HomeMy WebLinkAboutFAI20-0020 010-250-006 CF FA 3-13-24 ALARM AND DETECTION REPORT Page 1 of 5
..„
VOLTAGE\I%PECIALISTS
530-624-4514
610'fit6 Lic.nse 8660662 www.Voltag•Sp•cialists.com Inspection # 1-474
J
ALARM & DETECTION EQUIPMENT TEST REPORT
Type of Inspection: Annual Date: 3/13/24
Customer: Orchard Hospital Site: Main
Street: 240 Spruce Street Contact: Mike Newton
city/State: Gridley, CA. Phone#: 530-701-7687
Fax#:
1. Before Test Notify Proper Authorities: Name Phone #
A. Owner or Owner's Rep Mike Newton 530-701-7687
B. Fire Department Gridley Fire 846-5678
C. Central Station Central Station Monitoring 1-800-722-0364
D. Central Station Acct# #40-3704
2. Control Panel Status Yes No Note #
A. Is the system monitored by Central Station? X
On Test Time: 8:00 Return to Service Time: 10:00
".'4 B. Is the Power Light on? X
C. Does the Panel indicate Normal conditions? X
D. Are all indicating Lamp Bulbs in Operator order? X
E. Does the Trouble Light operate? X
F. Does the Silence Switch Operate? x
G. Battery A.H.18 Date Batteries Installed: 2021
H. Does the Panel have Non-Operational Zones? X
I. Does the Panel have Battery Backup? X
J. Do the batteries indicate they are Properly Charged? X
Condition of Batteries: Good Note#
Battery Voltage with AC Power: 27.40 Battery Voltage without AC Power: 27.35
K. List any trouble conditions on panel before test: Note#
Note#
Comments: Note#
Note#
3. FACP Manufacturer: Silent Knight Model# 5208 System Type: HARDWIRE
Location of Annunciators:
Location of Primary Power Source: Panel# Breaker
Comments: Note#
Note#
Silent Knight Model# 5496 Panel/Breaker# Location:Roof Penthouse
FCPS: Manufacturer: 9 P„4
Battery Voltage with A/C Power: 27.52 w/o A/C Power 27.50 Date: 8/17/23
FCPS: Manufacturer: Silent Knight Model# 5496 Panel/Breaker# Location:By FACP
N/A
Battery Voltage with NC Power: 27.45 w/o NC Power 27.12 Date: 6/22/23
FCPS: Manufacturer: Model# Panel/Breaker# Location:
‘,141.1I Battery Voltage with A/C Power: w/o A/C Power Date:
Owner/Rep: Phone#: Date:
Inspector Wyatt C. Phone#: 530-362-2609 Date:3/13/24
i Date:3/13/24 Inspector Sign: e - -
Owners Rep Sign:
ALARM AND DETECTION REPORT Page 2 of 5
Property Site: Main
Operational
•
#Tested
This
Equipment Total# Report Yes N/A Note#
4. Remote Annunciators
5. Zones
6. Manual Stations (Pull) •
Hardwire 10 10 X
Addressable
7. Detectors
Photoelectric 30 30 X
Ionization
Heats/Fixed or R of R
Flame
Duct (See#15) 8 8 X
8. Horn/Strobe
Strobe Only 10 10 X
Bell
Speakers
Horn
Chime 9 9 X
9.
Chime/Strobe 6 6 X
10. Automatic Door Release 9 9 X
11. Water Flow switches 1 1 X
Did WIF Ring Outside Bell?
Did WIF Activate Alarm Panel?
12. Tamper Switches 1 1 X
13. Ply
OS&Y
14.
15. Did test of Duct Detectors shut down air handling units? X
16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line)receive signal? X
17. Is system reset for normal conditions? X I
18. Is system restored to operational service? X I
19. Have Proper Authorities (see#1)been notified system is back in service? X
List Proper Authorities:Gridley Fire,Central Station
20. Indicate%of equipment tested this report 25% 50% 75% ✓ 00%
21. Indicate%of equipment tested YTD 25% 50% 75% ✓ 00%
Comments for any"no"answers or explanations (Note#):
3/13/24
Owners Rep Sign: _._ _. — Date: — — Inspector Sign: _T -. -
ALARM AND DETECTION REPORT Page 3 of 5
Property Site: Main
M
Zone or DEVICE
DEVICE SLC
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
DH ENTRANCE TO ICU X DH-9
DH DOUBLE DOORS TO 200 WING CORRIDOR X DH-7
DH DOUBLE DOORS TO 200 WING CORRIDOR X DH-8
DH DOOR TO ROTUNDA X DH-6
DH TREATMENT 5 X DH-5
DH REGISTRATION 1 X DH-2
is I DH REGISTRATION 2 X DH-3
DH RADIOLOGY CHECK IN X DH-1
DH BLOOW DRAW X DH-4
PDD FRONT ENTRANCE X 27 1
i.
