HomeMy WebLinkAboutFAI21-0014 078-240-023 CF FA OUHSD Las Plumas Ag Shop FA 4.5.24 ALARM AND DETECTION REPORT Page 1 of 7
VOLTAGE' SPEcIAusTs
530-624-4514
C101C16 License#880862 www.VoltageSpecialists.com Inspection # 1-008
ALARM & DETECTION EQUIPMENT TEST REPORT
Type of Inspection:ANNUAL Date: 4/5/24
Customer OROVILLE UNION HIGH SCHOOL DISTRICT
Site: LAS PLUMAS HIGH -AG SHOP
Street: 2380 LAS PLUMAS AVE Contact: Jim Lagrone
City/State: OROVILLE, CA Phone#: 530-682-0444
Fax#:
1. Before Test Notify Proper Authorities: Name Phone #
A. Owner or Owner's Rep Jim Lagrone 530-682-0444
B. Fire Department OROVILLE FIRE DEPARTMENT 520-538-6460
C. Central Station GSM 1-800-458-4519
D. Central Station Acct# MM0701
2. Control Panel Status Yes No Note #
A. Is the system monitored by Central Station? X
On Test Time: 3:30 Return to Service Time: 9:00
B. Is the Power Light on? X
C. Does the Panel indicate Normal conditions? X
D. Are all indicating Lamp Bulbs in Operator order? X
E. Does the Trouble Light operate? X
F. Does the Silence Switch Operate? X
G. Battery A.H. Date Batteries Installed:
H. Does the Panel have Non-Operational Zones? X
I. Does the Panel have Battery Backup? X
J. Do the batteries indicate they are Properly Charged? X
Condition of Batteries: Note#
Battery Voltage with AC Power: Battery Voltage without AC Power:
K. List any trouble conditions on panel before test: Note#
Note#
Comments: Note#
Note#
3. FACP Manufacturer: Silent Knight Model# 5820 System Type: HARDWIRE
Location of Annunciators:
Location of Primary Power Source:Main campus janitors closes Panel# x Breaker x
Comments: Note#
Note#
FCPS: Manufacturer: Silent Knight Model# 5496 Panel/Breaker# Location:Room 1011
1011/10
Battery Voltage with A/C Power: 27.47 w/o A/C Power 27.46 Date: 10/28/21
FCPS: Manufacturer: Silent Knight Model# 5895x1 Panel/Breaker# Location:Room 1011
1011/10 10/28/21
Battery Voltage with A/C Power: 27.44 w/o A/C Power 27.41 Date:
FCPS: Manufacturer: Silent Knight Model# 5895x1 Panel/Breaker# Location:Custodian room
Battery Voltage with A/C Power: 27.45 w/o A/C Power 27.42 Date: 10/28/21
Owner/Rep: Phone#: Date:
Inspector: Wyatt C. Phone#: 530-362-2609 Date:4/5/24
Owners Rep Sign: Date: Inspector Inspector Sign:
ALARM AND DETECTION REPORT Page 2 of 7
Property Site: LAS PLUMAS HIGH - AG SHOP
Operational
#Tested
This
Equipment Total# Report Yes N/A Note#
4. Remote Annunciators
5. Zones 9 9 X
6. Manual Stations (Pull)
Hardwire 14 14 X
Addressable
7. Detectors
Photoelectric 31 31 X
Ionization
Heats/Fixed or R of R 60 60 X
Flame
Duct(See#15) 9 9 X
8. Horn/Strobe 15 15 X
Strobe Only 17 17 X
Bell
Speakers
Horn 15 15 X
9.
10. Automatic Door Release X
11. Water Flow switches X
Did W/F Ring Outside Bell? X
Did W/F Activate Alarm Panel? X
12. Tamper Switches X
13. PIV X
OS &Y X
14.
