FAI15-0062 030-462-009 Fire Alarm Submittal Roseleaf, Oroville 12-24-25
24-Dec-25 DATA SHEET# PART# DESCRIPTION CSFM# 1 6820 Silent Knight Fire Alarm Contol Panel 7165-0559:0500 2 DURA12-12F2 Duracell 12VDC 10AH Battery N/A 3 5496 Silent Knight Intelligent Power Module 7300-0559:0171 4 5860 Silent Knight Remote Annunciator 7165-0559:0500 5 AL600ULX Altronix Power Supply Unit 7315-1335:0104 6 SK-PHOTO Silent Knight Addressable Photoelectric Smoke Detector 7272-0559:0149 7 SK-FIRE-CO Silent Knight Multi-Criteria Fire/CO Detector 7275-0559:0170 8 SK-HEAT-HT Silent Knight Addressable Hi-Temp Heat Detector 7270-0559:0147 9 SK-MINIMON Silent Knight Addressable Mini-Monitor Module 7300-0559:0155 10 SK-RELAY Silent Knight Addressable Relay Module 7300-0559:0155 11 SK-PULL-DA Silent Knight Addressable Dual Action Pull Station 7150-0559:0161 12 P2RK System Sensor Horn-Strobe, Multi-CD, Wall Mount 7135-1653:0532 13 P1224MCA System Sensor Strobe, Multi-CD, Wall Mount N/A Bill Bunch Project Manager Roseleaf, Oroville FIRE ALARM SYSTEM • Capable of providing up to 1110 points for enhanced design flexibility. Additional Signal Line Circuits can be added until maximum point levels are reached • Built-in USB interface for convenient and quick programming • Connect up to 17 panels on one site with convenient single- point access using the SK-NIC Network Interface Card. Connected panels can have mixed compatible FACP models • Convenient field-upgradeable GJSNXBSF •#VJMUJOEVBMQBUI 1054BOE*1 DPNNVOJDBUJPOTXJUI PQUJPOBMDFMMVMBS NPEFMTBWBJMBCMFGPS SFMJBCMFCBDLVQ SFQPSUJOH • 6860 annunciator with a 4 x 40 large display •+VNQ4UBSUkBVUP QSPHSBNNJOHSFEVDFT JOTUBMMBUJPOUJNF • Programmable date setting for automatic and convenient Daylight Saving Time changes •'PVSVTFS QSPHSBNNBCMF CVUUPOTNJOJNJ[F UJNFTQFOUFYFDVUJOH DPNQMFYPSSPVUJOF UBTLT • Flexputk circuits can be individually programmed to function as notification circuits, auxiliary power outputs, or initiating circuits that support both 2- and 4-wire smoke detectors 6820 "EESFTTBCMF'JSF"MBSN$POUSPM1BOFM 5IFJTBOBEESFTTBCMFfiSFBMBSNDPOUSPMQBOFM '"$1 BOEJTB EJSFDUSFQMBDFNFOUGPSUIF9-'"$15IFDBOCFDPOfiHVSFE UPBDIJFWFBQPJOUDBQBDJUZPGQPJOUTBOEDPOOFDUVQUPQBOFMT JOBTJOHMFDPNNVOJDBUJPOTMJOL 5IFIBTPOFCVJMUJOTJHOBMJOHMJOFDJSDVJU 4-$ XIJDIDBO TVQQPSU 4, 4ZTUFN4FOTPSkTFOTPSTBOE4,NPEVMFTPS 4% )PDIJLJkEFWJDFTQFSMPPQ5PJODSFBTFQPJOUDBQBCJMJUJFT BEEJUJPOBM 4-$MPPQTDBOCFBEEFEVTJOHUIF4-$FYQBOEFSGPS4,EFWJDFTPS UIF9-FYQBOEFSGPS4%EFWJDFT JODSFBTJOHUIFQPJOUDBQBDJUZUPB NBYJNVNPGQPJOUTGPS4,EFWJDFTBOEQPJOUTGPS4%EFWJDFT 5ISFFBEEJUJPOBM4-$TBSFOFFEFEUPSFBDIQPJOUT 4,EFWJDFT 'PVSBEEJUJPOBM4-$TBSFOFFEFEUPSFBDIQPJOUT 4%EFWJDFT "DPNNPODPNNVOJDBUJPOTBOEBOOVODJBUJPOMJOLBMMPXTVQUP QBOFMTUPCFDPOOFDUFEWJBDPQQFSPSfiCFSPQUJDDBCMF"EFTJHOBUFE QBOFMJTDPOfiHVSFEBTUIFDPNNVOJDBUPSGPSBMMQBOFMTJOUIFMJOLGPS DPOWFOJFOUTJOHMFQPJOUDPNNVOJDBUJPOT*UBMTPIBTBCVJMUJO EVBM MJOF1054BOE*1DPNNVOJDBUPSXJUIBEEJUJPOBMDFMMVMBSPQUJPOT BWBJMBCMF 5IFTZTUFNDBOCFFOIBODFECZBEEJOHNPEVMFTTVDIBTUIF SFNPUFBOOVODJBUPSXIJDIBMTPIBTGPVSQSPHSBNNBCMFGVODUJPO CVUUPOTUPIFMQBVUPNBUFUBTLTBOESFEVDFUJNFTQFOUBUUIFQBOFM 48*'5k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• General Alarm (Red)'MBTIFTJGJO BMBSNTPMJEXIFOBMBSNJTTJMFODFE • Supervisory (Yellow):'MBTIFTJGB TVQFSWJTPSZDPOEJUJPOFYJTUTTPMJE XIFOTVQFSWJTPSZJTTJMFODFE •System Troubles (Yellow)'MBTIFT JGBUSPVCMFDPOEJUJPOFYJTUT TPMJEXIFOUSPVCMFJTTJMFODFE •System Silenced (Yellow) 0OXIFOBOBMBSN USPVCMFPS TVQFSWJTPSZDPOEJUJPOIBTCFFO TJMFODFECVUOPUZFUDMFBSFE • System Power (Green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k"VUP1SPHSBNNJOH NJOJNJ[FTQSPHSBNNJOHSFRVJSFEUP TUBSUBOFXTZTUFN5IFCVJMUJOLFZQBE PSUIF PSSFNPUF BOOVODJBUPSTHJWFZPVPOTJUFBDDFTTUP DVSSFOUTZTUFNQSPHSBNNJOH 1SPHSBNNJOHDBOBMTPCFBDDPNQMJTIFE VTJOHUIF8JOEPXTkCBTFE)POFZXFMM 'JSF4PGUXBSF4VJUF )'44 QSPHSBN SOFTWARE TOOLS SKST:4JMFOU,OJHIU4FMFDUJPO5PPM QSPWJEFTUIFJOTUBMMFSPSEFTJHOBSDIJUFDU XJUIB8JOEPXTkTPGUXBSFTZTUFN DPOGJHVSBUJPOUPPMUPDSFBUFBEFUBJMFE #JMMPG.BUFSJBM #0. BOECBUUFSZ DBMDVMBUJPOT HFSS:)POFZXFMM'JSF4PGUXBSF4VJUF QSPWJEFTDPNNVOJDBUJPOBOEQBOFM QSPHSBNNJOH EFUFDUPSTUBUVT FWFOU IJTUPSZBOEBEEJUJPOBMEBUB3FRVJSFTB 1$SVOOJOH.JDSPTPGUk8JOEPXTk ADDITIONAL INFORMATION 5XJTUFEVOTIJFMEFEQBJSXJSFJT SFDPNNFOEFE5IFBMTPIBT QSFTFUOPUJGJDBUJPODBEFODFQBUUFSOT JODMVEJOH"/4* XBUFSGMPX TQSJOLMFSTVQFSWJTPSZ %"$5 OPODPEFE TJHOBMJOHTFSWJDFT •UL-JTUFE4 • CSFM • FDNY$0" •FMBQQSPWFE ORDERING INFORMATION "EESFTTBCMF'JSF"MBSN $POUSPM1BOFM 3FEDBCJOFU COMPATIBLE ANNUNCIATORS 6860:Y-$%SFNPUFGJSFBOOVODJBUPS MJOFTBOEVQUPDIBSBDUFST QFS TZTUFNGPVSQSPHSBNNBCMFCVUUPOT 5860:Y-$%SFNPUFGJSF BOOVODJBUPSJTHSBZ3JTSFE 6855:Y-$%SFNPUFGJSFBOOVODJBUPS 5865-3 or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www.silentknight.com Important::PVDBOOPUNJY4,BOE4% EFWJDFTJOUIFTBNFGJSFBMBSNTZTUFN Page 2 of 4 — 351610:B 9/26/2018 4,$0.1"5*#-&"%%3&44"#-& DEVICES SK-ACCLIMATE:.VMUJDSJUFSJB QIPUPFMFDUSJDTNPLFEFUFDUPSXJUIUIFSNBM m'GJYFEUFNQFSBUVSF SK-BEAM:3FGMFDUFECFBNTNPLFEFUFDUPS XJUIPVUUFTUGFBUVSF SK-BEAM-T:3FGMFDUFECFBNTNPLF EFUFDUPSXJUIUFTUGFBUVSF SK-CONTROL:4VQFSWJTFEDPOUSPMNPEVMF SK-CONTROL-6:4JYDJSDVJUTVQFSWJTFE DPOUSPMNPEVMF SK-DUCT:1IPUPFMFDUSJDEVDUTNPLF EFUFDUPSXJUIFYUFOEFEBJSTQFFESBOHF SK-FIRE-CO:'PVSDSJUFSJBGJSFBOEDBSCPO NPOPYJEFEFUFDUPS SK-HEAT:'JYFEUIFSNBMEFUFDUPS m' 4,)&"58'JYFEUIFSNBMEFUFDUPS m' XIJUF SK-HEAT-ROR:'JYFESBUFPGSJTFEFUFDUPS m' 4,)&"53038'JYFESBUFPGSJTFEFUFDUPS m' XIJUF SK-HEAT-HT:'JYFEIJHIUFNQFSBUVSF UIFSNBMEFUFDUPS m' 4,)&"5)58'JYFEIJHIUFNQFSBUVSF UIFSNBMEFUFDUPS m' XIJUF SK-ISO:'BVMUJTPMBUPSNPEVMF SK-MINIMON:.JOJNPOJUPSNPEVMF SK-MONITOR:.POJUPSNPEVMF SK-MONITOR-2:%VBMJOQVUNPOJUPS NPEVMF SK-MON-10:JOQVUNPOJUPSNPEVMF SK-PHOTO:1IPUPFMFDUSJDTNPLFEFUFDUPS 4,1)05081IPUPFMFDUSJDTNPLF EFUFDUPS XIJUF SK-PHOTO-T:1IPUPFMFDUSJDTNPLFEFUFDUPS XJUIUIFSNBM m'GJYFEUFNQFSBUVSF 4,1)050581IPUPFMFDUSJDTNPLF EFUFDUPSXJUIUIFSNBM m'GJYFE UFNQFSBUVSF XIJUF SK-PHOTOR:1IPUPFMFDUSJDEFUFDUPSXJUI SFNPUFUFTUDBQBCJMJUZ 4,1)050381IPUPFMFDUSJDEFUFDUPS XJUISFNPUFUFTUDBQBCJMJUZ XIJUF SK-PULL-SA:"EESFTTBCMFTJOHMFBDUJPOQVMM TUBUJPO SK-PULL-DA:"EESFTTBCMFEVBMBDUJPOQVMM TUBUJPO SK-RELAY:"EESFTTBCMFSFMBZNPEVMF SK-RELAY-6:"EESFTTBCMF4JYSFMBZDPOUSPM NPEVMF SK-RELAYMON-2:"EESFTTBCMF%VBMSFMBZ NPOJUPSNPEVMF SK-ZONE:"EESFTTBCMF[POFJOUFSGBDF NPEVMF SK-ZONE-6:4JY[POFJOUFSGBDFNPEVMF # *7 CBTFGPS4,84FSJFT B210LP:NPVOUJOHCBTF # 8)*5& *7 #- 'MBOHFMFTTCBTF B501:'MBOHFMFTTNPVOUJOHCBTF #4 *7 8) *OUFMMJHFOUTPVOEFSCBTF B200S:*OUFMMJHFOUTPVOEFSCBTF #4-' *7 8) -PXGSFRVFODZ JOUFMMJHFOUTPVOEFSCBTF #4-'-PXGSFRVFODZJOUFMMJHFOU TPVOEFSCBTF #3# *7 8) 3FMBZCBTF B224RB:3FMBZCBTF ##* *7 8) *TPMBUPSCBTF B224BI:*TPMBUPSCBTF SD COMPATIBLE ADDRESSABLE DEVICES SD505-6AB:"EESFTTBCMFCBTF SD505-6IB:"EESFTTBCMFTIPSUDJSDVJU JTPMBUPSCBTF SD505-6RB:"EESFTTBCMFSFMBZCBTF SD505-6SB:"EESFTTBCMFTPVOEFSCBTF SD500-AIM:"EESFTTBCMFJOQVUNPEVMF TXJUDIJOQVU SD500-ANM:"EESFTTBCMFOPUJGJDBUJPO NPEVMF SD500-ARM: "EESFTTBCMF SFMBZ NPEVMF SD505-DTS-K: 3FNPUF UFTU TXJUDI BOE -&%JOEJDBUPSGPSUIF4%%6$53 SD505-DUCT:"EESFTTBCMF%VDU4NPLF %FUFDUPS SD505-DUCTR:"EESFTTBCMF%VDU %FUFDUPSIPVTJOHXJUISFMBZCBTF SD505-HEAT:"CTPMVUFUFNQFSBUVSFIFBU EFUFDUPS5SJQQPJOUSBOHFGSPN m'ŗm' m$ŗm$ SD500-LIM:"EESFTTBCMF-JOFJTPMBUPS NPEVMF SD500-MIM:"EESFTTBCMF.JOJJOQVU NPOJUPSNPEVMF TXJUDIJOQVU SD505-PHOTO:1IPUPFMFDUSJDTNPLF EFUFDUPS SD500-PS/-PSDA:"EESFTTBCMF4JOHMFPS EVBMBDUJPOQVMMTUBUJPO SD500-SDM:"EESFTTBCMFTNPLFEFUFDUPS NPEVMF AUDIBLE/VISIBLE DEVICES 5IFTF"7EFWJDFTBSFBMMXJSF$PMPSş3Š JOEJDBUFTSFEş8ŠEFOPUFTXIJUF'PSB DPNQMFUFMJTUJOHPG4JMFOU,OJHIU"7EFWJDFT HPUPXXXTJMFOULOJHIUDPN CHSRL/CHSWL:8BMMDIJNFTUSPCF CHSCRL/CHSCWL:$FJMJOHDIJNFTUSPCF CHRL/CHWL:8BMMDIJNF HRL/HWL:8BMMIPSO P2RL/P2WL:8BMMIPSOTUSPCF PC2RL/PC2WL:$FJMJOHIPSOTUSPCF SRL/SWL:8BMMTUSPCF SCRL/SCWL:$FJMJOHTUSPCF SPSCRL/SPSCWL:$FJMJOHTQFBLFSTUSPCF SPSRL/SPSWL:8BMMTQFBLFSTUSPCF SPRL/SPWL:8BMMTQFBLFS SPCRL/SPCWL:$FJMJOHTQFBLFS SWIFT WIRELESS DEVICES SWIFT is only compatible with System Sensor (SK) devices. It is not compatible with Hochiki (SD) devices WSK-WGI:8JSFMFTT(BUFXBZ WSK-PHOTO:8JSFMFTT1IPUPFMFDUSJDTNPLF EFUFDUPS WSK-PHOTO-T:8JSFMFTT.VMUJDSJUFSJB QIPUPFMFDUSJDTNPLFEFUFDUPSXJUIUIFSNBM EFUFDUJPO mF fiYFEUFNQFSBUVSF BOE #8CBTF WSK-HEAT:8JSFMFTT)FBU mF fiYFE UFNQFSBUVSF BOE#8CBTF WSK-HEAT-ROR:8JSFMFTTIFBU 303 mF fiYFEUFNQFSBUVSF BOE#8 CBTF WSK-MONITOR:8JSFMFTTNPOJUPSNPEVMF WSK-RELAY:8JSFMFTTSFMBZNPEVMF W-USB:48*'55PPMT64#USBOTDFJWFSVTFE GPSDPNNVOJDBUJPOXJUI48*'5EFWJDFT SBUS ACCESSORIES 6815:&BDI4JOHMF-JOF$JSDVJUBMMPXTGPS BOBEEJUJPOBM4,NPEVMFTBOE4, TFOTPSTUPCFBEEFEUPUIFTZTUFNVQUP UPUBMQPJOUT4VQQPSUT4ZTUFN4FOTPS 4,EFWJDFTPOMZ 5815XL:&BDI4JOHMF-JOF$JSDVJUQSPWJEFT BOBEEJUJPOBM4%EFWJDFTUPCFBEEFEUP UIFTZTUFNGPSBNBYJNVNPGQPJOUT 4VQQPSUT4%EFWJDFTPOMZ 5496:"BNQOPUJfiDBUJPOQPXFSFYQBOEFS XJUIGPVSQPXFSMJNJUFEOPUJfiDBUJPO BQQMJBODFDJSDVJUPVUQVUT 5883:3FMBZ*OUFSGBDF1SPWJEFT'PSN$ SFMBZT 5824:4FSJBM1BSBMMFM1SJOUFS*OUFSGBDF .PEVMFGPSQSJOUFSDPOOFDUJPO 5895XL:1PXFS4VQQMZXJUITJY'MFYQVUƇ DJSDVJUT BOEUXP'PSN$SFMBZT.BYQFS TZTUFN 5815RMK:3FNPUFNPVOUJOHLJU %JNFOTJPOTŠ8YŠ)YŠ% COMMUNICATION OPTIONS CELL-CAB-SK:$FMMVMBSDPNNVOJDBUPS NFUBMFODMPTVSFXJUIMPDLLFZ CELL-MOD:$FMMVMBSDPNNVOJDBUPS QMBTUJD FODMPTVSF 4PMFQBUI QPXFSFECZQBOFM IPGSM-4G:%VBMQBUh fiSFBMBSN DPNNVOJDBUPS DFMMVMBSBOEPS*1 QSJNBSZ PSCBDLVQ TFMFDUBCMF SK-IP-2:3FNPUFSFQPSUJOHWJBUIF*OUFSOFU 3FRVJSFTB7JTPS"MBSNkSFDFJWFSBUUIF DFOUSBMTUBUJPO MISC. ACCESSORIES SK-NIC:/FUXPSL*OUFSGBDF$BSE1SPWJEFTB DPNNPODPNNVOJDBUJPOTMJOLGPSUIF SK-NIC-KIT:*OTUBMMBUJPO"DDFTTPSZ,JU SK-FML:'JCFS0QUJD.VMUJ.PEF USBOTNJUUFSBOESFDFJWFS SK-FSL:'JCFS0QUJD4JOHMF.PEF RBB:3FNPUFCBUUFSZCPYBDDFTTPSZDBCJOFU GPSCBUUFSJFTUIBUBSFUPPMBSHFUo fiUJOUIF '"$1DBCJOFU%JNFOTJPOTŠ8YŠ)Y Š% NN8YNN)YNN% SK-SCK:4FJTNJD$PNQMJBODF,JUVTFEUP TFDVSFMZGBTUFOCBUUFSJFTUPUIe fiSFQBOFM 1BHFPGŘ# 'MFYQVUk )POFZXFMMk +VNQ4UBSUk 4JMFOU,OJHIUk 48*'5k BOE4ZTUFN 4FOTPSkBSFSFHJTUFSFE USBEFNBSLTPG)POFZXFMM *OUFSOBUJPOBM*OD )PDIJLJkJTBSFHJTUFSFE USBEFNBSLPG)PDIJLJ $PSQPSBUJPO.JDSPTPGUk BOE8JOEPXTkBSF SFHJTUFSFEUSBEFNBSLTPG .JDSPTPGU$PSQPSBUJPO 5IJTEPDVNFOUJTOPU JOUFOEFEUPCFVTFEGPS JOTUBMMBUJPOQVSQPTFT8F USZUPLFFQPVSQSPEVDU JOGPSNBUJPOVQUP EBUFBOEBDDVSBUF8F DBOOPUDPWFSBMMTQFDJGJD BQQMJDBUJPOTPSBOUJDJQBUF BMMSFRVJSFNFOUT"MM TQFDJGJDBUJPOTBSFTVCKFDU UPDIBOHFXJUIPVUOPUJDF 'PS5FDIOJDBM4VQQPSU DBMM 5FDIOJDBM4QFDJGJDBUJPOT PHYSICAL Overall Dimensions:Š8YŠ)YŠ% Shipping Weight:MCT Color:3FE ENVIRONMENTAL Operating Temperature:m'UPm' m$UP m$ Humidity:UPSFMBUJWFIVNJEJUZ OPO DPOEFOTJOH ELECTRICAL 6820 Primary AC:"$!)