendations of the alarm equipment
(1) manufacturer or when the recharged battery voltage or current falls below the manufacturer's
recommendations
NFPA72 14.2.2.2.2 System deficiencies shall be corrected.
Hue&Cry,Inc. Page 4 of 16 Download Date:08/16/2024
Discrepancy Report
Proposed Solutions Report
Generated by:BuildingReports.com
Building: Wilson Elementary School Control Panel: 1
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report.Provide a check
mark where indicated to approve repairs listed within the report.Items listed as T/M are available for repair on a Time
and Materials basis.
ScaniD Locati ix
Control
Battery
44834484 FACP(L) Replace Battery DURA12-8F2 T/M ❑
Indicating
Horn/Strobe
11531289 Cafe North EOL 3.9k 27v Replace GX90s-4-15 T/M ❑
/75WR
PO#: (none) T/M
Hue&Cry,Inc. Page 5 of 16 Download Date:08/16/2024
Proposed Solutions Report
Notes & Recommendations
Generated by:BuildingReports.com
Building: Wilson Elementary School
The Notes&Recommendations Report details additional inspection notes made by the Inspectors during the course of the
building inspection.Notes are grouped by Category.
General Note
Horn/strobe in cafeteria damaged and needs to be replaced
Batteries in FACP need to be replaced (only one battery passed/recommend replacing both) 12v7ah x2
Ed White(contact for service):
Personal 530-403-7841 /Work 530-470-3118
Hue&Cry,Inc. Page 6 of 16 Download Date:08/16/2024
Notes&Recommendations
Inspection & Testing
Generated by:BuildingReports.com
Building: Wilson Elementary School Control Panel: 1
The Inspection& Testing section lists all of the items inspected in your building.Items are grouped by Passed or
Failed/Other.Items are listed by Category. Each item includes the services performed, and the time&date at which testing
occurred.
Device Type Location Service Time Date
Passed
Control
Annunciator Office Annual 8:10:58 AM 08/15/2024
Battery Power Supply Kitchen Annual 10:14:45 AM 08/15/2024
Battery EVS Amplifier(L) Annual 8:47:10 AM 08/15/2024
Battery EVS Amplifier(R) Annual 8:49:51 AM 08/15/2024
Battery FACP(R) Annual 8:01:52 AM 08/15/2024
Battery Room 22 Power Supply(L) Annual 8:52:34 AM 08/15/2024
Battery Room 22 Power Supply(R) Annual 8:54:04 AM 08/15/2024
Disconnect Janitors Room Main Hall Annual 10:34:14 AM 08/15/2024
Disconnect Kitchen Circuit Panel B#12 Annual 10:15:53 AM 08/15/2024
Disconnect Room 22 Annual 10:15:59 AM 08/15/2024
Power Supply Kitchen Annual 10:14:32 AM 08/15/2024
Power Supply Room 22 Annual 8:51:51 AM 08/15/2024
Power Supply Room 22 EVS Amplifier Annual 8:46:59 AM 08/15/2024
Indicating
Horn Library Outside Annual 10:53:14 AM 08/15/2024
Horn Main Hall Room 16 Annual 10:53:10 AM 08/15/2024
Horn Main Hall Rooms 11-12 Annual 10:53:03 AM 08/15/2024
Horn Main Hall at Janitors Room Annual 10:53:06 AM 08/15/2024
Horn Outside Room 21 Annual 10:53:22 AM 08/15/2024
Horn Outside Room 26 Annual 10:54:58 AM 08/15/2024
Horn Outside Room 32 Annual 10:55:01 AM 08/15/2024
Horn Outside Room 35 Annual 10:55:04 AM 08/15/2024
Horn Outside Rooms 19-20 Annual 10:53:17 AM 08/15/2024
Horn Room 36. EOL 3.9k 27v Annual 10:55:38 AM 08/15/2024
Horn Room 25 Annual 10:54:51 AM 08/15/2024
Horn Room 26 Annual 10:54:55 AM 08/15/2024
Horn Room 30 Annual 10:55:51 AM 08/15/2024
Horn Room 31 Annual 10:55:48 AM 08/15/2024
Horn Room 32 Annual 10:55:45 AM 08/15/2024
Hue&Cry,Inc. Page 7 of 16 Download Date:08/16/2024
Inspection&Testing
Device Type Location Service Time Date
Passed
Horn Room 33 Annual 10:55:42 AM 08/15/2024
