HomeMy WebLinkAboutFAI15-0100 022-170-020 Biggs High FA 10.31.24 ALARM AND DETECTION REPORT Page 1 of 10
VOLTAG PECIALisTs
530-624-4514
C101C16 License#880862 www.VoltageSpecialists.com Inspection #
ALARM & DETECTION EQUIPMENT TEST REPORT
Type of Inspection: Annual Date: 10/31/24
site: Biggs High School customer:Biggs Unified School District
street: 3046 2nd Street Contact: John Strattard
City/State: Biggs, Ca Phone#: 530-868-1281
Fax#:
1. Before Test Notify Proper Authorities: Name Phone #
A. Owner or Owner's Rep John Strattard 530-570-1963
B. Fire Department
C. Central Station Central Station 1-800-722-0364
D. Central Station Acct# 18-9480
2. Control Panel Status Yes No Note #
A. Is the system monitored by Central Station? X
On Test Time: 3:00 Return to Service Time: 7:30
B. Is the Power Light on? X
C. Does the Panel indicate Normal conditions? X
D. Are all indicating Lamp Bulbs in Operator order? X
E. Does the Trouble Light operate? X
F. Does the Silence Switch Operate? X
G. Battery A.H. 18 Date Batteries Installed: 9/2/2020
H. Does the Panel have Non-Operational Zones? X
I. Does the Panel have Battery Backup? X
J. Do the batteries indicate they are Properly Charged? X
Condition of Batteries: Good Note#
Battery Voltage with AC Power: 27.36 Battery Voltage without AC Power: 27.33
K. List any trouble conditions on panel before test: Note# Note 1
Note#
Comments: Note#
Note#
3. FACP Manufacturer: Silent Knight Model# 6820EVS System Type: Addressable
Location of Annunciators:
Location of Primary Power Source: Panel# Breaker
Comments: Note#
Note#
FCPS: Manufacturer: Silent Knight Model# EVS-100W Panel/Breaker# Location:MP Cost.
18ah
Battery Voltage with A/C Power: 27.26 w/o A/C Power 27.23 Date: 9/1/2020
FCPS: Manufacturer: Silent Knight Model# 5895XL Panel/Breaker# Location:MP Cust.
18ah
Battery Voltage with A/C Power: 27.32 w/o A/C Power 27.29 Date: 9/1/2020
FCPS: Manufacturer: Silent Knight Model# EVS-100W Panel/Breaker# Location:Admin.Storage
can 9/15/2022
Battery Voltage with A/C Power: 27.28 w/o A/C Power 27.25 Date:
Owner/Rep: Phone#: Date:
Inspector: Wyatt C. Phone#: 530 362 2609 Date: 10/31/24
Owners Rep Sign: Date:10/31/24 Inspector Sign: �j
ALARM AND DETECTION REPORT Page 2 of 10
Property Site: Biggs High School
l Operational
#Tested
This
Equipment Total# Report Yes N/A Note#
4. Remote Annunciators
5. Zones
6. Manual Stations (Pull) 5 5 X
Hardwire
Addressable
7. Detectors
Photoelectric 94 94 X
Ionization
Heats/Fixed or R of R 36 36 X
Flame
Duct(See#15)
8. Horn/Strobe
Strobe Only 39 39 X
Bell
Speakers 9 9 X
Horn
9. Speaker Strobes 37 37 X
10. Automatic Door Release X
11. Water Flow switches X
Did W/F Ring Outside Bell? X
Did W/F Activate Alarm Panel? X
12. Tamper Switches X
13. PIV X
OS &Y X
14.
15. Did test of Duct Detectors shut down air handling units? X
16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line) receive signal? X
17. Is system reset for normal conditions? X
18. Is system restored to operational service? X
19. Have Proper Authorities (see#1)been notified system is back in service? X
List Proper Authorities:Central Station
20. Indicate %of equipment tested this report 25% 50% 75% VJI00%
21. Indicate %of equipment tested YTD 25% 50% 75% 100%
Comments for any"no"answers or explanations (Note#):
10/31/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Page 3 of 10
Property Site: Biggs High School
Zone or
DEVICE SLC DEVICE
CHANNEL #
TYPE DEVICE LOCATION PASS FAIL NOTE#
PS Gym SW Exit X 02 207
PS Gym NW Exit X 02 211
PS Gym NE Exit X 02 213
PS Gym SE Exit X 02 214
PS Admin Office X 97 201
HT Kitchen Attic X 02 204
HT Weight Rm Attic X 02 217
HT Snack Shack Attic X 02 218
HT Gym RR Attic X 02 223
HT Class Rm 7 Attic X 02 228
HT Class Rm 8 Attic X 02 229
HT Girls Coach Office Attic X 02 230
HT Rms 15-17 Student RR Attic X 02 300
HT Rms 15-17 Work Rm Attic X 02 303
HT Class Rm 17 SE Attic X 02 304
HT Rms 15-17 Staff RR Attic X 02 305
HT Class Rm 17 Central Attic X 02 306
HT Class Rm 17 NE Attic X 02 308
HT Class Rm 16 NW Attic X 02 309
HT Class Rm 15 SW Attic X 02 310
HT Kitchen X 02 S051
HT Kitchen X 02 S052
10/31/24
Sign:Owners RepDate: Inspector Sign:
p J
ALARM AND DETECTION REPORT Biggs High School Page 4 of 10
Zone or
DEVICE SLC DEVICE
CHANNEL #
TYPE DEVICE LOCATION PASS FAIL NOTE#
HT Snack Shack X 02 S066
HT Shop Tool Rm Attic X 97 202
HT Admin Office Storage Attic X 97 203
HT Admin Office Women's RR attic X 97 204
HT Rm 3 Homemaking Heater Closet Attic X 97 205
HT Server Rm Attic X 97 206
HT Class Rm 7&8 Prep Rm Attic X 97 207
HT Shop Rm 10 X 97 S057
HT Shop Rm 10 X 97 S058
HT Shop Rm 10 X 97 S059
HT Shop Rm 10 X 97 S060
HT Shop Rm 10 X 97 S063
HT Shop Rm 10 X 97 S064
HT Shop Rm 10 X 97 S065
HT Shop Rm 10 X 97 S066
HT Shop Finishing Rm X 97 S068
HT Class Rm 9 Homemaking X 97 S072
HT Class Rm 9 Homemaking X 97 S073
HT Class Rm 9 Homemaking Heater Closet X 97 S080
10/31/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Biggs High School Page 5 of 10
Zone or
DEVICE SAC DEVICE
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL #
PSD Kitchen Hallway X 02 S045
PSD Class Rm 13 X 02 S046
PSD Class Rm 13 X 02 S047
PSD Class Rm 14 X 02 S048
PSD Class Rm 14 X 02 S049
PSD SW Gym Entry Hallway X 02 S050
PSD Music Practice Rm X 02 S053
PSD Kitchen RR X 02 S054
PSD Music Practice Rm X 02 S055
PSD Kitchen Storage Rm X 02 S056
PSD Music Rm 12 X 02 S057
PSD Music Rm 12 X 02 S058
PSD Music Rm 12 X 02 S059
PSD Music Rm 12 X 02 S060
PSD Gym S Exterior Storage Rm X 02 S061
PSD Laundry Rm X 02 S062
PSD Gym Electrical/Custodial Storage X 02 S063
PSD Chair Storage Rm X 02 S064
PSD Weight Rm X 02 S065
PSD Weight Rm X 02 S067
PSD Weight Rm X 02 S068
PSD Gym Women's RR X 02 S069
PSD Gym's Men's RR X 02 S070
PSD Girl's Coach's Office X 02 S071
PSD Girl's Coach's Office X 02 S073
PSD Entry Hallway Girl's Locker Rm X 02 S075
PSD Rms 15-17 Electrical Rm X 02 S1oo
PSD Rms 15-17 Office X 02 S103
PSD Rms 15-17 Staff RR X 02 S104
PSD Class Rm 17 X 02 S106
PSD Class Rm 17 X 02 Silo
PSD Class Rm 17 X 02 S113
PSD Rms 15-17 Girl's RR X 02 S114
10/31/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Biggs High School Page 6 of 10
Zone or
DEVICE SLC DEVICE
CHANNEL #
TYPE DEVICE LOCATION PASS FAIL NOTE#