[ "5PUBM "DDFTTPSZ-PBE"!7%$QPXFSMJNJUFE Standby Current:N" Alarm Current:N" Battery Charging Capacity:UP") Battery Size:")NBYBMMPXFEJODPOUSPMQBOFM DBCJOFU-BSHFSDBQBDJUZCBUUFSJFTDBOCFIPVTFEJO 3##BDDFTTPSZDBCJOFU ]#] g)POFZXFMM*OUFSOBUJPOBM*OD FLEXPUT CIRCUITS Six programmable circuits which can be programmed individually as: Notification Appliance Circuits:"!7%$ QFSDJSDVJU QPXFSMJNJUFE XJUIBQBOFMNBYJNVN DVSSFOUPG" Auxiliary power circuits:"!7%$QFSDJSDVJU QPXFSMJNJUFE Initiating Circuits (Circuits 5 and 6 Only):N" !7%$QFSDJSDVJU QPXFSMJNJUFE 4VQQPSUT$MBTT# 4UZMF BOE$MBTT" 4UZMF DPOfiHVSBUJPOGPS4-$ 4#64 BOE'MFYQVUDJSDVJUT WIRING:4FFUIFQSPEVDUNBOVBMGPSXJSJOHEFUBJMT Honeywell Silent Knight $MJOUPOWJMMF3PBE /PSUIGPSE $5 XXXTJMFOULOJHIUDPN CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No.:7165-0559:0500 CATEGORY:7165 - FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE:SILENT KNIGHT SECURITY One Fire-Lite Place, Northford, CT, 06472 Contact: Brant,Lisa (203) 484-6277 (203) 484-7309 Email: lisa.brant@honeywell.com DESIGN: Silent Knight Model 6820 and 6820-EVS, Fire Alarm Control Unit, automatic, manual, local, remote station (PPU), central station (PPU), releasing (water deluge only) and mass notification services (6820- EVS). *The CELL-MOD and CELL-CAB-SK have the option to be configured by a compatible control unit for the following pathways: Cellular only without a backup path, primary Cellular communication path, or secondary Cellular communication path. Model 6820 System Components: 5860 Remote Annunciator 6855 Remote Annunciator 6860 Remote Annunciator 5496 NAC Expander 5880 LED I/O Module 5865-3 Remote LED Annunciator 5865-4 Remote LED Annunciator 5883 Relay Interface 5824 Serial/Paralell Printer Interface Module 5895XL Power Supply SK-NIC Network Inerface Card SK-FML Mulit Mode Fiber Card SK-FSL Single Mode Fiber Card CELL-MOD Celullar Communicator in Plastic Enclosure CELL-CAB-SK Cellular Communicator in Metal Enclosure with Lock & Key RBB Remote Battery Box (16"WX10"HX6"D) SK-SKC Seismic Complaince Kit 5815XL SLC Expander Page 1 of 3 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 6815 SLC Expander Model 6820EVS System Components: EVS-50W 50 Watt Amplifier EVS-100W 100 Watt Amplifier EVS-125W 125 Watt Amplifier EVS-100WBU External Backup Amplifier EVS-INT50W 50 Watt Internal Amplifier EVS-CE4 Circuit Audio Expander EVS-SW24 24 Switch Expander EVS-VCM Voice Control Module EVS-LOC Local Operator Control 5860 Remote Annunciator 6855 Remote Annunciator 6860 Remote Annunciator 5496 NAC Expander 5880 LED I/O Module 5865-3 Remote LED Annunciator 5865-4 Remote LED Annunciator 5883 Relay Interface 5824 Serial/Paralell Printer Interface Module 5895XL Power Supply SK-NIC Network Inerface Card SK-FML Mulit Mode Fiber Card SK-FSL Single Mode Fiber Card CELL-MOD Celullar Communicator in Plastic Enclosure CELL-CAB-SK Cellular Communicator in Metal Enclosure with Lock & Key RBB Remote Battery Box (16"WX10"HX6"D) SK-SCK Seismic Complaince Kit 5815XL SLC Expander Page 2 of 3 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 6815 SLC Expander SK-NIC-KIT RATING: Primary Operating Power Supply: 120VAC, 60HZ, 3.25A Secondary Operating Power Supply: 24VDC, 750 mA, 55Ah INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as a commercial fire alarm control unit for use with separately listed initiating and indicating devices and for mass notication. Refer to listee’s Installation Instruction Manual for details. NOTES: This listing is based upon technical data submitted by the applicant. OSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: 05/10/2025 Listing Expires: 06/30/2026 Authorized By: Michael Huang, Program Coordinator Fire Engineering & Investigations Division *Rev 10-02-19 gt Page 3 of 3 ISO 9001:2008 Standard ISO 14001:2004 Standard 6FM12 (12V12Ah) LONGWAY®Standard battery is design for a general purpose by KaiYing Power.6FM12 is a general purpose battery up to 5 years in star service or more than 260 cycles at 100%discharge in cycle service.As with all LONGWAY®batteries,all are rechargeable highly efficient,leak proof and maintenance free. Specifications: Dimensions:L151*W98*H93(TH100) Constant Power Discharge Characteristics (A,25℃) F.V/TIME 5min 10min 15min 30min 60min 2h 3h 5h 8h 10h 20h 9.60 45.6 28.8 22.8 13.2 7.80 4.26 3.05 2.07 1.33 1.12 0.61 9.90 44.2 27.9 22.2 12.9 7.61 4.24 3.03 2.06 1.33 1.12 0.61 10.2 43.3 27.4 21.9 12.7 7.49 4.20 3.00 2.04 1.31 1.11 0.60 10.5 42.0 26.5 21.2 12.3 7.25 4.16 2.97 2.02 1.32 1.11 0.60 10.8 40.7 25.7 20.8 12.0 7.11 4.12 2.94 2.00 1.31 1.10 0.60 Constant Power Discharge Characteristics (Watt,25℃) F.V/TIME 5min 10min 15min 30min 60min 2h 3h 5h 8h 10h 20h 9.60 509 325 260 151 90.3 49.9 36.2 24.7 15.9 13.4 7.31 9.90 494 315 253 147 88.1 49.6 36.0 24.6 15.9 13.5 7.32 10.2 483 309 250 145 86.7 49.1 35.6 24.4 15.8 13.3 7.24 10.5 468 299 242 141 84.0 48.6 35.3 24.1 15.8 13.3 7.22 10.8 454 290 237 138 82.4 48.2 34.9 23.9 15.7 13.2 7.20 Cells per Unit 6 Normal Voltage 12V Capacity 12Ah@20Hr-rate to 1.75V per cell@25℃ Weight Approx.(3.24 ±3)%kg (7.14lbs) Maximum Discharge Current 120A(5sec) Internal Resistance Approx.18mΩ full charged @25℃ OperatingTemperature Range Discharge:-15℃~50℃ Charge:-15℃~40℃ Storage:-15℃~40℃ Nominal OperatingTemperature Range 25℃±3℃ Float Charging Voltage 13.7~13.9VDC/unit Average @25℃ Maximum Charging Current 3.6A Equalization and Cycle Service 14.4V~15.0VDC/unitAverage @ 25℃ Self Discharge LONGWAY Valve Regulated Lead Acid (VRLA)batteriescan be stored for more than 6 months at 25℃.Self-discharge ratio less than3% per month at 25℃.Please charge batteries before using. Terminal F2(0.250) Container Material ABS(UL94-HB) *Flammability resistance of (UL94-V0)can be available upon request 6FM12 (12V12Ah) LONGWAY®Standard battery is design for a general purpose by KaiYing Power.6FM12 is a general purpose battery up to 5 years in star service or more than 260 cycles at 100%discharge in cycle service.As with all LONGWAY®batteries,all are rechargeable highly efficient,leak proof and maintenance free. Specifications: Dimensions:L151*W98*H93(TH100) Constant Power Discharge Characteristics (A,25℃) F.V/TIME 5min 10min 15min 30min 60min 2h 3h 5h 8h 10h 20h 9.60 45.6 28.8 22.8 13.2 7.80 4.26 3.05 2.07 1.33 1.12 0.61 9.90 44.2 27.9 22.2 12.9 7.61 4.24 3.03 2.06 1.33 1.12 0.61 10.2 43.3 27.4 21.9 12.7 7.49 4.20 3.00 2.04 1.31 1.11 0.60 10.5 42.0 26.5 21.2 12.3 7.25 4.16 2.97 2.02 1.32 1.11 0.60 10.8 40.7 25.7 20.8 12.0 7.11 4.12 2.94 2.00 1.31 1.10 0.60 Constant Power Discharge Characteristics (Watt,25℃) F.V/TIME 5min 10min 15min 30min 60min 2h 3h 5h 8h 10h 20h 9.60 509 325 260 151 90.3 49.9 36.2 24.7 15.9 13.4 7.31 9.90 494 315 253 147 88.1 49.6 36.0 24.6 15.9 13.5 7.32 10.2 483 309 250 145 86.7 49.1 35.6 24.4 15.8 13.3 7.24 10.5 468 299 242 141 84.0 48.6 35.3 24.1 15.8 13.3 7.22 10.8 454 290 237 138 82.4 48.2 34.9 23.9 15.7 13.2 7.20 Cellsper Unit 6 Normal Voltage 12V Capacity 12Ah@20Hr-rate to 1.75V per cell@25℃ Weight Approx.(3.24 ±3)%kg(7.14lbs) Maximum Discharge Current 120A(5sec) Internal Resistance Approx.18mΩ full charged @25℃ Operating TemperatureRange Discharge:-15℃~50℃ Charge:-15℃~40℃ Storage:-15℃~40℃ Nominal Operating Temperature Range 25℃±3℃ FloatCharging Voltage 13.7~13.9VDC/unitAverage @25℃ Maximum Charging Current 3.6A Equalization and Cycle Service 14.4V~15.0VDC/unitAverage @ 25℃ SelfDischarge LONGWAY Valve Regulated Lead Acid (VRLA)batteries can be stored for more than 6 months at 25℃.Self-discharge ratio less than 3% per monthat 25℃.Please charge batteries before using. Terminal F2(0.250) Container Material ABS(UL94-HB) *Flammability resistance of (UL94-V0)can be available upon request 9 General Purpose DURA12-12F2 F2 Duracell® Ultra Valve Regulated Lead Acid (VRLA) batteries can be stored for more than 6 months at 25°C. Self-discharge ratio less than 3% per month at 25°C. Please charge batteries before using. General Purpose © 2014 DURACELL, a division of the Gillette Company, Bethel, CT 06801. DURACELL is a registered trademark of the Gillette Company, used under license. All rights reserved.The information contained on this specification is generally descriptive only and is not intended to make or imply any representation guarantee or warranty with respect to any cells and batteries. Cell and battery design/ specification are subject to modification without notice. www.batteriesplus.com DURA12-12F2 Battery Voltage and Charge Time for Standby Use FEATURES & BENEFITS • UL Listed for 6 amps of notification power • Power supply’s advanced switch mode design reduces damaging heat and manages power up to 50% more efficiently than other systems • 24 VDC filtered output voltage • Built-in synchronization for appliances from Gentex, AMSECO, System Sensor, and Wheelock • Four power-limited notification outputs; 2 Class A or 4 Class B, or 1 Class A and 2 Class B • NACs are programmable as notification appliance circuits, or as auxiliary power to be used as constant, resettable, or door holder power • 3 amps per output circuit • Ground fault detector • CSFM approved • Communicates to the FACP via 4-wire SBUS (wire runs up to 6000 ft) • AC loss delay option shuts off power to non-essential high current accessories like magnetic door holders • MEA approved • Lightweight design adds to ease of installation and reduces shipping costs • ANSI Cadence pattern output capability built-in • UL 864,1481 & 1971 listed • OSHPD (CA) OSP-0065-10 (see accessories) 5496 Intelligent Power Module The 5496 intelligent power module is the most cost-effective power supply available today. It delivers 6 amps of notification appliance circuit power and built-in synchronization for appliances from System Sensor®,Gentex®, AMSECO, and Wheelock®. The 5496’s advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies. The 5496 is a 6 amp notification power expander that provides its own AC power connection, battery charging circuit, and backup battery for use with the Honeywell Silent Knight series fire alarm control panels (FACPs). The 5496 is the cost-effective solution for powering notification appliances required by the Americans with Disabilities Act (ADA). The 5496 has built-in ANSI cadence pattern. The output circuits can be programmed as notification appliance circuits, or as auxiliary power (configurable for constant, resettable, or door holder power). Compatibility The 5496 is compatible with the following Honeywell Silent Knight FACPs: • 6820 / 6820EVS • 5820XL / 5820XL-EVS • 6808 • 6700 • 5808 • 5700 5496 For a complete listing of all compliance approvals and certifications, please visit www.silentknight.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. System Sensor® and Honeywell® are registered trademarks of Honeywell International, Inc This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, call 800-446-6444 5496 Technical Specifications PHYSICAL Overall Dimensions: 16" H x 12.25" W x 3" D (40.6 x 30.9 x 7.6 cm) Shipping Weight: 8.7lbs ENVIRONMENTAL Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity: 10 to 93% relative humidity (non- condensing) ELECTRICAL: AC Input: 120VAC at 2.7A Output: 24VDC at 6A Standby & Alarm Current: 10mA Notification/Aux. Power Circuits: 4 Output Configuration: 2 Class A (Style Z) 4 Class B (Style Y) 1 Class A & 2 Class B Amps Per Output Circuit: 3.0 (6.0 amps total) Notification Circuit Output: 20.4 – 27.3VDC @ 3.0A each End-of-Line Resistance: 4.7k W EOL resistor required on each Class B circuit Battery Charging Capacity: 7.0 – 35.0AH ORDERING INFORMATION 5496: Intelligent Power Module ACCESSORIES RBB: Remote Battery Box Accessory Cabinet. 16” W x 10” H x 6” D (406 mm W x 254 mm H x 152 mm D) SK-SCK: Seismic Compliance Kit AGENCY LISTINGS AND APPROVALS • CSFM approved • NFPA 72 • UL listed • FM approved • City of NY: 429-90-E Vol XIV Doc 350387| Rev F| 11/17 © 2017 Honeywell International Inc. For more information Learn more about Silent Knight's Product and other products available by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472 800-328-0103 www.silentknight.com CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No.:7300-0559:0171 CATEGORY:7300 - FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE:SILENT KNIGHT SECURITY One Fire-Lite Place, Northford, CT, 06472 Contact: Brant, Lisa 2034846105 Email: lisa.brant@honeywell.com DESIGN: Model 5496 Intelligent power module. The power module consists of the following: Model 054960; main board Model 122599; enclosure Model SK-F485C; fiber to sbus converter Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 120 VAC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as a power module for use with listee's Models 5820XL and IFP-1000 (CSFM No. 7165-0559-135), 5808 and IFP-100 (CSFM No. 7165-0559-142), IFP-50 and 5700 (CSFM No. 7165-0559-144), IFP-100ECS and IFP-1000ECS (CSFM No. 7165-0559- 169) fire alarm control units. Refer to listee’s Installation Instruction Manual for details. NOTES: 03-06-13 gt Page 1 of 2 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE This listing is based upon technical data submitted by the applicant. OSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: 05/03/2025 Listing Expires: 06/30/2026 Authorized By: Michael Huang, Program Coordinator Fire Engineering & Investigations Division Page 2 of 2 FEATURES & BENEFITS • 80-character backlit LCD display (4 lines with 20 characters per line) • Tactile / audible feedback when a key is pressed on the annunciator • Uses the RS-485 SBUS to interface with the panel • Support for simultaneous use of multiple 5860s • Easily view current status by alarms, supervisories, or troubles • Five Status LEDs • Available in red or light gray color • Accommodates wiring lengths up to 6000 ft. from the control panel for added design and install flexibility • Accepts user codes or fire fighter’s key • Larger keypad buttons makes it easier to maneuver for system reset and silencing 5860 Remote Annunciator The 5860 remote annunciator, can be used to operate and program Honeywell Silent Knight fire alarm control panels (FACPs) from anywhere within the system. The 5860 features include an 80-character backlit LCD providing easy-to understand system messages. The annunciator is ergonomically designed with over-sized buttons for the most frequently used features, like Reset and Silence. In addition to status messages displayed on the LCD, there are five LEDs for alarm, supervisory, trouble, silence, and AC power status. The 5860 annunciator is available in gray to match virtually any decor and red for applications where the annunciator must stand out. The annunciator enclosure can be surface or flush mounted. A trim ring kit is available for surface mounting. COMPATIBILITY The 5860 is compatible with the following Honeywell Silent Knight FACPs: 6820: Addressable fire alarm control panel with up to 1,110 addressable points 6820EVS: Addressable fire alarm control panel with an emergency communication systems and up to 1,110 addressable points 6808: Addressable fire alarm control panel with up to 198 addressable points 6700: Addressable fire alarm control panel with up to 100 addressable points 5820XL: Addressable fire alarm control panel 5820XL-EVS: Addressable fire alarm control panel with an emergency communication systems 5808: Addressable fire alarm control panel 5700: Addressable fire alarm control panel 5860 / 5860R For a complete listing of all compliance approvals and certifications, please visit www.silentknight.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Silent Knight® and Honeywell® are registered trademarks of Honeywell International, Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, call 800-446-6444. 5860 Technical Specifications PHYSICAL Dimensions: 9.1”W x 7.4”H x 1.5”D (23.1W x 18.8H x 3.8D cm) Shipping Weight: 2.8 lbs (1.3 kg) Color: 5860R: Red; 5860: Gray ENVIRONMENTAL Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity: 10% - 93% non-condensing) ELECTRICAL Operating Voltage: 24VDC Standby Current: 20mA Alarm Current: 25mA ORDERING INFORMATION 5860: Remote Annunciator, four line (4x20) LCD annunciator with 20 characters per line. Gray 5860R: Remote Annunciator, four line (4x20) LCD annunciator with 20 characters per line. Red ACCESSORIES 5860TR: Red Trim Ring for surface mounting 5860TG: Gray Trim Ring for surface mounting AGENCY LISTINGS AND APPROVALS UL listed CSFM approved Meets NFPA 72 requirements FM approved MEA approved Doc 350224 | Rev J | 12/17 © 2017 Honeywell International Inc. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472 800-328-0103 5860 Features - Available with 1, 4, 8 or 16 outputs - Fused or PTC ptotected outputs - Supervision: - AC Fail. - Battery Fail and Battery Presence - Built-in charger for sealed lead acid or gel type batteries - Instantaneous transfer to stand-by batteries - Short circuit and overload protection - AC input and DC output options - UL Listed in the U.S. and Canada - CSFM and MEA Approved - Lifetime Warranty - All units are available in grey or red enclosure AL600ULX Series Power Supply Configuration Reference Chart Key Features Altronix Model Number Input Rating:115VAC, 60Hz InputFuseRating Total Output Rating (A) PowerDistributionModule Class 2 Rated Power-Limited Outputs(auto-resettable) NumberofOutputs Fused Output Ratings PTC Output Ratings AccommodatesBatteries AL600ULX 3.5A 5A/250V 6A N/A –1 6A –Two (2) 7AH AL600ULXX Two (2) 12AH AL600ULPD4 PD4UL –4 3.5A –Two (2) 7AH AL600ULXPD4 Two (2) 12AH AL600ULPD4CB PD4ULCB P 4 –2.5A Two (2) 7AH AL600ULXPD4CB Two (2) 12AH AL600ULPD8 PD8UL –8 3.5A –Two (2) 7AH AL600ULXPD8 Two (2) 12AH AL600ULPD8CB PD8ULCB P 8 –2.5A Two (2) 7AH AL600ULXPD8CB Two (2) 12AH AL600ULXPD16 Two (2) PD8UL –16 3.5A –Two (2) 12AH AL600ULXPD16CB Two (2) PD8ULCB P 16 –2.5A Two (2) 12AH AL600ULPD8 AL600ULX Series Power Supply/Chargers Altronix AL600ULX series power supply/chargers convert a 115VAC, 60Hz input into a single fused, four (4), eight (8) or sixteen (16) fuse or PTC protected outputs. Outputs are selectable for 12VDC or 24VDC with a total of 6A max. Lifetime Warranty Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com Rev. 06282023 Input Voltage 115VAC, 60Hz, 3.5A max. Fusing 5A/250V Outputs Voltage 12VDC or 24VDC selectable Current 6A @ 12VDC or 24VDC continuous max. Protection Fused 3.5A / PTC 2.5A Other Overvoltage protection Filtered and regulated Battery Charging Capacity 7AH/12VDC (1 or 2 within enclosure) 12AH/12VDC (requires larger “X” enclosure) 40AH/65AH (requires separate enclosure) Type Sealed lead acid or gel type Failover Upon AC loss, instantaneous Batteries are sold separately Supervision AC Failure Form “C” contacts Battery Form “C” contacts Indicators (LED) Input 115VAC is present DC Output Powered Battery Discharged or not connected Agency Listings All Models: UL: UL294 Access Control System Units UL1481 Power Supplies for Fire Protective Signaling Systems cUL: CSA C22.2 No.205 Signal Equipment AL600ULX and AL600ULXX only: CSFM California State Fire Marshall Approved MEA NYC Department of Buildings Approved AL600ULX only: FM Factory Mutual Approved Physical and Environmental Dimensions (H x W x D) AL600ULX, AL600ULPD4(CB), AL600ULPD8(CB): Enclosure: 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm) Shipping: 15” x 13.875” x 4.75” (381mm x 352.4mm x 120.6mm) AL600ULXX, AL600ULXPD4(CB), AL600ULXPD8(CB), AL600ULXPD16(CB): Enclosure: 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) Shipping: 16.5” x 13.5” x 6” (419.1mm x 342.9mm x 152.5mm) Weight (approx.) Model Product Weight Shipping Weight AL600ULX 7.05 lb. (3.2 kg)8.9 lb. (4.1 kg) AL600ULXX 8.65 lb. (3.92 kg)10.95 lb. (4.97 kg) AL600ULPD4(CB)7.2 lb. (3.27 kg)9.05 lb. (4.1 kg) AL600ULXPD4(CB)8.7 lb. (3.95 kg)11.05 lb. (5.01 kg) AL600ULPD8(CB)7.3 lb. (3.31 kg)9.15 lb. (4.15 kg) AL600ULXPD8(CB)8.8 lb. (4.0 kg)11.15 lb. (5.06 kg) AL600ULXPD16(CB)8.95 lb. (4.06 kg)11.25 lb. (5.1 kg) Temperature Operating: 0ºC to 49ºC (32ºF to 120ºF) Storage: – 20ºC to 70ºC (– 4ºF to 158ºF) Relative Humidity 85% +/– 5% BTU/Hr (approx.) 12VDC: 37 BTU/Hr. 24VDC: 74 BTU/Hr. Specifications Lifetime Warranty Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com AL600ULX Series Power Supply/Chargers Lifetime Warranty Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com AL600ULX Series Power Supply/Chargers AL600ULX, AL600ULPD4(CB), AL600ULPD8(CB) Dimensions (H x W x D approximate) 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm) Dimensions and Drawing 1.40”(35.6mm)1.40”(35.6mm) 1.40” (35.6mm) 4.85” (123.2mm)4.85” (123.2mm)3.25” (82.6mm)0.75”(19.1mm)0.75”(19.1mm)11.0” (279.4mm) 12.5” (317.5mm)1.20”(30.5mm)1.20”(30.5mm) 0.9375” (23.8mm) 0.9375” (23.8mm)5.10” (129.5mm)1.40” (35.6mm)5.10” (129.5mm)6.5625” (166.7mm)3.25” (82.6mm)3.25” (82.6mm)3.25” (82.6mm)10.5” (266.7mm)1.0”(25.4mm)1.0”(25.4mm) 1.0” (25.4mm)13.0” (330.2mm)5.10” (129.5mm)1.20”(30.5mm) Lifetime Warranty Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com AL600ULX Series Power Supply/Chargers AL600ULXX, AL600ULXPD4(CB), AL600ULXPD8(CB), AL600ULXPD16(CB) Dimensions (H x W x D approximate) 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) Dimensions and Drawing 1.5”(38.1mm)1.5”(38.1mm)4.615” (117.2mm)4.615” (117.2mm) 1.5”(38.1mm)1.5”(38.1mm)4.615” (117.2mm)4.615” (117.2mm) 1.75”(44.5mm) 1.75”(44.5mm) 1.375” (34.9mm) 1.125” (28.6mm) 1.5”(38.1mm)1.5”(38.1mm)5.0” (127.0mm)5.0” (127.0mm)4.5” (114.3mm)4.5” (114.3mm)1.25” (31.8mm) 1.25” (31.8mm)0.79” (20.1mm)0.91” (23.1mm)0.91” (23.1mm)15.5” (393.7mm)1.1” (27.9mm) 1.1” (27.9mm) 1.1” (27.9mm)12.23” (310.6mm) 2.0”(50.8mm) 2.0”(50.8mm) 1.25” (31.8mm)1.25” (31.8mm) CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No.:7315-1335:0104 CATEGORY:7315 - POWER UNITS LISTEE:Altronix 140 58th Street, Bldg A, Ste 2N, Brooklyn, NY, 11220 Contact: Zatz, Gary (718) 567-8181 (718) 567-9056 Email: garyz@altronix.com DESIGN: Models AL600ULX and AL600ULM Power Supply Unit. Model AL600ULM is an AL600ULX power supply with an MOM5 multi-output power module. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 115 VAC input, 12 or 24 VDC output INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as power supply units for use with separately listed compatible fire alarm control units*. Also suitable for use with access control systems. Authority having jurisdiction should be consulted prior to installation. NOTES: For fire alarm use, the standby batteries must provide at least 24 hours standby power during power loss. The battery circuit must be fully supervised. This listing is based upon technical data submitted by the applicant. OSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: 04/10/2025 Listing Expires: 06/30/2026 Authorized By: Michael Huang, Program Coordinator Fire Engineering & Investigations Division 11-09-98 Page 1 of 1 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No.:7272-0559:0149 PARENT LISTING No.:7272-0028:0206 CATEGORY:7272 - SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE:SILENT KNIGHT SECURITY One Fire-Lite Place, Northford, CT, 06472 Contact: Brant, Lisa 2034846105 Email: lisa.brant@honeywell.com DESIGN:Models IDP-PHOTO, IDP-PHOTOR*, IDP-PHOTO-T, IDP-ACCLIMATE, SK- PHOTO, SK-PHOTOR*, SK-PHOTO-T and SK-ACCLIMATE photoelectric type smoke detectors. Model IDP-PHOTO-T employs a 1350F supplement integral heat sensor which only assists in a fire situation. This thermal circuitry is NOT approved for use in lieu of a required heat detector. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING:24 VDC INSTALLATION:In accordance with listee's printed installation instructions, applicable codes & ordinances and in manner acceptable to the authority having jurisdiction. MARKING:Listee's name, product number, electrical rating and UL label. APPROVAL:Listed as photoelectric type smoke detector for use with listee's separately listed compatible fire alarm control units and bases. All models are suitable for open areas and inside duct installations with air velocities between 0-4000 FPM. Models IDP- PHOTO and IDP-PHOTOR are approved for installations inside System sensor duct housing DNR (OSFM Listing No. 3242-1653:209) and DNRW (OSFM Listing No. 3242- 1653:210)*. Models SK-PHOTO and SK-PHOTOR are approved for installations inside Silent Knight SK-DUCT (OSFM Listing No. 3242-0559:162) and System Sensor DNRW (OSFM Listing No. 3242-1653:210)* NOTES:The photoelectric type detectors are generally more effective at detecting slow, smoldering fires that smolder for hours before bursting into flame. Sources of these fires may include cigarettes burning in couches or bedding. The ionization type detectors are generally more effective at detecting fast, flaming fires that consume combustible materials rapidly and spread quickly. Sources of these fires may include paper burning in a waste container or a grease fire in the kitchen. *Rev. 02-01-10 fm This listing is based upon technical data submitted by the applicant. OSFM Fire Engineering staff has reviewed the test resultsand/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria.Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: 07/07/2025 Listing Expires: 06/30/2026 Authorized By: Michael Huang , Program Coordinator Fire Engineering & Investigations Division Page 1 of 1 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No.:7272-0559:0517 CATEGORY:7272 - SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE:SILENT KNIGHT SECURITY One Fire-Lite Place, Northford, CT, 06472 Contact: Brant, Lisa 2034846105 Email: lisa.brant@honeywell.com DESIGN:Models IDP-FIRE-CO-W, IDP-FIRE-CO-IV, SK-FIRE-CO-W, photoelectric smoke detector with complementary heat detector, electrochemical carbon monoxide (CO) detector and supplemental infrared flame sensor, analog addressable. Models IDP-PTIR-W, IDP-PTIR-IV, SK-PTIR-W, photoelectric smoke detector with complementary heat detector, and supplemental infrared flame sensor, analog addressable. Model SK-PHOTO-CO-W, photoelectric smoke detector with complementary carbon monoxide (CO) detector, analog addressable. Refer to listee's printed data sheet for additional detailed product description and operational considerations. RATING: 24 VDC INSTALLATION:In accordance with the listee’s printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING:Listee's name, model number, electrical rating, and UL label. APPROVAL:Listed as photoelectric smoke detector with complementary heat detector, and supplemental infrared flame sensor for use withSystem Sensor (S911) - Models B200S, B200S-WH, B200S-IV, B200SR, B200SR-WH, B200SR-IV, (CSFM Listing 7300- 1653:0213) *B200S-LF, *B200S-LF-IV, *B200S-LF-WH, B200SR-LF, B200SR-LF-WH, B200SR-LF-IV, (CSFM Listing 7300-1653:0238), B210LP, B300-6, B300-6-IV, B300-6- IS, B300-6-IS-W, B300-6-IS-IV, B501, B501-WHITE, B501-IV, B501-BL, (CSFM Listing 7300-1653:0109) B224BI, B224BI-WH, B224BI-IV, B224RB, B224RB-WH, B224RB-IV, (CSFM Listing 7300-1653:0126). Silent Knight (S6173) - Model IDP-6AB (CSFM Listing 7300-0559:0159). Fire-Lite (S1059) - Model B350LP (CSFM Listing 7300-0075:0192). NOTES: *Rev 08-02-19 gt This listing is based upon technical data submitted by the applicant. OSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: 05/06/2025 Listing Expires: 06/30/2026 Authorized By: Michael Huang, Program Coordinator Fire Engineering & Investigations Division Page 1 of 1 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No.:7270-0559:0147 PARENT LISTING No.:7270-0028:0196 CATEGORY:7270 - HEAT DETECTOR LISTEE:SILENT KNIGHT SECURITY One Fire-Lite Place, Northford, CT, 06472 Contact: Brant, Lisa 2034846105 Email: lisa.brant@honeywell.com DESIGN:Models IDP-HEAT and SK-HEAT* (fixed temperature), IDP-HEAT-ROR,IDP-HEAT-HT, SK-HEAT-ROR*, and SK-HEAT-HT*(fixed temperature with Rate-of-Rise) electronic heat detectors. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING:135°F fixed temperature for Models IDP-HEAT, IDP-HEAT-ROR, SK-HEAT* and SK- HEAT-ROR* 190°F fixed temperature for Model IDP-HEAT-HT and SK-HEAT-HT INSTALLATION:In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING:Listee's name, model number, electrical ratings, and UL label. APPROVAL:Listed as heat detectors for use with *listee’s separately listed compatible base and fire alarm control units. Refer to listee’s Installation Instructions Manual for details. NOTES: *Rev. 07-14-09 fm This listing is based upon technical data submitted by the applicant. OSFM Fire Engineering staff has reviewed the test resultsand/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria.Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: 07/07/2025 Listing Expires: 06/30/2026 Authorized By: Michael Huang , Program Coordinator Fire Engineering & Investigations Division Page 1 of 1 FEATURES & BENEFITS • Single contact monitor • SK-Minimon support for Class B (Style B) contact monitor wiring • Small and lightweight size allows for flexible mounting options • Rotary address switches for fast installation • UL Listed • CSFM Listed • FM Approved SK-MINIMON Intelligent Mini Monitor Module The SK-MINIMON is an addressable monitor modules for use with the Honeywell Silent Knight fire alarm control panels (FACPs). The SK- MINIMON acts as an interface to contact devices, such as waterflow switches and pull stations. The SK-MINIMON supports Class B supervised wiring to the load device. Conventional 4-wire smoke detectors can be monitored for alarm and trouble conditions The SK-MINIMON can be mounted in a single gang junction box directly behind the monitored device. Its small size and light weight allow it to be installed without rigid mounting requirements. INSTALLATION The SK-MINIMON can be mounted in a single gang junction box directly behind the monitored device. Its small size and light weight allow it to be installed without rigid mounting requirements. SK-MINIMON For a complete listing of all compliance approvals and certifications, please visit www.silentknight.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Silent Knight®, System Sensor® and Honeywell® are registered trademarks of Honeywell International, Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, call 800-446-6444. SK-MINIMON Technical Specifications PHYSICAL Dimensions: 2.75” W x 1.3" H x 0.5" D Weight: 1.2 oz (37 g) ELECTRICAL Operating Voltage: 15 – 32VDC SLC Standby and Alarm Current: 350 μA End-of-Line Resistance: 47K W Initiating device circuit wiring resistance: 1,500W max SLC loop resistance: 40W max Wire Length: 6” min. ENVIRONMENTAL Operating Temperature: 32ºF – 120ºF (0ºC – 49ºC) Humidity: 10% – 93% non-condensing ORDERING INFORMATION SK-MINIMON: Mini monitoring module COMPATIBILITY The SK-MINIMON is compatible with the following Honeywell Silent Knight fire alarm control panels: 6820: Addressable fire alarm control panel 6820EVS: Addressable fire alarm control panel with an emergency voice system. 6808: Addressable fire alarm control panel 6700: Addressable fire alarm control panel 5700: Addressable fire alarm control panel 5808: Addressable fire alarm control panel 5820XL: Addressable fire alarm control panel 5820XL-EVS: Addressable fire alarm control panel with an emergency voice system Doc 350133 | Rev G | 11/17 © 2017 Honeywell International Inc. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472 800-328-0103 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No.:7300-0559:0155 PARENT LISTING No.:7300-0028:0219 CATEGORY:7300 - FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE:SILENT KNIGHT SECURITY One Fire-Lite Place, Northford, CT, 06472 Contact: Brant, Lisa 2034846105 Email: lisa.brant@honeywell.com DESIGN: Models IDP-Relay-6, SK-Relay-6, relay module, IDP-Control-6, SK -Control-6, supervising control module, IDP-Monitor-10, SK-Mon-10, input monitor module, IDP- Zone-6, SK-Zone-6 six zone interface module, IDP-Monitor, IDP-Minimon, IDP-Zone, SK-Monitor, SK-Minimon, SK-Zone monitor modules, IDP-Control, IDP-Relay, SK- Control, SK-Relay, control modules, IDP-Monitor-2, SK-Monitor-2, dual monitor modules,and *IDP-RELAYMON-2, *SK-RELAYMON-2 with 2 input/2 output relay modules. All devices are intended to be connected between the signaling line circuit of a compatible fire alarm control panel. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 16-33 VDC Primary INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in manner acceptable to the authority having jurisdiction. MARKING: Listee's name, product number and UL label. APPROVAL: Listed as control unit accessories for use with listee's separately listed compatible fire alarm control units. NOTES: If an external power supply is used for Model SK-Zone-6 and IDP-Zone-6, the negative of the external power supply is referenced to the negative of the auxiliary supply of the compatible control panel. This is done in order to detect ground faults on the initiating circuit. *Rev. 10-25-11 mt Page 1 of 2 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE This listing is based upon technical data submitted by the applicant. OSFM Fire Engineering staff has reviewed the test resultsand/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria.Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: 07/07/2025 Listing Expires: 06/30/2026 Authorized By: Michael Huang , Program Coordinator Fire Engineering & Investigations Division Page 2 of 2 FEATURES & BENEFITS • Two sets of Form C contacts • Rotary address switches for fast installation • Contacts are rated for a variety of amps (see Specifications) • Panel controlled status LED that flashes green in normal state and is solid red in alarm • Relay programming is completely flexible– can be mapped to zone conditions • Polling LED visible through the cover plate • SEMS screws for easy wiring • UL Listed SK-RELAY Intelligent Relay Module The SK-RELAY is an addressable relay module for use with Honeywell Silent Knight Series fire alarm control panels (FACPs). The SK-RELAY allows a Silent Knight FACP to switch discrete contacts by code command. The relay contains two isolated sets of Form C contacts, which operate as a DPDT switch. No supervision is provided for the notification appliance circuit. The SK-RELAY contacts can be used for virtually any normally open or normally closed application. Each SK-RELAY is programmed with a unique signaling line circuit (SLC) loop address. When an event occurs that controls the SK-RELAY, the relay is triggered by the FACP. INSTALLATION The SK-RELAY mounts directly into a 4” square electrical box. The box must have a minimum depth of 2-1/8”. A surface mount electrical box (System Sensor® PN SMB500) is available from Silent Knight. SK-RELAY For a complete listing of all compliance approvals and certifications, please visit www.silentknight.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Silent Knight®, System Sensor® and Honeywell® are registered trademarks of Honeywell International, Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, call 800-446-6444. SK-RELAY Technical Specifications PHYSICAL 4.675" H x 4.275" W x 1.4" D Shipping Weight: 6.3 oz (196 g) ELECTRICAL Operating Voltage: 15 – 32 VDC End-of-Line Resistance: Not used SLC Standby & Alarm Current: .255mA max @ 24VDC (one communication every 5 sec with LED enabled) ENVIRONMENTAL Operating Temperature: 32ºF – 120ºF (0ºC – 49ºC) Humidity: 10% – 93% non-condensing RELAY CONTACT RATINGS 3.0A @ 30VDC resistive 0.9A @ 110VDC resistive 0.9A @ 125VAC resistive 0.5A @ 125VAC inductive (PF = .35) 0.7A @ 75VAC inductive (PF = .35) ORDERING INFORMATION SK-RElAY: Relay Module ACCESSORIES. SMB500: 4” Square Surface Mount Electrical Box CB500 :Module Barrier COMPATIBILITY The SK-RELAY is compatible with the following Honeywell Silent Knight fire alarm control panels: 6820: Addressable fire alarm control panel 6820EVS: Addressable fire alarm control panel with an emergency mass notification system. 