15. Did test of Duct Detectors shut down air handling units? X
16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line) receive signal? X
17. Is system reset for normal conditions? X
18. Is system restored to operational service? X
19. Have Proper Authorities (see#1)been notified system is back in service? X
List Proper Authorities:Central Station
20. Indicate %of equipment tested this report 25% 50% 75% VJI00%
21. Indicate %of equipment tested YTD 25% 50% 75% 100%
Comments for any"no"answers or explanations (Note#):
4/5/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Page 3 of 7
Property Site: LAS PLUMAS HIGH - AG SHOP
DEVICE zone or SLC DEVICE
#
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
HT PORTABLE 1011 X 1 1
HT PORTABLE 1011 X 1 2
HT PORTABLE 1012 X 1 3
HT PORTABLE 1012 X 1 4
HT PORTABLE 1013 X 1 5
HT PORTABLE 1013 X 1 6
HT PORTABLE 1014 X 1 7
HT PORTABLE 1014 X 1 8
HT PORTABLE 1015 X 1 9
HT PORTABLE 1015 X 1 10
HT PORTABLE 1016 X 1 11
HT PORTABLE 1019 X 1 12
HT AG SHOP X 3 1
HT AG SHOP X 3 2
HT AG SHOP X 3 3
HT AG SHOP X 3 4
HT AG SHOP X 3 5
HT AG SHOP X 3 6
HT AG SHOP X 3 7
HT AG SHOP X 3 8
HT AG SHOP X 3 9
HT AG SHOP X 3 10
HT AG SHOP X 3 11
HT AG SHOP CLASSROOM AC X 3 12
HT AG SHOP CLASSROOM AC X 3 13
HT AG SHOP CLASSROOM AC X 3 14
HT AG SHOP CLASSROOM AC X 3 15
HT 2000 WING GIRLS RR X 5 1
HT 2000 WING GIRLS RR X 5 2
HT ROOM 2001 X 5 3
HT ROOM 2001 X 5 4
4/5/24
Sign:Owners RepDate: Inspector Sign:
p J
ALARM AND DETECTION REPORT LAS PLUMAS HIGH - AG SHOP Page 4 of 7
DEVICE zone or SLC DEVICE
#
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
HT ROOM 2001 X 5 5
HT 2000 WING BOYS RR X 6 1
HT 2000 WING BOYS RR X 6 2
HT ROOM 2001 X 6 3
HT ROOM 2001 X 6 4
HT ROOM 2001 X 6 5
HT BLDG 2000 AC ROOM 2001 X 7 1
HT BLDG 2000 AC ROOM 2001 X 7 2
HT BLDG 2000 AC ROOM 2001 X 7 3
HT BLDG 2000 AC ROOM 2001 X 7 4
HT BLDG 2000 PREP ROOM X 7 5
HT BLDG 2000 AC ROOM 2005 X 7 6
HT BLDG 2000 AC ROOM 2005 X 7 7
HT BLDG 2000 AC ROOM 2005 X 7 8
HT BLDG 2000 AC ROOM 2005 X 7 9
HT BLDG 2000 AC ROOM 2002 X 8 1
HT BLDG 2000 AC ROOM 2002 X 8 2
HT BLDG 2000 AC ROOM 2002 X 8 3
HT BLDG 2000 AC ROOM 2002 X 8 4
HT BLDG 2000 AC ROOM 2002 X 8 5
HT BLDG 2000 AC ROOM 2002 X 8 6
HT BLDG 2000 AC ROOM 2006 X 8 7
HT BLDG 2000 AC ROOM 2006 X 8 8
HT BLDG 2000 AC ROOM 2006 X 8 9
HT BLDG 2000 AC ROOM 2006 X 8 10
HT BLDG 2000 JANITORS ROOM X 8 11
HT BLDG 2000 JANITORS ROOM AC X 6 6
PDD ROOM 2001 AC X 9 1
PDD ROOM 2001 AC X 9 2
PDD ROOM 2001, 2002 PREP AREA AC X 9 3
PDD BLDG 2000 JANITORS ROOM AC X 10 1
PDD BLDG 2000 JANITORS ROOM AC X 10 2