Horn Room 34 Annual 10:55:07 AM 08/15/2024
Horn Room 35 Annual 10:55:35 AM 08/15/2024
Horn/Strobe Cafe South Annual 10:55:54 AM 08/15/2024
Speaker Outside Room 17 Annual 10:52:57 AM 08/15/2024
Speaker Outside Room 19 Annual 10:52:53 AM 08/15/2024
Speaker/Strobe Boys Restroom Annual 10:51:54 AM 08/15/2024
Speaker/Strobe Girls Restroom Annual 10:51:57 AM 08/15/2024
Speaker/Strobe Room 17 Annual 10:52:28 AM 08/15/2024
Speaker/Strobe Room 17 Annual 10:52:32 AM 08/15/2024
Speaker/Strobe Room 18 Annual 10:52:21 AM 08/15/2024
Speaker/Strobe Room 19 Annual 10:52:07 AM 08/15/2024
Speaker/Strobe Room 20 Annual 10:52:04 AM 08/15/2024
Speaker/Strobe Room 21 Annual 10:52:00 AM 08/15/2024
Speaker/Strobe Room 22 Annual 10:51:50 AM 08/15/2024
Speaker/Strobe Staff Restroom Annual 10:52:46 AM 08/15/2024
Speaker/Strobe Staff Restroom Annual 10:52:49 AM 08/15/2024
Speaker/Strobe Storage Annual 10:52:43 AM 08/15/2024
Speaker/Strobe Office Room 17 Annual 10:52:36 AM 08/15/2024
Speaker/Strobe Restroom Room 17 Annual 10:52:39 AM 08/15/2024
Strobe Boys R/R by Room 33 Annual 10:51:38 AM 08/15/2024
Strobe Girls R/R by Room 33 Annual 10:51:32 AM 08/15/2024
Strobe Girls R/R by Room 33 Annual 10:51:41 AM 08/15/2024
Strobe Handicap R/R by Room 33 Annual 10:51:35 AM 08/15/2024
Strobe Kitchen Annual 10:51:44 AM 08/15/2024
Initiating
Heat Detector Room 17 Annual 10:33:18 AM 08/15/2024
Heat Detector Room 18 Annual 9:48:35 AM 08/15/2024
Heat Detector Room 18 Annual 9:48:45 AM 08/15/2024
Heat Detector Room 19 Annual 9:48:32 AM 08/15/2024
Heat Detector Room 20 Annual 9:48:29 AM 08/15/2024
Heat Detector Room 21 Annual 9:48:26 AM 08/15/2024
Heat Detector Room 22 Annual 9:48:20 AM 08/15/2024
Heat Detector Restroom Room 17 Annual 10:33:22 AM 08/15/2024
Pull Station Cafe North Annual 10:09:42 AM 08/15/2024
Pull Station Cafe South Annual 10:13:08 AM 08/15/2024
Pull Station Main Hall North Doors Annual 8:16:18 AM 08/15/2024
Hue&Cry,Inc. Page 8 of 16 Download Date:08/16/2024
Inspection&Testing
Device Type Location Service Time Date
Passed
Pull Station Main Hall Office Annual 8:18:46 AM 08/15/2024
Pull Station Main Hall Room 14B Annual 8:32:02 AM 08/15/2024
Pull Station Main Hall South End Annual 8:34:00 AM 08/15/2024
Pull Station Office Annual 8:14:00 AM 08/15/2024
Pull Station Room 24 Annual 8:42:27 AM 08/15/2024
Pull Station Room 25 Annual 8:39:50 AM 08/15/2024
Pull Station Room 26 Annual 8:38:23 AM 08/15/2024
Pull Station Room 30 Annual 9:47:58 AM 08/15/2024
Pull Station Room 31 Annual 9:50:05 AM 08/15/2024
Pull Station Room 32 Annual 9:51:42 AM 08/15/2024
Pull Station Room 33 Annual 9:52:50 AM 08/15/2024
Pull Station Room 34 Annual 9:55:35 AM 08/15/2024
Pull Station Room 35 Annual 9:56:41 AM 08/15/2024
Pull Station Room 36 Annual 9:57:46 AM 08/15/2024
Smoke Detector All-Gender Restroom Annual 9:06:15 AM 08/15/2024
Smoke Detector Boys Restroom Annual 9:07:42 AM 08/15/2024
Smoke Detector Girls Restroom Annual 9:07:44 AM 08/15/2024
Smoke Detector Room 17 Annual 10:21:25 AM 08/15/2024
Smoke Detector Room 17 Annual 10:21:28 AM 08/15/2024
Smoke Detector Room 18 Annual 9:00:05 AM 08/15/2024
Smoke Detector Room 18 Annual 9:01:40 AM 08/15/2024
Smoke Detector Room 19 Annual 9:00:02 AM 08/15/2024
Smoke Detector Room 19 Annual 9:01:50 AM 08/15/2024
Smoke Detector Room 20 Annual 8:58:01 AM 08/15/2024
Smoke Detector Room 20 Annual 8:58:04 AM 08/15/2024
Smoke Detector Room 21 Annual 8:55:58 AM 08/15/2024
Smoke Detector Room 21 Annual 8:57:54 AM 08/15/2024