6808: Addressable fire alarm control panel 6700: Addressable fire alarm control panel 5700: Addressable fire alarm control panel 5808: Addressable fire alarm control panel 5820XL: Addressable fire alarm control panel 5820XL-EVS: Addressable fire alarm control panel with an emergency mass notification system. Doc 350127| Rev G| 11/17 © 2017 Honeywell International Inc. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472 800-328-0103 FEATURES & BENEFITS • Installer can open station without causing an alarm condition • Dual-color LED is visible through handle of station blinks green to indicate normal operation and remains steady red in an alarm condition • Key operated test and reset lock using lock plate actuator • Key matches compatible FACP locks • Meets ADA requirement for 5 lbs maximum pull force to active • Meets the Americans with Disabilities Act Accessibility Guidelines (ADAAG) controls and operating mechanisms guidelines (Section 4.1.3[13]) • Shell, door, and handle molded from durable LEXAN® • Reliable analog communications for trouble-free operation • Braille text on station handle • Rotary address switches for fast installation • Handle latches in down position and the word Activated appears, clearly indicating the station has been pulled • UL Listed, including UL 38, Standard of Manually Actuated Signaling System • CSFM Listed • MEA Listed SK-PULL-SA / SK-PULL-DA Intelligent Pull Stations The SK-PULL-SA is a single action pull station requiring only one motion to activate the station. The SK-PULL-DA is a dual action pull station requiring two motions to active the station. The SK-PULL-SA and SK-PULL-DA are for use with Honeywell Silent Knight Series fire control panel (FACP). Extremely easy to operate, the SK-PULL-DA and SK-PULL-SA provide a fast and practical means of manually initiating a fire alarm signal. The FACP recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. INSTALLATION The SK-PULL-SA and SK-PULL-DA can be surface mounted to an SB-I/O surface back box or semi-flush mounted on a standard single-gang with a minimum depth of 2.13”(5.40 cm) or double gang or 4” (10.61 cm) square electrical box. You can also use the optional (System Sensor® PN BG-TR) trim ring if the station is being semi-flush mounted. SK-PULL-SA SK-PULL-DA For a complete listing of all compliance approvals and certifications, please visit www.silentknight.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Silent Knight®, System Sensor® and Honeywell® are registered trademarks of Honeywell International, Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, call 800-446-6444. SK-PULL-SA / SK-PULL-DA Technical Specifications PHYSICAL Dimensions: 5.5” H x 4" W x 1.45" D (14 x 10.2 x 3.7cm) Housing Material: LEXAN polycarbonate resin Bi-Colored LED: Blinking Green: Normal Steady Red: Alarm Switch: Single pole, single throw (SPST) normally open (N/O) switch which closes upon activation of the pull station ELECTRICAL Operating Voltage: 15 – 32VDC SLC Standby and Alarm Current: 350μA Wire Gauge: Up to 12AWG (3.1 mm2) ENVIRONMENTAL Operating Temperature: 32ºF – 120ºF (0ºC – 49ºC) Humidity: 10% – 93% non-condensing ORDERING INFORMATION SK-Pull-SA: Single Action Pull Station SK-Pull-DA: Dual Action Pull Station ACCESSORIES BG-TR: Optional trim ring. SB-I/O: Surface backbox, indoor/outdoor. * Unless otherwise noted, specifications apply to SK-Pull-SA and SK-Pull-DA COMPATIBILITY The SK-PULL-SA AND SK-PULL-DA are compatible with the following Honeywell Silent Knight fire alarm control panels: 6820: Addressable fire alarm control panel 6820EVS: Addressable fire alarm control panel with an emergency voice system. 6808: Addressable fire alarm control panel 6700: Addressable fire alarm control panel 5700: Addressable fire alarm control panel 5808: Addressable fire alarm control panel 5820XL: Addressable fire alarm control panel 5820XL-EVS: Addressable fire alarm control panel with an emergency voice system Doc 350135 | Rev E | 11/17 © 2017 Honeywell International Inc. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472 800-328-0103 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No.:7150-0559:0161 PARENT LISTING No.:7150-0028:0199 CATEGORY:7150 - FIRE ALARM PULL BOXES LISTEE:SILENT KNIGHT SECURITY One Fire-Lite Place, Northford, CT, 06472 Contact: Brant, Lisa 2034846105 Email: lisa.brant@honeywell.com DESIGN: Models SK-PULL-SA and SK-PULL-DA single/dual action fire alarm pull boxes. Refer to listee's data sheet for detailed product description and operational considerations. RATING: INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, rating, and UL label. APPROVAL: Listed as fire alarm pull boxes for use with separately listed compatible fire alarm control units. Refer to listee’s Installation Instruction Manual for details. * These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition with California amendments. NOTES: This listing is based upon technical data submitted by the applicant. OSFM Fire Engineering staff has reviewed the test resultsand/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria.Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: 07/07/2025 Listing Expires: 06/30/2026 04-16-09 Page 1 of 2 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE Authorized By: Michael Huang , Program Coordinator Fire Engineering & Investigations Division Page 2 of 2 Agency Listings AVDS115-02 • 12/3/2019 • Page 1 MEA452-05-E3023572 7300-1653:187 (outdoor strobes) 7125-1653:188 (horn strobes, chime strobes) 7135-1653:189 (horns, chimes) S4011 (chimes, horn strobes, horns) S3593 (outdoor and alert strobes) Features • Weatherproof per NEMA 4X, IP56 • Listed to UL 1638 (strobe) and UL 464 (horn) • Compatible with System Sensor synchronization protocol and legacy SpectrAlert products • Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 • Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela • Rotary switch for horn tone and three volume selections • Horn rated at 88+ dBA at 16 volts • Rated from –40°F to 151°F • Universal mounting plate with an onboard shorting spring that tests wiring continuity before devices are installed • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Listed for ceiling or wall mounting SpectrAlert Advance offers the broadest line of outdoor horns, strobes, and horn strobes in the industry. With white or red plastic housings, wall or ceiling mounting options, and plain or FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement, including indoor, outdoor, wet, and dry applications in temperatures from −40°F to 151°F. Like the entire SpectrAlert Advance line, outdoor horns, strobes, and horn strobes for wall applications include a variety of features that increase application flexibility and simplify installation. First, field-selectable settings, including candela, automatic selection of 12- or 24-volt operation, horn tones, and three volume options enable installers to easily adapt devices to meet requirements. Next, SpectrAlert Advance devices use a universal mounting plate for both wall and ceiling applications. This mounting plate includes an onboard shorting spring that ensures wiring continuity before devices are installed, so installers can verify proper wiring without mounting the devices and exposing them to potential construction damage. Once the plates are mounted, all SpectrAlert Advance devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults. Outdoor devices ship with weatherproof plastic back boxes (metal back boxes are available separately) that accommodate in-and- out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater corrosion. Knock-outs located on the back eliminate the need to drill holes for screw-in mounting. Plastic and metal weatherproof back boxes come with ¾-inch top and bottom conduit entries and ¾-inch knock-outs at the back. A screw-in NPT plug with an O-ring gasket for a watertight seal is included with each back box. Outdoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications SpectrAlert® Advance outdoor audible visible products are rich with features that cut installation times and maximize profits. AVDS115-02 • 12/3/2019 • Page 2 SpectrAlert Advance Outdoor Horn, Strobe, and Horn StrobeSpecifications Architect/Engineer Specifications General SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Outdoor SpectrAlert Advance products shall operate between −40 and 151 degrees Fahrenheit from a regulated DC or full- wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options shall be set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn or horn strobe models shall operate on a coded or non-coded power supply. The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. Physical/Electrical Specifications Operating Temperature –40°F to 151°F (–40°C to 66°C) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage with MLD3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens)5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D) Horn