HomeMy WebLinkAboutFAI15-0050 041-130-044 Butte College Bldg #9 Mathmatics Qtr Sprink 4.4.25 (2) Wet Pipe California Code of Regulations -Title 19 Quarterly and 1 of 3
Fire Sprinkler System Inspection, Testing, and Maintenance Annual Report
Property Information ";��CF CaCI-0�II Contractor or Licensed Owner Information
Building Name Butte College Mathmatics i t 1 '/ Name Voltage Specialists
Address +fi'i1Q�f Address 370 Apple Lane
3536 Butte Campus Drive ��. F., City Paradise St. CA Zip 95969
'City Oroville (License# 880862 (Phone (530)854-4180
'Contact Person I ❑ SFM IJob# 1-160
' Jake Gonzales (530)961-3016 I ✓❑ CSLB 'Misc.
Riser Information IL. Main Drain Test(Annual) M
Riser Location Riser Main Drain Initial Static Residual Final Static p F,N/A
No. Diameter Diameter Pressure Pressure Pressure
1 Outside Closet 4" 2"
I
I I I I II
I I
I I I I I I I
Q This building has more than 5 risers. See additional AES 2.9 form attached Number of AES 2.9 forms attached 1 I
Quarterly Inspections
1 =Inspection T=Test M=Maintenance P=Pass F=Fail N/A =Not Applicable
Item 1 Description
NFPA 25 CA ed. Date Date Date Date
Reference 04/04/25
1.1 I Control Valves—Identification Sign 13.3.1 P
1.2 I Control Valves—Inspection 13.3.2 P
1.3 I Waterflow Alarm Devices 5.2.5 P
1.4 I Supervisory Devices 5.2.5 P
1.5 I Gauges(Wet Pipe Systems) 5.2.4.1 P
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1 P
1.9 I Hydraulic Design Information Sign 5.2.6 P
(for hydraulically designed systems)
1.10 I General Information Sign 5.2.8 P
(not required for system prior to 2007 edition of NFPA 13)
1.11 I Heat Tape 5.2.7 N/A N/A N/A N/A
1.12 I Spare Sprinklers 5.2.1.4 P
1.13 I Fire Department Connections 13.7 P
1.14 I Alarm Valves—Exterior Inspection 13.4.1 P
1.15 I Pressure Reducing Valves 13.5.1.1 N/A N/A N/A N/A
1.16 I Backflow Preventers 13.6.1 P
1.17 I Small Hose Connections- Hose Valve* 5.1.6, 13.5.2 N/A N/A N/A N/A
13.5.5.1
1.18 I PRV—Fire Sprinkler Systems 13.5.1.1 N/A N/A N/A N/A
*Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III
standpipe systems.
Form AES 2.1 Sept.3,2013
Wet Pipe California Code of Regulations -Title 19 Quarterly and 2 of 3
Fire Sprinkler System Inspection, Testing, and Maintenance Annual Report
"'Si cilt111$
,
:,<Property Information � Contractor or Licensed Owner Information
1.0
'Building Name Butte College Mathmatics i { Jz''0 'Name Voltage Specialists
'Address 3536 Butte Campus Drive 'j ,. 'Job# 1-160
'City Oroville ', E MR= I
ANNUAL INSPECTION, TESTING, AND MAINTENANCE miii
Include ALL Quarterly Inspections
I =Inspection T =Test M=Maintenance P=Pass F=Fail N/A =Not Applicable
ItemDescription Reference ate Comments Only P,F,N/A
1.19 1 Sprinklers 5.2.1
1.20 I Buildings(Freeze Protection) 4.1.1.1 N/A Owner's Responsibility N/A
1.21 I Pipe and Fittings 5.2.2
1.22 I Hangers 5.2.3
1.23 I Seismic Braces 5.2.3
Field Service Test Required If REQUIRED, Enter'F' until
2.1 T (Send Report to Fire Code Official) 5.3.1 results are returned from Lab
2.2 T Recalled Sprinklers Title 19
If not present=Pass; If present=Fail 904.1(c)
Water Flow Alarm Devices 5.3.3
2.3 T 90 sec. maximum - (Enter Time) 13.2.6 sec.
2.4 T Main Drain Test 13.2.5
(Enter data on Page 1 of this form) 13.3.3.4
2.5 T Control Valve-Position 13.3.3.2
2.6 T Control Valve—Operation 13.3.3.1
2.7 T Supervisory Devices 13.3.3.5
2.8 T Backflow Preventer Assemblies 13.6.2 N/A N/A
2 9 T Small Hose Connections* 13.5.2.3 N/A N/A
w/PRV Hose Valves—Partial Flow Test 13.5.3.3
2.10 T PRV—Fire Sprinkler Systems 13.5.1.3 N/A N/A
3.1 M Control Valves 13.3.4
3.2 M Small Hose Connections* 13.5.6.3 N/A N/A
I Obstruction Investigation required I El Yes '3.3 M (If"Yes" see Deficiencies and Comments Section14.3 No
for Results.)
3.4 I M 'System Returned to Service I 4.5.3 I IEYeS I
No
*Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III
standpipe systems.
D=Deficiency C=Comment (Indicate type)
Item' Date =MMIIIMI. Deficiencies and Comments
Indicate all equipment,devices and parts that were repaired or replaced
_III
I LU
I 1 I1_1
I I III I 1
Form AES 2.1 Sept.3,2013
Wet Pipe California Code of Regulations -Title 19 Quarterly and 3 of 3
Fire Sprinkler System Inspection, Testing, and Maintenance Annual Report
Property Information "<'7k1)441 Contractor or Licensed Owner Information
�!` z'\t
'Building Name Butte College Mathmatics S [ a r Name Voltage Specialists
'Address 3536 Butte Campus Drive �-I ,�� Job# 1-160
'City Oroville ti� E MP
D=Deficiency C=Comment (Indicate type)
Item Date Riser D C Deficiencies and Comments(cont.)
Indicate all equipment,devices and parts that were repaired or replaced
II ✓
_!J
1i1J
`ate
`■ 11
ELi
illil
❑Check here if additional Deficiencies and Comments are listed on Form AES9 Number attached:
❑ See Correction Form AES 10 for corrected deficiencies. Number attached:
I hereby certify that the fire protection equipment listed above has been fully inspected, tested,and maintained on this date by
the company indicated above,in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable
except as noted in the"Deficiencies and Comments"section of this form.
Check box if Annual Inspection, Testing &Maintenance Items are Completed in the Indicated Quarter
Quart d - ❑ Annual Annua riu4th - ❑ Annual
Date 03/22/24
Print Name I Wyatt C.
Signature
Form AES 2.1 Sept.3,2013