PDD ER WAITING FSD 4 X 27 2
PDD ER WAITING FSD 5 X 27 3
PDD OUTSIDE REGISTRATION FSD 3 X 28 1
PDD OUTSIDE REGISTRATION FSD 2 X 28 2
PDD OUTSIDE ADMINISTRATION FSD 1 X I 28 3
PDD PENTHOUSE X 23 1
is
1
PS ADMIN LOBBY X 7 1
PS OPERATION DIRECTOR'S OFFICE STORAGE X 8 124
PS FRONT LOBBY X 22 1
PS KITCHEN ALCOVE BY LOCKERS X 1 125 I
PS BY FCPS X 4 13
PS CORRIDOR OUTSIDE ROOM 35 X 5 104
PS CORRIDOR OUTSIDE ROOM 25 X 10 108
PS CORRIDOR OUTSIDE ROOM 4 X 12 128
PS CORRIDOR OUTSIDE ROOM X-RAY X 13 120
ftilipo
PS CORRIDOR OUTSIDE ROOM 45 X 14 1161
I
3/13/24 e-
Owners -- _Rep Sign: _ — Date: ..— Inspector Sig„, _ _.
• ALARM AND DETECTION REPORT Main Page 4 of 5
Zone or DEVICE
am" DEVICE SLC n
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
PSD CORRIDOR TO DINING X , 2 126
} PSD CORRIDOR TO PHARMACY X I 2 127
PSD CORRIDOR OUTSIDE PHARMACY X 2 128 1,
PSD CORRIDOR OUTSIDE ROOM 9 X 2 130
PSD CORRIDOR OUTSIDE RADIOLOGY X 3 119
PSD CORRIDOR OUTSIDE ER 1 X 3 121 1
PSD CORRIDOR OUTSIDE ER 3 X 3 122 .
PSD CORRIDOR OUTSIDE ROOM 49 X 9 114
PSD CORRIDOR OUTSIDE ROOM 47 X 9 115
PSD CORRIDOR OUTSIDE SURGERY WORK ROOM X 9 117
PSD ICU CORRIDOR X 9 118
PSD CCU WAITING ALCOVE X 11 6
PSD CORRIDOR OUTSIDE ROOM 29 X 11 1
' PSD CORRIDOR OUTSIDE ROOM 33 X 11 2 1
PSD CORRIDOR OUTSIDE ROOM 34 X 11 3
PSD CORRIDOR OUTSIDE ROOM 38 X 11 4
PSD CORRIDOR OUTSIDE ROOM 41 X 11 5 1
PSD ABOVE FACP X 15 1
PSD ELECTRICAL BY HR X 17 1
PSD FRONT LOBBY X 26 1
' PSD ER WAITING X 26 2
PSD CORRIDOR OUTSIDE TRIAGE 1 X 26 3
PSD CORRIDOR OUTSIDE MEN'S RESTROOM @ BLOOD DRAW X 26 4
PSD CORRIDOR OUTSIDE ROOM 21A X 11 110
PSD MEDICAL SURGERY HALL X 11 111
PSD MEDICAL SURGERY HALL X 11 112
PSD CORRIDOR OUTSIDE ROOM 23A X 11 109 I
PSD CORRIDOR OUTSIDE ROOM 25A X 11 107 1
PSD CORRIDOR OUTSIDE ROOF PENTHOUSE ABOVE FACP X 25 1 I
PSD PENTHOUSE X 25 1 1
I
r 3/13/24
Owners Rep Sign: Date: inspector Sign: _ _ -
_
ALARM AND DETECTION REPORT Main Page 5 of 5
Zone or DEVICE
DEVICE SLC #
TYPE DEVICE LOCATION PASS FAIL NOTE it CHANNEL
r
KH ANSUL SYSTEM X 6 1
WF Water flow X 16 1 1
TS Tamper switch X 6 2
t
1
i
1
LEGEND
PSD-Photoelectric Smoke Detector BD-BeamDetecto- H-Horn V-Visual
ISD-Ionization Smoke Detector FS-Pull Station WPH-Weather P-oof Horn TS-Tamper Switch
r PDD-Photo Duct Smoke Detector RR-Rate of Rise Heat Detector C-Chime WF-Water Flow Switch
IDD-Ion Duct Smoke Detector HT-Fixed Temp Heat Detector CV-Chime Visual DH-DoorHcader
DHS-DoorHolder&SmokeDetectx FD-Flame Detector S-Speaker 0SY-Outside Stem&Yoke TarrperValve
SSD-Sianal Station Smoke Detector R-Rpll AV-Audible Visual PR/-Post Innicat_or Valve
Cur-Elevator Curtains FRD-Fire Rolldown Door SDC Smoke Detector&Door Holder Combo
CO-Carbon Monoxide Detector - _ --
NOTE# I COMMENT
viumw
3/13/24 e- - - -
__ —. _ Inspector Sign: —
Owners Rep Sign: Date:
Page 1 of 2
x
rrrr VOLTAG VOLTAGE4SPECIALisTs
530-624-4514
Cto1C16 License N880862 www.VoltagoSpercialis ts.corn
Inspection #
F SENSITIVITY INSPECTION
Type of Inspection: i-e.Quarterly,Annual Sensitivity Date: 4/15/2024
Property Name: Orchard Hospital