Smoke Detector Room 22 Annual 8:45:48 AM 08/15/2024
Smoke Detector Room22 Annual 8:45:56 AM 08/15/2024
Smoke Detector Staff Restroom Annual 9:05:13 AM 08/15/2024
Smoke Detector Storage Annual 10:21:31 AM 08/15/2024
Smoke Detector Work room Annual 10:21:36 AM 08/15/2024
Smoke Detector Custodian Room Annual 8:45:36 AM 08/15/2024
Smoke Detector Office Room 17 Annual 10:21:22 AM 08/15/2024
Device Type Location Service Time Date
Failed/Other
Control
Hue&Cry,Inc. Page 9 of 16 Download Date:08/16/2024
Inspection&Testing
Device Type Location Service Time Date
Failed/Other
1 Battery FACP(L) Annual 8:01:49 AM 08/15/2024
Indicating
1 Horn/Strobe Cafe North EOL 3.9k 27v Annual 10:12:07 AM 08/15/2024
Hue&Cry,Inc. Page 10 of 16 Download Date:08/16/2024
Inspection&Testing
Building: Wilson Elementary School Control Panel: 2 - Honeywell 6820 EVS
The Inspection& Testing section lists all of the items inspected in your building.Items are grouped by Passed or
Failed/Other.Items are listed by Category.Each item includes the services performed, and the time&date at which testing
occurred.
Device Type ocation ervice to
Passed
Control
Control Panel Custodian Room Annual 7:51:03 AM 08/15/2024
Hue&Cry,Inc. Page 11 of 16 Download Date:08/16/2024
Inspection&Testing
Service Summary
Generated by:BuildingReports.com
Building: Wilson Elementary School
The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Failed/Other
Battery Annual 1
Horn/Strobe Annual 1
Total 2
Passed
Annunciator Annual 1
Battery Annual 6
Control Panel Annual 1
Disconnect Annual 3
Heat Detector Annual 8
Horn/Strobe Annual 1
Horn Annual 18
Power Supply Annual 3
Pull Station Annual 17
Smoke Detector Annual 20
Speaker/Strobe Annual 14
Speaker Annual 2
Strobe Annual 5
Total 99
Grand Total 101
Hue&Cry,Inc. Page 12 of 16 Download Date:08/16/2024
Service Summary
Auxiliary Functions Testing
Generated by:BuildingReports.com
Building: Wilson Elementary School Control Panel: 1
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are
controlled by the system control unit.Items are grouped by Passed or Failed/Other. The items are listed by device type,
and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScaniD Simulated
Passed
Smoke Detector
Smoke Compartment All-Gender Restroom Passed 44834486
Smoke Compartment Boys Restroom Passed 44834527
Smoke Compartment Girls Restroom Passed 44834526
Smoke Compartment Room 17 Passed 44834501
Smoke Compartment Room 17 Passed 44834500
Smoke Compartment Room 18 Passed 44834510
Smoke Compartment Room 18 Passed 44834499
Smoke Compartment Room 19 Passed 44834515
Smoke Compartment Room 19 Passed 448314
Smoke Compartment Room 20 Passed 44834520
Smoke Compartment Room 20 Passed 44834518
Smoke Compartment Room 21 Passed 44834521
Smoke Compartment Room 21 Passed 4623
Smoke Compartment Room 22 Passed 44834539
Smoke Compartment Room22 Passed 44834538
Smoke Compartment Staff Restroom Passed 44834488
Smoke Compartment Storage Passed 44834491
Smoke Compartment Work room Passed 44834481
Smoke Compartment Custodian Room Passed 60675142
Smoke Compartment Office Room 17 Passed 44834506
Hue&Cry,Inc. Page 13 of 16 Download Date:08/16/2024
Auxiliary Functions Testing
Battery & Power Supply Testing
Generated by:BuildingReports.com
Building: Wilson Elementary School Control Panel: 1
The Battery&Power Supply Testing section details the readings and measurements of batteries and power supplies used
to provide power to the fire alarm and life safety systems.Items are grouped by Passed or Failed/Other.