4/5/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT LAS PLUMAS HIGH - AG SHOP Page 5 of 7
DEVICE zone or SLC DEVICE
#
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
PDD BLDG 2000 JANITORS ROOM AC X 10 3
PDD BLDG 2000 JANITORS ROOM AC X 10 4
PDD AG SHOP X 3 1
PDD AG SHOP X 3 2
PS PORTABLE 1011 X 2 1
PS PORTABLE 1013 X 2 2
PS PORTABLE 1014 X 2 3
PS PORTABLE 1015 X 2 4
PS PORTABLE 1016 X 2 5
PS PORTABLE 1017 X 2 6
PS PORTABLE 1018 X 2 7
PS PORTABLE 1019 X 2 8
PS AG SHOP X 3 1
PS AG SHOP X 3 2
PS ROOM 2001 X 4 1
PS ROOM 2002 X 4 2
PS ROOM 2005 X 4 3
PS ROOM 2006 X 4 4
PSD PORTABLE 1011 X 1 1
PSD PORTABLE 1011 X 1 2
PSD PORTABLE 1012 X 1 3
PSD PORTABLE 1012 X 1 4
PSD PORTABLE 1013 X 1 5
PSD PORTABLE 1013 X 1 6
PSD PORTABLE 1014 X 1 7
PSD PORTABLE 1014 X 1 8
PSD PORTABLE 1015 X 1 9
PSD PORTABLE 1015 X 1 10
PSD PORTABLE 1016 X 1 11
PSD PORTABLE 1016 X 1 12
PSD PORTABLE 1017 X 1 13
Owners Rep Sign: Date: 4/5/24 Inspector Sign:
ALARM AND DETECTION REPORT LAS PLUMAS HIGH - AG SHOP Page 6 of 7
DEVICE Zone or
DEVICE
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL #
PSD PORTABLE 1017 X 1 14
PSD PORTABLE 1018 X 1 15
PSD PORTABLE 1018 X 1 16
PSD PORTABLE 1019 X 1 17
PSD PORTABLE 1019 X 1 18
PSD CHEMICAL STORAGE X 3 1
PSD TOOL STORAGE X 3 2
PSD METAL SHOP OFFICE X 3 3
PSD AG SHOP TEACHERS X 3 4
PSD HALL BETWEEN AG & CLASSROOM X 3 5
PSD AG SHOP RESTROOM X 3 6
PSD AG SHOP RESTROOM X 3 7
PSD AG SHOP CLASSROOM X 3 8
PSD AG SHOP CLASSROOM X 3 9
PSD BLDG 2000 ROOM 2005 X 5 1
PSD BLDG 2000 ROOM 2005 X 5 2
PSD BLDG 2000 ROOM 2003 X 8 1
PSD BLDG 2000 ROOM 2003 X 8 2
HT Girls RR X 2 9
HT Boys RR X 3 16
4/5/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT LAS PLUMAS HIGH - AG SHOP Page 7 of 7
Zone or DEVICE
DEVICE SAC #
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
LEGEND
PSD—Photoelectric Smoke Detector BD—Beam Detector H—Horn V—Visual
ISD—Ionization Smoke Detector PS—Pull Station WPH—Weather Proof Horn TS—Tamper Switch
PDD—Photo Duct Smoke Detector RR—Rate of Rise Heat Detector C—Chime WF—Water Flow Switch
IDD—Ion Duct Smoke Detector HT—Fixed Temp Heat Detector CV—Chime Visual DH—Door Holder
DHS—Door Holder&Smoke Detector FD—Flame Detector S—Speaker OSY—Outside Stem&Yoke Tamper Valve
SSD—Signal Station Smoke Detector B—Bell AV—Audible Visual Ply—Post Indicator Valve
Cur-Elevator Curtains FRD-Fire Rolldown Door SDC Smoke Detector&Door Holder Combo
CO-Carbon Monoxide Detector - - -
NOTE # COMMENT
Discrepancies Found? n Yes VI No
See Discrepancy Report? n Yes 17 I No
4/5/24
Owners Rep Sign: Date: Inspector Sign: