HomeMy WebLinkAboutB16-2029 CALFIRE UNDERGROUND TANK INSPECTIONUnderground LPG Tank Inspection Form
%b California Department of Forestry and Fire Protection
Butte County Fire Department
176 Nelson Avenue, Oroville, CA 95965 ■ (530)
Property OwnAr- Property Location: City:
Inspector: 4 Iaspec ' n Date: / O / Permit #: APN: +i
ASME Tank Information: NFPA 58: 2001 edition
kApproved underground tank installed with no vehicle traffic shall be at least 6 inches below grade. NFPA 58: 32.9.1(a).
0 Approved interchangeable aboveground/underground installation, maximum depth. 12 inches below grade NFPA 58:32.9.1(d)
D Approved non -interchangeable underground installation shall have a minimum depth of 18 inches or provide adequate vehicle
protection for all appurtenances. NFPA 58:3.2.9.1(b)
Location of Tank: NFPA 58:2001 edition
11 YES ❑ NO Tanks of 125 -gallon water capacity and under at least 10 feet from all buildings and property lines. NFPA 58:
3.2.2.2
S D NO Capacity from 125 - 2000 gallons is at least 10 feet away from all buildings and property lines?
NFPA Table 58:3.22.2
Capacity from 2001 gallons and larger shall be 50 ft from buildings / property lines.
NFPA Table 58:32.2.2
YES ❑ NO All sources of ignition at least 10 feet away from tank appurtenances. NFPA 58: appendix figure I: 1(c)
T"K Installation: NFPA 58: 2001 edition
❑ NO Underground tank installed upon a level surface. NFPA 58: 3.2.9.1. (1).
ONO Adequate vehicle protection of tank appurtenances. NFPA 58:3.2.9. 1 (b), (c) & NFPA 58:A-5.4.2.2.
YES 0 NO Minimum 14 AWG corrosion resistant tracer wire (entrenched) being visible at riser or building.
NFPA 58: 3.2.16.9.
ES 0 NO Tanks shall be coated to protect against corrosion. NFPA 58 3.2.9.2(h), NFPA 58: 3.2.4, NFPA 58:A-
3.2.9.3(cxd).
Pressure Relief Devices: NFPA 58: 2001 edition
..9'YES 0 NO Adequate protection provided to prevent water or debris from entering the relief valve or discharge
piping. NFPA 58:32.11.4.
Underground tanks with less than 2000 gal. Capacity:
0 YES ONO If relief device discharges into manhole or protective shroud, the manhole shall be equipped with
ventilated louvers or passive system to provide ventilation. NFPA 58: 3.2.11.6 (See exceptions for
�� dispensing stations)
.P"T ES 0 NO If discharge piping has been installed has the relief valve capacity been verified as
adequately meeting its discharge capacity. NFPA 58:3.2.11.8, 2.3.2.4. (a).
Underground tanks with more than 2000 gal. Capacity:
A YES 0 NO Discharge from pressure relief is piped vertically and directly upward to a point at least 7 feet above the ground
level. NFPA 58:3.2.11.7 (See exceptions for dispensing stations)
Corrosion (Cathodic) Protection: NRA 58: 34.24.58: A 3.2.9.3(d). 58: A 3.2.2.4
Specify Type of Backfill Material:
Backfill Material:
0 Damp 0 Wet
0 NO Additional coating materials applied to surface areas disturbed during installation or shipment of tank
YES ❑ NO After installation of anode and prior to backfilling the anode bag(s) was pre-soaked with water.
0 YES 0 NO Installation site, anode bag, and backfill naturally wet due to weather or other conditions:
,cx ES 0 NO Anode bag lead wire accessible inside dome for testing.
OK to Enter in Trahit Date:
Underground LPG Tank Inspection Form— Mauer 6/7!07