HomeMy WebLinkAboutFAI21-0014 078-240-023 CF FA OUHSD Las Plumas 1700 WING FA 4.3.24 ALARM AND DETECTION REPORT Page 1 of 5
VOLTAG PECIALisTs
530-624-4514
C101C16 License#880862 www.VoltageSpecialists.com Inspection # 1-008
ALARM & DETECTION EQUIPMENT TEST REPORT
Type of Inspection: ANNUAL Date: 4/3/24
Site: LAS PLUMAS HIGH - 1700 WING Customer: OROVILLE UNION HIGH SCHOOL DISTRICT
Street: 2380 LAS PLUMAS Contact: Jim LaGrone
City/State: OROVILLE, CA Phone#: 530-682-0444
Fax#:
1. Before Test Notify Proper Authorities: Name Phone #
A. Owner or Owner's Rep Jim LaGrone 530-682-0444
B. Fire Department OROVILLE FIRE DEPARTMENT 530-538-6460
C. Central Station
D. Central Station Acct#
2. Control Panel Status Yes No Note #
A. Is the system monitored by Central Station? I X
On Test Time: Return to Service Time:
B. Is the Power Light on? X
C. Does the Panel indicate Normal conditions? X
D. Are all indicating Lamp Bulbs in Operator order? X
E. Does the Trouble Light operate? X
F. Does the Silence Switch Operate? X
G. Battery A.H.8 Date Batteries Installed: 2/24/17
H. Does the Panel have Non-Operational Zones? X
I. Does the Panel have Battery Backup? X
J. Do the batteries indicate they are Properly Charged? X
Condition of Batteries: Note#1
Battery Voltage with AC Power: Battery Voltage without AC Power:
K. List any trouble conditions on panel before test: Note#
Note#
Comments: Note#
Note#
3. FACP Manufacturer: SILENT KNIGHT Model# 5207 System Type: HARDWIRE
Location of Annunciators:
Location of Primary Power Source:Back of Portable Panel# 1204 Breaker 6
Comments: Note#
Note#
FCPS: Manufacturer: Model# Panel/Breaker# Location:
Battery Voltage with A/C Power: w/o A/C Power Date:
FCPS: Manufacturer: Model# Panel/Breaker# Location:
Battery Voltage with A/C Power: w/o A/C Power Date:
FCPS: Manufacturer: Model# Panel/Breaker# Location:
Battery Voltage with A/C Power: w/o A/C Power Date:
Owner/Rep: Phone#: Date:
Inspector: Wyatt C. Phone#: 530 362 2609 Date:4/3/24
Owners Rep Sign: Date:4/3/24 Inspector Sign:
ALARM AND DETECTION REPORT Page 2 of 5
Property Site: LAS PLUMAS HIGH - 1700 WING
Operational
#Tested
This
Equipment Total# Report Yes N/A Note#
4. Remote Annunciators
5. Zones 5 5 X
6. Manual Stations (Pull)
Hardwire 1 1 X
Addressable
7. Detectors
Photoelectric 8 8 X
Ionization
Heats/Fixed or R of R 20 20 X
Flame
Duct(See#15)
8. Horn/Strobe 4 4 X
Strobe Only 4 4 X
Bell
Speakers
Horn 2 2 X
9.
10. Automatic Door Release X
11. Water Flow switches X
Did W/F Ring Outside Bell? X
Did W/F Activate Alarm Panel? X
12. Tamper Switches X
13. PIV X
OS &Y X
14.
15. Did test of Duct Detectors shut down air handling units? X
16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line) receive signal? X
17. Is system reset for normal conditions?
18. Is system restored to operational service?
19. Have Proper Authorities (see#1)been notified system is back in service?
List Proper Authorities:Oroville Fire
20. Indicate %of equipment tested this report 25% 50% 75% VJI00%
21. Indicate %of equipment tested YTD 25% 50% 75% 100%
Comments for any"no"answers or explanations (Note#):
4/3/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Page 3 of 5
Property Site: LAS PLUMAS HIGH - 1700 WING
DEVICE zone or SLC DEVICE
#
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
HT ROOM 1704 AC X 3-3
HT ROOM 1704 AC X 3-4
HT ROOM 1704 AC X 3-5
HT ROOM 1704 AC X 3-6
HT ROOM 1703 AC X 4-4
HT ROOM 1703 AC X 4-5
HT ROOM 1703 AC X 4-6
HT ROOM 1703 AC X 4-7
HT ROOM 1702 AC X 5-4
HT ROOM 1702 AC X 5-5
HT ROOM 1702 AC X 5-6
HT ROOM 1702 AC X 5-7
HT ROOM 1701 AC X 6-4
HT ROOM 1701 AC X 6-5
HT ROOM 1701 AC X 6-6
HT ROOM 1701 AC X 6-7
HT JANITORS X 8-1
HT STAFF RR X 8-2
HT BOYS RR X 8-3
HT GIRLS RR X 8-4
PS ROOM 1704 X 7-1
Owners Rep Sign: Date: 4/3/24 Inspector Sign:
p J
ALARM AND DETECTION REPORT LAS PLUMAS HIGH - 1700 WING Page 4 of 5
DEVICE Zone or DEVICE
SLC #
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
PSD ROOM 1704 X 3-1
PSD ROOM 1704 X 3-2
PSD ROOM 1703 X 4-1
PSD ROOM 1703 X 4-2
PSD ROOM 1702 X 5-1
PSD ROOM 1702 X 5-2
PSD ROOM 1701 X 6-1
PSD ROOM 1701 X 6-2
Owners Rep Sign: Date: 4/3/24 Inspector Sign: e
ALARM AND DETECTION REPORT LAS PLUMAS HIGH - 1700 WING Page 5 of 5
Zone or DEVICE
DEVICE SLC #
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
LEGEND
PSD—Photoelectric Smoke Detector BD—Beam Detector H—Horn V—Visual
ISD—Ionization Smoke Detector PS—Pull Station WPH—Weather Proof Horn TS—Tamper Switch
PDD—Photo Duct Smoke Detector RR—Rate of Rise Heat Detector C—Chime WF—Water Flow Switch
IDD—Ion Duct Smoke Detector HT—Fixed Temp Heat Detector CV—Chime Visual DH—Door Holder
DHS—Door Holder&Smoke Detector FD—Flame Detector S—Speaker OSY—Outside Stem&Yoke Tamper Valve
SSD—Signal Station Smoke Detector B—Bell AV—Audible Visual Ply—Post Indicator Valve
Cur-Elevator Curtains FRD-Fire Rolldown Door SDC Smoke Detector&Door Holder Combo
CO-Carbon Monoxide Detector - - -
NOTE # COMMENT
**See Discrepancy Report**
Discrepancies Found? VI Yes n No
See Discrepancy Report? L] Yes LI No
4/3/24
Owners Rep Sign: Date: Inspector Sign: