HomeMy WebLinkAboutFAI15-0052 041-130-044 Butte College Bldg #8 ITS Allied 6.13.25 Report of Inspection/Test Annual Special Hazard FM200 System VOLTAGPECIAuSTS
Date: 6/13/25
Property Owner/Agent
Butte College Butte College C10/16 License#880862 530-624-4514
Allied Health South Jake Gonzales
Conducted by: Don Cantrell
Inspection Ref: 11-168
Signatures
Inspector- Printed Inspector-Signature Date I state that the information on this form is correct at the
Don Inspector
and place of my inspection,and that all equipment
Cantrell 00C0iri" 6/13/25 tested at this time was left in operational condition upon
completion of this inspection except as noted.
Owner- Printed Owner-Signature Date Except as noted,the building is occupied with the same
Jake occupancy classification and hazard of contents as last
inspection. Also,the system has remained in service
Gonzales without modification and been free of actuation of
devices or alarms.
Notifications
To Be Notified I Testing I Time I Phone I Contact
NA Start
EndI I
System and Panel Information
Type Fm 200 I425 LBS Amount of Agent I Hazard Computer room
Panel Manufacturer I Model I Serial No. 1 Location
Chemtron I Micro 1002 I Server room
Over current Protection Type Over current Size(Amps) Primary Supply Disconnect Location I Panel#/Breaker#
Breaker 20 PANEL SLB
Cylinder(s)
ICylinder Fill I Inspection -Service
Equip ID Description/ Size Manufacturer I Weight I L > toi c 0.
Location Model _ a 3 0 12 9- Y W D R U d
R R N Of 'a - 2l7C 00) O r O
0 cm3 3 u- '0 O L (, l4 o w =
I- Q 0 _1 = U m H IA
Server room Chemtrom 1. , ' 3 8 t =13701 Ok Ok Ok Ok Ok Okl Okl Okl Ok Ok
Ok- Passes Inspection -Serviced on site - Requires Service NA- Not Applicable
Page 1 of 3
Voltage Specialists 370 Apple Lane, Paradise 95969
Report of Inspection/Test
Annual Special Hazard FM200 System VOLTAG PECIALISTS
Date: 6/13/25
Property: Butte College c10/16 License#880862 530-624-4514
Owner: Butte College Inspection Ref: I1-168
System Function Summary & Test
Function Description Yes No I
Alarm Panel Supervisory Functions
Panel AC Power Loss I Loss of AC power to the alarm panel is detected by the alarm system. I O 0
Panel Sec Power Loss I Loss of Secondary power to the alarm panel is detected by the alarm O ❑
system.
Open Alarm Circuits I Electrical opens in initiating and indicating circuits are detected. I ❑✓ ❑
Short Alarm Circuits I Electrical shorts in initiating and indicating circuits are detected. I I✓I ❑
Panel to Panel Circuits Integrity of single or multiple circuits providing interface between two or I a ❑
more control panels verified.
Ground Faults Detected I Ground faults in alarm and power circuits are detected •
I ✓❑ ❑
Alarm Functions - Chemical Suppression
1st Alarm A single initiating zone shows alarm. ❑✓ ❑
2nd Alarm A 2nd initiating zone shows alarm. n n
Time Delay Delay between 1st alarm and agent discharge. L✓J ❑
I Discharge Alarm Audible alarm upon agent discharge. �� ❑
Agent discharge Actual discharge of chemical fire suppression agent. �✓ ❑
Abort Switch Switch prevents discharge of chemical fire suppression agent. n n
Panel Inspection
Yes ❑✓ No ❑ System was in operation upon arrival?
Yes ❑✓ No ❑ Panel and surrounding equipment, conduit and wiring well secured and in good condition
Yes ElNo ❑ Are all lamps and displays operating correctly?
Yes ❑✓ No ❑ Primary power supply operates properly under full load ?
Yes ❑ No ❑✓ Are drawings and wiring diagrams available at the panel?
Yes ❑✓ No ❑ Are operating instructions posted or available at the panel?
Yes n No ❑ Are zones labeled and identified?
Chemical Suppression Inspection
Yes ElNo El Agent control heads or nozzles are in good condition and properly mounted ?
Yes ❑✓ No ❑ All ceiling and floor panels are in place?
Yes ❑✓ No ❑ Warning signs are proper and visible ?
Central Station Test
Yes ❑ No ✓❑ Type Transmission
Yes ❑ No El Alarm, Trouble and Supervisory indication tested and verified with the central station?
Yes ❑ No ❑ Operator spoke to
Page 2 of 3
Voltage Specialists 370 Apple Lane, Paradise 95969
Report of Inspection/Test
Annual Special Hazard FM200 System VOLTAG PECIALISTS
Date:6/13/25 c10/16 License#880862 530-624-4514
Property: Butte College
Owner: Butte College Inspection Ref: 11-168
Alarm Device List
Zone Physical Functional
Device Type Address Location Description Manufacture Model Condition Test
Photo smoke 1 Ceiling I Hochiki Good Passed
Ion smoke 1 Ceiling I Hochiki Good Passed
Ion smoke 2 Ceiling I Hochiki Good Passed
Ion smoke 1 Ceiling I Hochiki Good Passed
Smoke Under floor I No access
Smoke Ion 1 Under floor Good Passed
Smoke Under floor No access
Smoke Under floor I No access
Pull station Man rise. West exit Notifier Good Passed
Pull station Man rise. East exit Notifier Good Passed
Abort Abort West exit Chemtron Good Passed
Abort Abort East exit Chemtron Good Passed
Horn strobe N1 Above FACP System sensor Good Passed
Strobe N1 Hall System senso Good Passed
Bell N1 Above FACP System sensor Good Passed
8 ah batteries Panel 2023 Good Passed
Alarm Device Summary Number 1 6 IS Items Serviced 11 E I 1 E
of Items IX Iltems Requiring Service 11 E I 1 E
Page 3 of 3
Voltage Specialists 370 Apple Lane, Paradise 95969