Loading...
HomeMy WebLinkAboutTPM14-0003_Cal Fire Comments_051414.pdf1 Hickel, Rowland From:Damon, Matt@CALFIRE <matt.damon@fire.ca.gov> Sent:Wednesday, May 14, 2014 11:22 AM To:Hickel, Rowland Subject:RE: Scruby TPM14-0003 Follow Up Flag:Follow up Flag Status:Flagged Rowland,    Here are the comments for this project:     Construction, installation or development of buildings and/or roads, driveways, gates and bridges on  parcels/lots shall comply with current Butte County Improvement Standards.   Prior to building construction, provide an all‐weather access of at least 10 feet wide for residential, and 20 feet  wide for commercial, and vertical clearance of 15 feet that will allow for ingress and egress and accommodate a  40,000‐pound fire apparatus to within 150 feet of all structures.   13.01‐1 Requirement Class 1  A pressurized water supply for fire protection will not be required. The developer will install an automatic fire  sprinkler system in all new residential structures in accordance with the National Fire Protection Association  standard for the installation of sprinkler systems in one and two family dwellings and mobile homes, NFPA  Standard 13D.    Matt   From: Hickel, Rowland [mailto:rhickel@buttecounty.net] Sent: Monday, May 05, 2014 1:43 PM To: Damon, Matt@CALFIRE Subject: Scruby TPM14-0003 Hi Matt, I didn’t see any comments in Trakit for this project. The property is not located in an SRA or High Wildlife Hazard Area (it’s in Thermalito). Are you going to have any requirements/conditions? Thanks Rowland Hickel Senior Planner - Butte County Department of Development Services  7 County Center Drive  Oroville, CA 95965  (530) 538‐7150 – Phone  (530) 538‐7785 – Fax  rhickel@buttecounty.net