PSD Rms 15-17 Boy's RR X 02 S115
PSD Class Rm 16 X 02 S116
PSD Class Rm 15 X 02 S119
PSD Class Rm 17 X 02 S122
PSD Admin Office Storage Rm X 97 Soo1
PSD Admin Office Vault X 97 S002
PSD Principal's Office X 97 S003
PSD Assistant Principal's Office X 97 S004
PSD Assistant Principal's RR X 97 S005
PSD Admin Office Women's RR X 97 S006
PSD Break Rm X 97 S007
PSD IT Office X 97 S008
PSD IT/Server Rm X 97 S009
PSD ServerRm X 97 solo
PSD Class Rm 2 X 97 S011
PSD Class Rm 2 X 97 S012
PSD Class Rm 7&8 Prep Rm X 97 S013
PSD Class Rm 7&8 Dark Rm X 97 S014
PSD Class Rm 8 X 97 S015
PSD Class Rm 8 X 97 S016
PSD Principal's Office Closet X 97 sole
PSD Admin Office X 97 S019
PSD Migrant Education X 97 S021
PSD Quad Girls RR X 97 S022
PSD Class Rm 1 X 97 S023
PSD Class Rm 1 X 97 S024
PSD Career Center Office Rm 2 X 97 S025
PSD Class Rm 3 X 97 S027
PSD Class Rm 3 X 97 S028
PSD Class Rm 3 X 97 S029
PSD NW Custodial Rm X 97 S031
PSD Quad Boys RR X 97 S033
PSD Library Rm 6 A/V Rm X 97 S034
10/31/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Biggs High School Page 7 of 10
Zone or
DEVICE SLC DEVICE
CHANNEL #
TYPE DEVICE LOCATION PASS FAIL NOTE#
PSD Library Rm 6 Conference Rm X 97 S035
PSD Library Rm 6 X 97 S036
PSD Library Rm 6 X 97 S037
PSD Class Rm 5 X 97 S038
PSD Class Rm 5 X 97 S039
PSD Class Rm 4 X 97 S040
PSD Class Rm 4 X 97 S041
PSD MP NE Hallway X 97 S042
PSD MP X 97 S043
PSD MP X 97 S044
PSD MP X 97 S045
PSD MP X 97 S046
PSD MP X 97 S047
PSD MP X 97 S048
PSD SE MP Hallway X 97 S049
PSD Assistant Principal's Office Closet X 97 S050
PSD Class Rm 11 X 97 S051
PSD Class Rm 11 X 97 S052
PSD Class Rm 5 Storage X 97 S053
PSD Class Rm 11 Storage X 97 S054
PSD Class Rm 5 Office X 97 S055
PSD Class Rm 5 X 97 S056
PSD Shop Project Storage X 97 S067
PSD Shop Tool Rm X 97 S069
PSD Shop Office X 97 S070
PSD Shop Storage/IDF Rm X 97 S071
PSD Class Rm 9 Homemaking X 97 S074
PSD Class Rm 9 Homemaking Storage X 97 S075
10/31/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Biggs High School Page8 of 10
Zone or
DEVICE SLC DEVICE
CHANNEL #
TYPE DEVICE LOCATION PASS FAIL NOTE#
DD Kitchen Attic HVAC DD X 02 203
DD Gym HVAC NE DD X 02 212
DD Gym SE HVAC DD X 02 215
DD Weight Rm Attic HVAC DD X 02 216
DD Gym RR Attic HVAC DD X 02 220
DD Gym RR Attic HVAC DD X 02 221
DD Gym RR Attic HVAC DD X 02 222
DD Class Rmn16 AC3 DD X X 02 321
BD North Gym X
BD Center Gym X 02 90
BD South Gym X
10/31/24
Sign:Owners RepDate: Inspector Sign:
p J
ALARM AND DETECTION REPORT Biggs High School Page of 10
Zone or
DEVICE SLC DEVICE
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL #
10/31/24
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Biggs High School Page of 10
Zone or
DEVICE sLC DEVICE
CHANNEL #
TYPE DEVICE LOCATION PASS FAIL NOTE#
LEGEND
PSD—Photoelectric Smoke Detector BD—Beam Detector H—Horn V—Visual
ISD—Ionization Smoke Detector PS—Pull Station WPH—Weather Proof Horn TS—Tamper Switch
PDD—Photo Duct Smoke Detector RR—Rate of Rise Heat Detector C—Chime WF—Water Flow Switch
IDD—Ion Duct Smoke Detector HT—Fixed Temp Heat Detector CV—Chime Visual DH—Door Holder
DHS—Door Holder&Smoke Detector FD—Flame Detector S—Speaker OSY—Outside Stem&Yoke Tamper Valve
SSD—Signal Station Smoke Detector B—Bell AV—Audible Visual Ply—Post Indicator Valve
Cur-Elevator Curtains FRD-Fire Rolldown Door SDC Smoke Detector&Door Holder Combo
CO-Carbon Monoxide Detector - - -
NOTE # COMMENT
Discrepancies Found? I✓I Yes I I No
See Discrepancy Report? 171 Yes _ No
10/31/24