Street: 240 Spruce st Contact: Mike Newton
City& State: Gridley Ca Phone: 530-701-7687
•
Voltsf
Device Device#I Make/Model: I Location: I Sensitivity I Pass + Fail I Notes:
PSD zN11-1 System sensor 2WTA-B I Hallway at nurse station I I 2.6 I X
PSD zN11-2 System sensor2wTA-B I Hallway outside room 33 ' 2.4 j X
PSD zN11-3 System sensor2WTA-B I Hallway at room 348 2.4 I X
PSD zN11-4 System sensor 2WTA-B I Hallway at room 38 I X 2
PSD zN11-5 System sensor2WTA-B I Hallway at room 41 2.6 X
PSD FPS 107 System sensor 2WTA-B I Hallway at room 25B I i 2.4 X
PSD FPS109 System sensor 2WTA-6 I Hallway at room 23B I J 2.4 X
PSD FPS 110 System sensor 2WTA-B I Hallway at room 21 A double doors 2.4 X
V PSD FPS 111 System sensor 2WTA-B I Hallway at room south side of double doorIs f 2.4 X
PSD FPS 112 System sensor 2WTA-B I Hallway at rotunda to rooms 21-28 X I 2
PSD FPS 127 System sensor 2WTA-8 I Hallway at rotunda to rooms 4-9 i 2.6 X
PSD FPS 128 System sensor 2WTA-B+ Hallway at Pharmacy i 2.6 X
PSD FPS 130 System sensor 2wTA-B I Hallway at room 9A 2.4 X
PSD FPS118 System sensor2WTA-B I Hallway at rotunda to rooms 45-51 I X 2
PSD FPS 11-11 System sensor 2WB I Alcove j 2.4 X
PSD FPS 117 System sensor2WTA•B I Hallway at room 45 ` 2.4 X
PSD FPS 115 System sensor 2WTA-B I Hallway at room 47 2.4 X 2
PSD FPS 114 System sensor 2WTA-B I Hallway at room 49 i 2.6 X 2
PSD FPS 122 System sensor 2WTA-B I Hallway at rotunda treatment room 3 i 2.6 X
PSD FPS 121 System sensor 2WTA-B I Hallway at Xray. i 2.6 X
PSD FPS 119 System sensor 2wTA.B j Hallway X Ray waiting I 2.4 X
PSD FPS 126 System sensor 2WB I Hallway at rotunda to dinning I 2.2 X
PSD ZN 26-3 System sensor 2W8 I Hallway to front lobby 2.6 X
• PSD ZN 26-4 System sensor 2WB 1 Lobby restroom hallway I 2.6 X
PSD ZN26-2 System sensor 2W6 I Front Lobby I 2.4 X
PSD ZN26-1 System sensor 2WB I Front lobby foyer I 2.6 X
PSD ZN25-1 System sensor 2WB I Penthouse ` 2.6 X
PDD ZN23-1 System sensor D4120 I Penthouse N/A X 1
PDD ZN23-2 System sensor D4120 I Penthouse i N/A X 1
PSD ZN17 System sensor 2WB I Switch room I 2.6 X
(j(
CUSTOMER SIGNATURE DATE: 4/15/2024 VOLTA E H SI NATURE:
Page 2 Of 2
Volts/
Device Device#I Make/Model: I Location: I Sensitivity I Pass I Fail I Notes:
PSD I 132 System sensor 2wta I Room 6 ER I I 2.4 X I
PSD I Zn-1 System sensor 2wta J Above FACP I I 2.6 X I
PDD I 27-1 System sensor D41201 Front entrance I X 1
PDD I 27-2 System sensor D4120 I ER waiting 4 1 X 1
PDD I 27-3 System sensor D4120 I ER waiting 5 I X 1
PDD I 28-1 System sensor D4120I Outside registration i X 1
PDD 28-2 System sensor 041201 Outside registration I J X 1
PDD I 28-3 System sensor 041201 Outside admitting I X 1
I I
I I
I I
I1
I I I
I 1
I II
i
I I li
I I II
I I i !
I I I
Nor
I I I
'. I
I I I
I I I
1
I I
I I I
I i
i
NOTES
#1 system sensor use flashes on duct detectors to determine sensitivity. Passed per manufactures spec.
#2 out of calibration failed
System sensor 2WB 1.0 to 4.0, System sensor 2WTA-B 1.0 to 3.62
CUSTOMER SIGNATURE DATE: 4/15/2024 VOLTA H R . .