Rated Rated Post
Type Location Ah Volts Pre Test Test Min Ah Tested Ah
Battery
Passed
Sealed Lead Acid Power Supply Kitchen 7 12
Sealed Lead Acid EVS Amplifier(L) 7 12
Sealed Lead Acid EVS Amplifier(R) 7 12
Sealed Lead Acid FACP(R) 8 12 12.87 4.55 4.8
Sealed Lead Acid Room 22 Power Supply(L) 8 12
Sealed Lead Acid Room 22 Power Supply(R) 8 12
Failed/Other
Sealed Lead Acid FACP(L) 8 12 12.93 4.55 4.4
Hue&Cry,Inc. Page 14 of 16 Download Date:08/16/2024
Battery&Power Supply Testing
Inventory & Warranty Report
Generated by:BuildingReports.com
Building: Wilson Elementary School Control Panel: 1
The Inventory& Warranty Report lists each of the devices and items that are included in your Inspection Report.A
complete inventory count by device type and category is provided.Items installed within the last 90 days, within the last
year, and devices installed for two years or more are grouped together.for easy reference.
Device or Type Catego %of Inventory Quantity
Annunciator Control 0.99% 1
Battery Control 6.93% 7
Control Panel Control 0.99% 1
Disconnect Control 2.97% 3
Heat Detector Initiating 7.92% 8
Horn Indicating 17.82% 18
Horn/Strobe Indicating 1.98% 2
Power Supply Control 2.97% 3
Pull Station Initiating 16.83% 17
Smoke Detector Initiating 19.80% 20
Speaker Indicating 1.98% 2
Speaker/Strobe Indicating 13.86% 14
Strobe Indicating 4.95% 5
Type Qty Model# Description Install Date
In Service - 90 Days - 1 Year
Power Sonic
Battery 2 PS-1270 F1 Sealed Lead Acid 08/18/2023
In Service - 1 Year to 2 Years
Precision Consumer P
Battery 2 B LA12V 7.0A Sealed Lead Acid 05/10/2023
In Service- 3 Years to 5 Years
Power-Sonic
Battery 1 PS-1270 F1 Sealed Lead Acid 11/24/2020
Duracell
Battery 2 DURA12-8F2 Sealed Lead Acid 04/30/2020
In Service- 15 Years to 25 Years
GE
Disconnect 1 20amp Breaker 01/31/2005
Disconnect 1 Breaker 01/30/2005
FCI
Horn 9 130-3117c 01/30/2005
Pull Station 9 MS-2 Dual Action 01/30/2005
FIRE•LITE Alarms, In
Hue&Cry,Inc. Page 15 of 16 Download Date:08/16/2024
Inventory&Warranty Report
Pull Station 1 BG-8 Dual Action 01/30/2005
Faraday
Horn 1 01/30/2005
Fire-Lite
Pull Station 2 BG10 Dual Action 01/30/2005
Gentex
Horn/Strobe 2 GX90s-4-15/75WR 01/30/2005
Strobe 1 GXS-4-15/75WR 01/30/2005
Honeywell
Power Supply 1 EVS-50W 01/30/2005
Smoke Detector 1 SK-Fire-Co Combination 01/30/2005
Smoke Detector 19 SK- Photo Photoelectric 01/30/2005
Silent Knight
Annunciator 1 RA-1000R LCD Display 01/30/2005
Heat Detector 8 SK-HEAT-HT Fixed Temperature 01/30/2005
Power Supply 1 5496 01/30/2005
Standard
Horn 5 14 01/30/2005
Power Supply 1 Fire Lite Box Only 01/30/2005
Pull Station 5 750 Single Action 01/30/2005
System Sensor
Speaker 2 SPWK 01/30/2005
Speaker/Strobe 2 SPSCRL 01/30/2005
Speaker/Strobe 12 SPSRL 01/30/2005
Wheelock
Horn 3 MT 12/24 01/30/2005
Strobe 4 RS-241575 01/30/2005
Zinsco
Disconnect 1 20amp Breaker 01/30/2005
Building: Wilson Elementary School Control Panel: 2 - Honeywell 6820 EVS
The Inventory& Warranty Report lists each of the devices and items that are included in your Inspection Report.A
complete inventory count by device type and category is provided.Items installed within the last 90 days, within the last
year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Model# Description Install Date
In Service- 15 Years to 25 Years
Honeywell
Control Panel 1 6820 EVS Conventional 01/30/2005
Hue&Cry,Inc. Page 16 of 16 Download Date:08/16/2024
Inventory&Warranty Report