Dimensions 5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D) Wall-Mount Weatherproof Back Box Dimensions (SA-WBB)5.7˝ L × 5.1˝ W × 2.0˝ D (145 mm L × 130 mm W × 51 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC FWR DC FWR Standard Candela Range 15 123 128 66 71 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High Candela Range 135 NA NA 228 207 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd) DC Input 8–17.5 Volts 16–33 Volts 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd) DC Input 16–33 Volts FWR Input 16–33 Volts 135 150 177 185 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC FWR DC FWR Temporal High 57 55 69 75 Temporal Medium 44 49 58 69 Temporal Low 38 44 44 48 Non-Temporal High 57 56 69 75 Non-Temporal Medium 42 50 60 69 Non-Temporal Low 41 44 50 50 Coded High 57 55 69 75 Coded Medium 44 51 56 69 Coded Low 40 46 52 50 UL Current Draw Data Horn Tones and Sound Output DataCandela Derating For K series products used at low temperatures, listed candela ratings must be reduced in accordance with this table. Strobe Output (cd) Listed Candela Candela rating at –40°F 15 Do not use below 32°F15/75 30 75 44 95 70 110 110 115 115 135 135 150 150 177 177 185 185 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts 24-Volt Nominal Reverberant Anechoic DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non- Temporal High 82 82 88 88 93 92 100 100 5 Non- Temporal Medium 78 78 85 85 90 90 98 98 6 Non- Temporal Low 75 75 81 81 88 84 96 92 7†Coded High 82 82 88 88 93 92 101 101 8†Coded Medium 78 78 85 85 90 90 97 98 9†Coded Low 75 75 81 81 88 85 96 92 †Settings 7, 8, and 9 are not available on 2-wire horn strobe. 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2019 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS115-02 • 12/3/2019 SpectrAlert Advance Diagrams Model Description Red White Wall Horn Strobes P2RK P2WK 2-Wire Horn Strobe, Standard cd, Outdoor (includes plastic weatherproof back box) P2RK-P P2WK-P 2-Wire Horn Strobe, Standard cd, Outdoor, Plain (includes plastic weatherproof back box) P2RK-R P2WK-R 2-Wire Horn Strobe, Standard cd, Outdoor (does not include plastic weatherproof back box) P2RHK P2WHK 2-Wire Horn Strobe, High cd, Outdoor (includes plastic weatherproof back box) P2RHK-P P2WHK-P 2-Wire Horn Strobe, High cd, Outdoor, Plain (includes plastic weatherproof back box) P2RHK-R P2WHK-R 2-Wire Horn Strobe, High cd, Outdoor (does not include plastic weatherproof back box) P4RK P4WK 4-Wire Horn Strobe, Standard cd, Outdoor (includes plastic weatherproof back box) P4RK-R —4-Wire Horn Strobe, Standard cd, Outdoor (does not include plastic weatherproof back box) P2RHK-120 —2-Wire Horn Strobe, High cd, Outdoor, 120 V (includes plastic weatherproof back box) Wall Strobes SRK SWK Strobe, Standard cd, Outdoor (includes plastic weatherproof back box) SRK-P SWK-P Strobe, Standard cd, Outdoor, Plain (includes plastic weatherproof back box) SRK-R SWK-R Strobe, Standard cd, Outdoor (does not include plastic weatherproof back box) SRHK SWHK Strobe, High cd, Outdoor (includes plastic weatherproof back box) SRHK-P SWHK-P Strobe, High cd, Outdoor, Plain (includes plastic weatherproof back box) SRHK-R SWHK-R Strobe, High cd, Outdoor (does not include plastic weatherproof back box) Horns HRK —Horn, Red, Outdoor (includes plastic weatherproof back box) HRK-R —Horn, Red, Outdoor (does not include plastic weatherproof back box) Accessories SA-WBB SA-WBBW Metal Weatherproof Back Box WTP WTPW Metal Weatherproof Outdoor Flush-mounting Plate SpectrAlert Advance Ordering Information Notes: All -P models have a plain housing (no “FIRE” marking on cover). All -R models require metal weatherproof outdoor flush mounting plate or a metal weatherproof outdoor back box (order separately). “Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. When replacing standard outdoor units both the device and back box must be replaced. 4.7˝ 5.6˝ 6.8˝Dia. 2.5˝ 2.5˝64mm119mm 142mm Wall-Mount Horn Strobes Wall Plastic Weatherproof Back Box Wall-Mount Horn Strobe with Plastic Weatherproof Back Box CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No.:7125-1653:0188 CATEGORY:7125 - FIRE ALARM DEVICES FOR THE HEARING IMPAIRED LISTEE:System Sensor, Unincorporated Div of Honeywell Int'l Inc. 3825 Ohio Ave, St. Charles, IL, 60174 Contact: Brant,Lisa (203) 484-6105 (203) 484-7309 Email: lisa.brant@honeywell.com DESIGN: Models CHSR and CHSW Chime/Strobes. Models P2R, P2W, P2RH and P2WH Horn/Strobes two-wire type, rectangular enclosure. Models PC2R, PC2W, PC2RH and PC2WH Horn/Strobes two-wire type, round enclosure Models P4R, P4W, P4RH and P4WH Horn/Strobes four-wire type, rectangular enclosure. Models PC4R, PC4W, PC4RH and PC4WH Horn/Strobes* four-wire type, round enclosure. All models are intended for indoor use only unless other wise indicated. Models may be followed by the suffix “K” indicating indoor or outdoor use, or may be followed by suffix “P” for plain housing with no lettering. “K” suffix models are suitable for outdoor applications at temperatures from -40°F to +151°F (- 40°C to +66°C) and are rated NEMA 4X when used with the System Sensor weather proof back boxes models SA-WBB (Wall), SA-WBBW (Wall), SA-WBBC (Ceiling) and *SA-WBBCW (Ceiling). Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: Standard Horn/Strobes and Chime/Strobes 8 - 17.5 or 16-33 VDC/FWR Hi CD Horn/Strobes 16-33 VDC/FWR INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances, and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as *horn/strobes or chime/strobes suitable for signaling appliances and equipment for the hearing impaired applications when used with separately listed compatible fire alarm control units. Horn/strobes with -K suffix are suitable for indoor or outdoor use, ceiling or wall mount. Chime section is suitable for private mode and indoor use only. Horn/Strobes or chime/strobes* can generate the distinctive three-pulse audible Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2010 Edition. Refer to listee’s Installation Instruction Manual for details. NOTES: Page 1 of 2 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING & INVESTIGATIONS DIVISION BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE This listing is based upon technical data submitted by the applicant. OSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: 05/12/2025 Listing Expires: 06/30/2026 Authorized By: Michael Huang, Program Coordinator Fire Engineering & Investigations Division *Corrected 12-15- 11 bh Page 2 of 2 SELECTABLE OUTPUT STROBES AND HORNS MODELS P1224MC, S1224MC . System Sensor SpectrAlert Series Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments for their use. Specifications subject to change without notice. © 2003 All Rights Reserved www.firecontrolinstruments.com 9020-0562/Ver. 1.1 Page 1 of 4 An ISO 9001 Company Building Intelligent Networks A Honeywell Company Description The System Sensor Spectralert® select- able output strobes and horn/strobes offer enhanced features that include the widest range of candela options available, and the capability to recognize and self-adjust for either 12 or 24 volt operation. Spectralert selectable candela wall- mounted strobes and horn/strobes offer key performance features long associated with the Spectralert name. The selectable candela strobes and horn/strobes offer av- erage current draws that are not only lower than conventional fixed-candela Spectralert products, but also lower than similar products by others. By con- suming less current, the ability to con- nect even more devices per circuit is pos- sible, resulting in lower installed cost. Spectralert selectable candela strobes and horn/strobes offer the same installation- friendly features synonymous with the Spectralert name, such as the option of 2- and 4-wire operation; the ability to use standard size backboxes with no encroach- ment into the box; and universal mounting incorporating the labor-saving QuickClick™ feature. Such labor-saving features make wire connections simple and fast, further reducing installed cost. These strobes and horn/strobes offer the broadest range of candela options. In ad- dition, they can operate on either 12V or 24V with no settings required. The device recognizes and self-adjusts to the correct current automatically. Temporal 3 or con- tinuous tone options continue to be avail- able, in either an electro-mechanical or 3 kHz pattern These strobes and horn/strobes incor- porate the same stylish, low profile design of the conventional Spectralert products, for a consistent and aesthetically pleasing appearance across the entire product line. The selectable strobe and horn/ strobe is available in either red or white. The devicesmount on a standard 4” x 4” x 11/2” backbox or a single gang 2” x 4” x 17/8” backbox using the universal mount- ing plate included with each Spectralert unit. An optional strobe sychronization mod- ule is available for compliance the Ameri- cans with Disabilities Act (ADA). The MDL (red) MDLW (white) synchronizes the strobes at 1 Hz and the horns to a tempo- ral 3 coded pattern. The synchronization modules mounts on a 4 11/16” x 4 11/16” x 2 1/8” backbox and supports two (2) Style Y (Class B) or one (1) Style Z (Class A) notification appliance circuit. A separate horn control input is available to allow silenceable audible devices and non- silenceable visual devices on the same pair or wires. Features • Operates on either12 VDC or 24 VDC • Widest Range of Candela Options: • 12V: 15 amd 15/75 candela • 24V: 15, 15.75, 30, 75 110 candela • Easy Candela Selection • Easy DIP Switch Selection for Horn Options • Eask Mounting with QuickClick™ • Synchronization avalable with optional MDL Sync•Circuit™ module • Meets UL1971, NFPA72, and ADA Signaling Requirements SpectrAlert Selectable Ouput Strobe and Horn/StrobeBuilding Intelligent Networks FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood, MA 02090 USA • Tel: 781-471-3000 • Fax: 781-471-3099 • www.firecontrolinstruments.com A Honeywell Company Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate.However, no responsibility is assumed by Fire Control Instruments for their use. Specifications subject to change without notice.© 2003 All Rights Reserved 9020-0562/Ver. 1.1 / Page 2 of 4 alednaC )Am(TNERRUCNAEMEGAREVA )Am(TNERRUCKAEP )Am(TNERRUCHSURNI V21tAV42tA21tAVV42tAV21tAV42tA V5.9V21V5.71V61V42V33V5.9V21V5.71V61V42V33V5.9V21V5.71V61V42V33 CDRWFCDRWFCDRWFCDRWFCDRWFCDRWFCDRWFCDRWFCDRWFCDRWFCDRWFCDRWFCDRWFCDRWFCDRWFCDRWFCDRWFCDRWF 51994856959444257424830483122722471951551531151731921561331103269497781992119711331771981562 57/5191111197968525265584344414ANANANANANAN391491951602551223ANANANANANAN98911131571771352 03ANANANANANAN087875863585342875571452741491751602921071721033741516973912138701321171581352 57ANANANANANAN441031001091827ANANANANANAN503435152034712815ANANANANANAN77511911571381552 011ANANANANANAN49117103181130139ANANANANANAN663605413073072434ANANANANANAN59311131181181742 Strobe only stceleStluafeD CDstlov@ABdmooRtnarebreveRLU 5.9 215.71614233 laropmeT emuloVwoL lacinahcemortcelE*07*4767670818 detpurretnIzH0003*175787770828 emuloVhgiH lacinahcemortcelE 67 9718182848 detpurretnIzH0003 77 1838284858 laropmeT-noN emuloVwoL lacinahcemortcelE 57 8718184868 detpurretnIzH0003 67 9738285878 emuloVhgiH lacinahcemortcelE 08 3868587888 detpurretnIzH0003 18 5878688888 Spectralert Current Tables Sound output guide * This tone only suitable for private mode use at rated voltage tested by UL. STCELESTLUAFED )Am(TNERRUCNAEMEGAREVA V21tAV42tA enoT woL/hgiH emuolV pmeT noN/ V5.9V21V5.71V61V42V33 CDRWFCDRWFCDRWFCDRWFCDRWFCDRWF -ortcelE .hcem hgiH pmeT4017827569525265585058535 noN9012908179616173696164776 woL pmeT2017807266505853535643594 noN4019837661645367585253685 .zH0003 .tpurretnI hgiH pmeT5019837660645366506259555 noN1114928373746475637567717 woL pmeT3017807367515953545744515 noN5019847763665468516456606 Horn/ Strobe 15 cd: STCELESTLUAFED )Am(TNERRUCNAEMEGAREVA V21tAV42tA enoT woL/hgiH emuolV pmeT noN/ V5.9V21V5.71V61V42V33 CDRWFCDRWFCDRWFCDRWFCDRWFCDRWF -ortcelE .hcem hgiH pmeT42141168578606273646552665 noN92191149188796181757668707 woL pmeT22141148275685861695157525 noN42161178670726375646757616 .zH0003 .tpurretnI hgiH pmeT52161178679626374666753685 noN13112169382827483797071847 woL pmeT32141148376695961606258545 noN52161188772746476676950736 Horn/ Strobe 15/75 cd: STCELESTLUAFED )Am(TNERRUCNAEMEGAREVA V42tA enoT woL/hgiH emuolV pmeT noN/ V61V42V33 CDRWFCDRWFCDRWF -ortcelE .hcem hgiH pmeT093937081737 noN9910148197878 woL pmeT681986676696 noN195937286787 .zH0003 .tpurretnI hgiH pmeT194957282757 noN20130188590919 woL pmeT781996777617 noN296967489708 STCELESTLUAFED )Am(TNERRUCNAEMEGAREVA V42tA enoT woL/hgiH emuolV pmeT noN/ V61V42V33 CDRWFCDRWFCDRWF -ortcelE .hcem hgiH pmeT4518316112019978 noN361641721311511101 woL pmeT051631111894938 noN55104161140140129 .zH0003 .tpurretnI hgiH pmeT55193181140100198 noN661841131711811501 woL pmeT151631211995958 noN65114191160170149 STCELESTLUAFED )Am(TNERRUCNAEMEGAREVA V42tA enoT woL/hgiH emuolV pmeT noN/ V61V42V33 CDRWFCDRWFCDRWF -ortcelE .hcem hgiH pmeT402971641031121801 noN312781751141731221 woL pmeT002771141621611401 noN502181641231621311 .zH0003 .tpurretnI hgiH pmeT502081841231221011 noN612981161541041621 woL pmeT102771241721711601 noN602281941431921511 Horn/ Strobe 30 cd: Horn/ Strobe 75 cd: Horn/ Strobe 110 cd: Building Intelligent Networks FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood, MA 02090 USA • Tel: 781-471-3000 • Fax: 781-471-3099 • www.firecontrolinstruments.com A Honeywell Company Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments for their use. Specifications subject to change without notice.© 2003 All Rights Reserved 9020-0562/Ver. 1.1 / Page 3 of 4 alednaC )Am(TNERRUCNAEMEGAREVA V21tAV42tA V5.9V21V5.71V61V42V33 CDRWFCDRWFCDRWFCDRWFCDRWFCDRWF 5150101147776536065674854495 57/5142194198987627275755469446 03ANANANANANAN2911176699598 57ANANANANANAN16116171112149601 011ANANANANANAN012902051151021131 STCELESTLUAFED )Am(TNERRUCNAEMEGAREVA V21tAV42tA enoT woL/hgiH emuolV pmeT noN/ V5.9V21V5.71V61V42V33 CDRWFCDRWFCDRWFCDRWFCDRWFCDRWF -ortcelE .hcem hgiH pmeT21171158781777478766779638 noN021421697968198819485919401 woL pmeT90141108385627863785076667 noN21171158882797579776084788 .zH0003 .tpurretnI hgiH pmeT41181168882787579776972758 noN221521899998491939888949701 woL pmeT90141118486627964795172667 noN31181198983708671807287719 Horn/ Strobe 15 cd: Strobe only: STCELESTLUAFED )Am(TNERRUCNAEMEGAREVA V21tAV42tA enoT woL/hgiH emuolV pmeT noN/ V5.9V21V5.71V61V42V33 CDRWFCDRWFCDRWFCDRWFCDRWFCDRWF -ortcelE .hcem hgiH pmeT131651001992868688847384788 noN931361111901790010011012910169901 woL pmeT82135159596718083866671718 noN1316510010013888789857689739 .zH0003 .tpurretnI hgiH pmeT3317511010013878789857587709 noN1414613111110013013013016940199211 woL pmeT82135169697718184876777618 noN2317511011014898881987882869 Horn/ Strobe 15/75 cd: STCELESTLUAFED )Am(TNERRUCNAEMEGAREVA V42tA enoT woL/hgiH emuolV pmeT noN/ V61V42V33 CDRWFCDRWFCDRWF -ortcelE .hcem hgiH pmeT6014216850148011 noN021731401321601131 woL pmeT001911878918301 noN7015217880198511 .zH0003 .tpurretnI hgiH pmeT7015217870178211 noN321931801621901431 woL pmeT101021979977301 noN8017210901129811 Horn/ Strobe 30 cd: STCELESTLUAFED )Am(TNERRUCNAEMEGAREVA V42tA enoT woL/hgiH emuolV pmeT noN/ V61V42V33 CDRWFCDRWFCDRWF -ortcelE .hcem hgiH pmeT571471631041911031 noN981781451851141151 woL pmeT961961821331611321 noN671571731341421531 .zH0003 .tpurretnI hgiH pmeT671571731241221231 noN291981851161441451 woL pmeT071071921431211321 noN771771041541721831 Horn/ Strobe 75 cd: STCELESTLUAFED )Am(TNERRUCNAEMEGAREVA V42tA enoT woL/hgiH emuolV pmeT noN/ V61V42V33 CDRWFCDRWFCDRWF -ortcelE .hcem hgiH pmeT42222961071541551 noN832532781881761671 woL pmeT812712161361241841 noN522322071371051061 .zH0003 .tpurretnI hgiH pmeT522322071271841751 noN142732191191071971 woL pmeT912812261461831841 noN622522371571351361 Horn/ Strobe 110 cd: Current measurements (Average RMS method) NOTE: The 12V 15/75 cd strobe was tested at the 9.5-17.5 volt-FWR/DC limits. All other 12 V strobes were tested at the 8-17.5 volt-FWR/DC limits. All 24V strobes were tested at the 16-33 volt-FWR/DC limits. This does not include the 80% low end or 110% high end voltage limits. SpectrAlert Selectable Ouput Strobe and Horn/Strobe Building Intelligent Networks FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood, MA 02090 USA • Tel: 781-471-3000 • Fax: 781-471-3099 • www.firecontrolinstruments.com A Honeywell Company Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments for their use. Specifications subject to change without notice.© 2003 All Rights Reserved 9020-0562/Ver. 1.1 / Page 4 of 4 SpectrAlert Selectable Ouput Strobe and Horn/Strobe Specifications Walk Test SpectrAlert horn/strobe and horn only work on “walk tests” with time durations of 4 seconds or greater Input terminals 12 to 18 AWG Dimensions Strobe and horn/strobe with universal plate 5” x 5 5/8” x 2 15/16” Strobe and horn/strobe with small footprint plate 3 3/8” x 5 5/8” x 2 5/16” Horn with universal mounting plate 5” x 5 5/8” x 1 5/16” Horn without mounting plate 2 15/16” x 5 5/16” x 15/16” Weight, horn only 7.2 0z. Weight, strobe and horn/strobe 8.8 oz. Mounting 4” x 4”x 1 1/2” or 2” x 4” x 17/8” standard boxes Indoor operating temperature 32°F to 120°F (0°C to 49°C) Maximum humidity 95% as tested per UL464 Weatherproof (horn and horn/strobe) Operating temperature 32°F to 150°F (0°C to 66°C) (outdoor strobe only) -40°F to 158°F (-40°C to 70°C) Voltages 12 or 24VDC and FWR unfiltered Operating Voltage Range* 12V: 10.5-17V; 24V: 20-30V Operating Voltage Range (with Sync•Circuit module MDL) 12V: 11-17V; 24V: 20-30V * These products should be operated within their rated voltage range; UL does test functional integrity to-20% and +10% of manufacturer’s stated ranges. deRetihWegatloValednaC*Am.gvA CDV.moN@ *Am.gvA **CDV.moN@ sebortS/nroHCM4221PWCM4221P42/21:elbatceleS dc011,57,03,57/51,51 __ sebortSCM4221SWCM4221S42/21:elbatceleS dc011,57,03,57/51,51 __ seirosseccA eludoMtiucriC•cnySLDMWLDM42/21AN11/0151/21 rofetalPgnitnuoMtnirptooFllamS ylnognaGelgniS PM-SWPM-SANANANAN trikSxoBkcaBtnuoMecafruSSBBWSBBANANANAN etalPgnitnuoMlasrevinU )tnemecalper( PM-DWPM-DANANANAN Ordering Information